A cooling system is being designed for use at high elevation (5000 ft or 1500 m) where the outdoor air is very dry. The space with a high latent load,
Want to see the full answer?
Check out a sample textbook solutionChapter 3 Solutions
Heating Ventilating and Air Conditioning: Analysis and Design
Additional Engineering Textbook Solutions
Starting Out with C++: Early Objects (9th Edition)
Thinking Like an Engineer: An Active Learning Approach (4th Edition)
Java How to Program, Early Objects (11th Edition) (Deitel: How to Program)
Electric Circuits. (11th Edition)
Concepts Of Programming Languages
Introduction To Programming Using Visual Basic (11th Edition)
- In an air conditioning system, return air at 24°C dry-bulb temperature and 40% relative humidity is mixed with outdoor ambient air at 30°C dry-bulb temperature and 70% relative humidity. The dry air mass flow rate of outdoor air is 20% of the supply air mass flow rate to the space. The pressure is constant at 101.3 kPa.-Calculate the dry-bulb temperature of the supply air in °C.-The humidity ratio of the supply air.-The enthalpy of supply air in kJ/kg.arrow_forwardI need this with perfect answer 143103 An air-conditioning system operates at a total pressure of 1 atm and consists of a heating section and an evaporative cooler. Air enters the heating section at 15°C and 55 percent relative humidity at a rate of 30 m3 /min, and it leaves the evaporative cooler at 25°C and 45 percent relatively humidity. Determine (a) the temperature and relative humidity of the air when it leaves the heating section, (b) the rate of heat transfer in the heating section, and (c) the rate of water added to air in the evaporative cooler.arrow_forwarda stream of outdoor air is mixed with a stream of return airin an airconditioning system that operates at 101 kpa pressure.the flow rate of outdoor air is 3kg/s and its condition is 30 C Tbd and 23 C Twb. the flow rate of return air is 2.5 kg/s and its condition is 15 C Twb and 60% RH. Determine:a - enthalpy of mixture b - humidity ratio of mixturec- dry bulb temperature of mixtured- dry bulb temperature by the weighted average of the dry bulbtemperature of the entering streamsarrow_forward
- An incoming air flow of 200 m3/h at a temperature of 20°C and a humidity ratio of 0.012 kgv/kga is mixed in a chamber with another incoming air flow of 500 m3/h at a temperature of 15°C and a humidity ratio of 0.008 kgv/kga. Based on the corresponding mass flow rates (and NOT the original volumetric flow rates) determine: a) The mass flow rate of the mixed air (i.e., the combination of the two flows) leaving the chamber in kg/s. b) The temperature of the mixed air leaving the chamber. Please use PyscPro software for solving this question. Notes: For part (a), you will first need to find the density or specific volume for each state (density = 1/specific volume). The units the 'v' and 'a' are intended as subscripts: · kgv = kg_v = kgv = kilogram(s) [vapour] kga = kg_a =kga = kilogram(s) [air]arrow_forwardAn air-conditioning system operates at a total pressure of 1 atm and consists of a heating section and anevaporative cooler. Air enters the heating section at 14°C and 60 percent relative humidity at a rate of 30m3/min, and it leaves the evaporative cooler at 25°C and 45 percent relatively humidity. Determine (a) thetemperature and relative humidity of the air when it leaves the heating section, (b) the rate of heat transfer in theheating section, and (c) the rate of water added to air in the evaporative cooler.arrow_forward28 m3/min of air at 43°C dry bulb temperature and 15% relative humidity are mixed adiabatically with 14.0 m3/min of air at 18°Cdb temperature and 90% relative humidity. Calculate for the final Humidity Ratio (kgwv/kgda)? <Psat 43°C = 8.649 kPa, Psat 18°C = 2.064kPa>arrow_forward
