Heating Ventilating and Air Conditioning: Analysis and Design
Heating Ventilating and Air Conditioning: Analysis and Design
6th Edition
ISBN: 9780471470151
Author: Faye C. McQuiston, Jeffrey D. Spitler, Jerald D. Parker
Publisher: Wiley, John & Sons, Incorporated
bartleby

Videos

Textbook Question
Book Icon
Chapter 3, Problem 3.15P

Air enters a cooling coil at the rate of 5000 cfm (2.4 m3/s) at 80 F (27 C) db, 68 F (20 C) wb and sea-level pressure. The air leaves the coil at 55 F (13 C) db, 54 F (12 C) wb. (a) Determine the SHF and the apparatus dew point. (b) Compute the total and sensible heat transfer rates from the air.

Blurred answer
Students have asked these similar questions
Problem 2. Consider a Variable Air Volume (VAV) system, which serves for two rooms. The air temperature at the exist of the cooling coil is 10 °C. The design room temperature is 24 °C for both rooms. For room 1, the sensible and latent heat load is 60 and 10 kW, respectively. For room 2, the sensible and latent heat load is 40 and 10 kW, respectively. Determine (1) The mass flow rate for each room in kg/s; (2) The actual relative humidity of each room.
An auditorium is designed to seat 4500 people. The ventilation rate is 1.62 x 107 ft3/hr of outside air. The outside temperature is 0oF dry bulb, and outside pressure is 14.6 psia. Air leaves the auditorium at 70oF dry bulb. There is no recirculation. The furnace has a capacity of 1,250,000 Btu/hr. The temperature at which the air should enter the auditorium is most nearly
* OMANTEL I. A moodle1.du.edu.om IVidi Keu out or 4.U P Flag question Air enters a 28-cm diameter pipe steadily at 200 kPa and 20°C with a velocity of 5 m/s. Air is heated as it flows, and leaves the pipe at 180 kPa and 40°C. The volume flow rate of air at the inlet (m3/s) is Select one: a. 0.608 O b. 0.408 O c. 0.508 d. 0.308 Droviouo nagn Noxt naan

Chapter 3 Solutions

Heating Ventilating and Air Conditioning: Analysis and Design

Ch. 3 - The environmental conditions in a room are to be...Ch. 3 - Air enters a cooling coil at the rate of 5000 cfm...Ch. 3 - Air flowing in a duct has dry and wet bulb...Ch. 3 - Air is humidified with the dry bulb temperature...Ch. 3 - Air at 38 C db and 20 C wb is humidified...Ch. 3 - Two thousand cfm (1.0 m3/s) of air at an initial...Ch. 3 - Air at 40 F (5 C) db and 35 F (2 C) wb is mixed...Ch. 3 - Rework Problem 3-25, using Chart 1a, with the...Ch. 3 - The design cooling load for a zone in a building...Ch. 3 - Assume that the air in Problem 3-22 is supplied to...Ch. 3 - The sensible heat loss from a space is 500,000...Ch. 3 - Air enters a refrigeration coil at 90 Fdb and 75...Ch. 3 - A building has a total heating load of 200,000...Ch. 3 - Reconsider Problem 3-36 for an elevation of 5000...Ch. 3 - The system of Problem 3-34 has a supply air fan...Ch. 3 - An evaporative cooling system is to be used to...Ch. 3 - A cooling system is being designed for use at high...Ch. 3 - Consider a space heating system designed as shown...Ch. 3 - A variable-air-volume VAV cooling system is a type...Ch. 3 - Rework Problem 3-43 for an elevation of 5000 feet...Ch. 3 - The design condition for a space is 77 F (25 C) db...Ch. 3 - Rework Problem 3-45 for an elevation of 5000 feet...Ch. 3 - It is necessary to cool and dehumidify air from 80...Ch. 3 - Conditions in one zone of a dual-duct conditioning...Ch. 3 - Rework Problem 3-48 for an elevation of 5000 ft...Ch. 3 - A water coil in Problem 3-48 cools return air to...Ch. 3 - A multizone air handler provides air to several...Ch. 3 - Under normal operating conditions a zone has a...Ch. 3 - An interior zone of a large building is designed...Ch. 3 - Outdoor air is mixed with room return air to...Ch. 3 - Consider an enclosed swimming pool. The pool area...Ch. 3 - One particular zone served by a multizone air...Ch. 3 - A research building requires 100 percent outdoor...Ch. 3 - A space requires cooling in the amount of 120,000...
Knowledge Booster
Background pattern image
Mechanical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Elements Of Electromagnetics
Mechanical Engineering
ISBN:9780190698614
Author:Sadiku, Matthew N. O.
Publisher:Oxford University Press
Text book image
Mechanics of Materials (10th Edition)
Mechanical Engineering
ISBN:9780134319650
Author:Russell C. Hibbeler
Publisher:PEARSON
Text book image
Thermodynamics: An Engineering Approach
Mechanical Engineering
ISBN:9781259822674
Author:Yunus A. Cengel Dr., Michael A. Boles
Publisher:McGraw-Hill Education
Text book image
Control Systems Engineering
Mechanical Engineering
ISBN:9781118170519
Author:Norman S. Nise
Publisher:WILEY
Text book image
Mechanics of Materials (MindTap Course List)
Mechanical Engineering
ISBN:9781337093347
Author:Barry J. Goodno, James M. Gere
Publisher:Cengage Learning
Text book image
Engineering Mechanics: Statics
Mechanical Engineering
ISBN:9781118807330
Author:James L. Meriam, L. G. Kraige, J. N. Bolton
Publisher:WILEY
The Refrigeration Cycle Explained - The Four Major Components; Author: HVAC Know It All;https://www.youtube.com/watch?v=zfciSvOZDUY;License: Standard YouTube License, CC-BY