Heating Ventilating and Air Conditioning: Analysis and Design
Heating Ventilating and Air Conditioning: Analysis and Design
6th Edition
ISBN: 9780471470151
Author: Faye C. McQuiston, Jeffrey D. Spitler, Jerald D. Parker
Publisher: Wiley, John & Sons, Incorporated
bartleby

Videos

Textbook Question
Book Icon
Chapter 3, Problem 3.53P

An interior zone of a large building is designed to have a supply air-flow rate of 5000 cfm (2.4 m3/s). The cooling load is constant at 10 tons (35 kW) with a SHF of 0.8 year-round. Indoor conditions are 75 F (24 C) db and 50 percent relative humidity (RH). (a) What is the maximum air dry bulb temperature and humidity ratio that would satisfy the load condition using all outdoor air? (b) Consider a different time when the outdoor air has a temperature of 40 F (4 C) db and 20 percent relative humidity. Return air and outdoor air may be mixed to cool the space. but humidification ill be required. Assume that saturated water vapor at 14.7 psia (101 kPa) is used to humidify the mixed air, and compute the amounts of outdoor and return air in cfm (m3/s). (c) At another time, outdoor air is at 65 F (18 C) db with a relative humidity of 90 percent. The cooling coil is estimated to have a minimum apparatus dew point of 45 F (7.2 C). What amount of outdoor and return air should be mixed before entering the coil to satisfy the given load condition? (d) What is the refrigeration load for the coil of part (c) above?

Blurred answer
Students have asked these similar questions
Q2) Air is supplied to an automobile cabin from the outside, where the temperature is 20F and the relative humidity is 70%. It is desired to keep the cabin at 70F and Ø = 60%. Hoe many pounds of water must be supplied to each pound of air entering the car cabin if these conditions are to be met? The barometric pressure is 29.5 in.Hg. %3D Ans. (0.00797 lbs/Ibdry air)
ASHRAE standard 55, Thermal Environmental Conditions for Human Occupancy, notes that for thermal comfort purposes, the indoor temperature should range from approximately 67ºF to 82°F (19.4ºC to 27.8ºC), and systems designed to control humidity must be able to maintain a dew-point temperature of 16.8°C (62.2°F). ASHRAE standard 62.1, Ventilation and Acceptable Indoor Air Quality, recommends that relative humidity in occupied spaces be controlled to less than 65% to reduce the likelihood of conditions that can lead to microbial growth. Determine the minimum allowable indoor temperature that will ensure a humidity control system designed according to ASHRAE standard 55 will also satisfy the humidity requirements of standard 62.1
In a place where a summer air-conditioning plant will be installed, 40% of the air entering the air-conditioning plant is the fresh air, and 60% is the return (bypass) air. The sensible heat gain of the place is 10 kW. and the latent heat gain is 2.5 kW.> Outdoor conditions: 32 °C DB, %50 RH.> Indoor conditions: 20 °C DB. %50 RH.> Take the relative humidity of the air passing through the cooling coil 90% at the coil outlet. > The total air flow rate in the mixing chamber is 3000 m3/h> Take the density of the air as 1.2 kg/m3Based on the above.a) Show the process on a psychrometric diagram. b) Calculate the amount of fresh air. c) What is the value of enthalpy of blowing air. d) Calculate the ratio of by-pass air at cooling coil. e) Calculate the flow rate of by-passed air.

Chapter 3 Solutions

Heating Ventilating and Air Conditioning: Analysis and Design

Ch. 3 - The environmental conditions in a room are to be...Ch. 3 - Air enters a cooling coil at the rate of 5000 cfm...Ch. 3 - Air flowing in a duct has dry and wet bulb...Ch. 3 - Air is humidified with the dry bulb temperature...Ch. 3 - Air at 38 C db and 20 C wb is humidified...Ch. 3 - Two thousand cfm (1.0 m3/s) of air at an initial...Ch. 3 - Air at 40 F (5 C) db and 35 F (2 C) wb is mixed...Ch. 3 - Rework Problem 3-25, using Chart 1a, with the...Ch. 3 - The design cooling load for a zone in a building...Ch. 3 - Assume that the air in Problem 3-22 is supplied to...Ch. 3 - The sensible heat loss from a space is 500,000...Ch. 3 - Air enters a refrigeration coil at 90 Fdb and 75...Ch. 3 - A building has a total heating load of 200,000...Ch. 3 - Reconsider Problem 3-36 for an elevation of 5000...Ch. 3 - The system of Problem 3-34 has a supply air fan...Ch. 3 - An evaporative cooling system is to be used to...Ch. 3 - A cooling system is being designed for use at high...Ch. 3 - Consider a space heating system designed as shown...Ch. 3 - A variable-air-volume VAV cooling system is a type...Ch. 3 - Rework Problem 3-43 for an elevation of 5000 feet...Ch. 3 - The design condition for a space is 77 F (25 C) db...Ch. 3 - Rework Problem 3-45 for an elevation of 5000 feet...Ch. 3 - It is necessary to cool and dehumidify air from 80...Ch. 3 - Conditions in one zone of a dual-duct conditioning...Ch. 3 - Rework Problem 3-48 for an elevation of 5000 ft...Ch. 3 - A water coil in Problem 3-48 cools return air to...Ch. 3 - A multizone air handler provides air to several...Ch. 3 - Under normal operating conditions a zone has a...Ch. 3 - An interior zone of a large building is designed...Ch. 3 - Outdoor air is mixed with room return air to...Ch. 3 - Consider an enclosed swimming pool. The pool area...Ch. 3 - One particular zone served by a multizone air...Ch. 3 - A research building requires 100 percent outdoor...Ch. 3 - A space requires cooling in the amount of 120,000...

Additional Engineering Textbook Solutions

Find more solutions based on key concepts
Knowledge Booster
Background pattern image
Mechanical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Elements Of Electromagnetics
Mechanical Engineering
ISBN:9780190698614
Author:Sadiku, Matthew N. O.
Publisher:Oxford University Press
Text book image
Mechanics of Materials (10th Edition)
Mechanical Engineering
ISBN:9780134319650
Author:Russell C. Hibbeler
Publisher:PEARSON
Text book image
Thermodynamics: An Engineering Approach
Mechanical Engineering
ISBN:9781259822674
Author:Yunus A. Cengel Dr., Michael A. Boles
Publisher:McGraw-Hill Education
Text book image
Control Systems Engineering
Mechanical Engineering
ISBN:9781118170519
Author:Norman S. Nise
Publisher:WILEY
Text book image
Mechanics of Materials (MindTap Course List)
Mechanical Engineering
ISBN:9781337093347
Author:Barry J. Goodno, James M. Gere
Publisher:Cengage Learning
Text book image
Engineering Mechanics: Statics
Mechanical Engineering
ISBN:9781118807330
Author:James L. Meriam, L. G. Kraige, J. N. Bolton
Publisher:WILEY
The Refrigeration Cycle Explained - The Four Major Components; Author: HVAC Know It All;https://www.youtube.com/watch?v=zfciSvOZDUY;License: Standard YouTube License, CC-BY