- The cooling load of a building is estimated at 60 000 Btu/hr, of which 25 % is latent heat. The space is to be maintained at 75 F db and S0 % relative humidity. The outdoor air is at 110 F db and 40 % relative humidity. The air is supplied to the space at 55 F. If the sensible heat factor of the cooling equipment is SHF-0.6 and by using the psychrometric chart The supplied air mass tlow rate is around Choose The outside mass flow rate is around Choose. The cooling coil total heat rate is around Choose The sensible heat rate of the cooling coil is around Choose The latent heat rate of the cooling coil is around: Choosearrow_forwardA space is to be maintained at 22C and 50% relative humidity. The sensible heat load is 100 kW, and the latent heat load is 15 kW. Outside air is at 38C DB and 25C WB temp. Air is supplied to the space at 13C. If all-outside air system (no recirculation) is to be implemented, determine: (a) the cooling capacity in tons; (b) capacity of supply air fan in cmh; and (c) the coil bypass factor.arrow_forwardFor summer air conditioner application of a room; The sensible heat gain of the room is 13kW, the latent heat gain is 3kW, and the design conditions are determined as 21°C relative humidity 55%. Outdoor air conditions are at 42 °C 35% relative humidity, and the relative humidity of the air passing through the cooling coil at the exit from the coil will be 95%. Since the amount of air blown into the environment is 5000m^3/h, the return air is 700 m^3/h: a- Show the event in the psychometric diagram according to the data of the air conditioning application. b-Find the dry bulb temperature of the air at the outlet of the cooling coil. c-Calculate the amount of air that is bypassed and not by-passed from the coil B Mahalarrow_forward
- Read the question carefully. Don't miss any calculations. The recycled duct air in a centralized air conditioning system takes in air at a rate of 60 m3/min with a dry bulb temperature of 20 oC and 30% relative humidity. The recycled air is mixed adiabatically with fresh outdoor air at a rate of 80 m3/min with a dry bulb temperature of 30 oC and 50% relative humidity. Calculate the volumetric flow rate, dry bulb temperature and relative humidity of the mixed air stream. Use the psychrometric chart to get property data and plot the process on the psychrometric chart.arrow_forwardAir enters a cooling tower at a rate of 1100 cubic meters per minute, at 15°C and 65% relative humidity. Atmospheric pressure is 100 kPa. Water enters the tower at 38°C and leaves at 17°C. Air leaves the tower at 31°C and saturated. Using a psychrometric chart calculate the absolute humidity of the air leaving the cooling tower. 0.029 kg water vapour/kg air 0.069 kg water vapour/kg air O 0.0101 kg water vapour/kg air 0.364 kg water vapour/kg airarrow_forwardAir enters the heating section of an air-conditioning at 1atm, 10C, and 70 percent relative humidity at a rate of 35m^3/min, and it leaves the humidifying section at 20C with a relative humidity of 90 percent. If the humidifier supplies wet steam at 100C, determine: The temperature and relative humidity of the air leaving the heating section The rate of heat transfer in the heating sectionarrow_forward
- Elements Of ElectromagneticsMechanical EngineeringISBN:9780190698614Author:Sadiku, Matthew N. O.Publisher:Oxford University PressMechanics of Materials (10th Edition)Mechanical EngineeringISBN:9780134319650Author:Russell C. HibbelerPublisher:PEARSONThermodynamics: An Engineering ApproachMechanical EngineeringISBN:9781259822674Author:Yunus A. Cengel Dr., Michael A. BolesPublisher:McGraw-Hill Education
- Control Systems EngineeringMechanical EngineeringISBN:9781118170519Author:Norman S. NisePublisher:WILEYMechanics of Materials (MindTap Course List)Mechanical EngineeringISBN:9781337093347Author:Barry J. Goodno, James M. GerePublisher:Cengage LearningEngineering Mechanics: StaticsMechanical EngineeringISBN:9781118807330Author:James L. Meriam, L. G. Kraige, J. N. BoltonPublisher:WILEY