Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN: 9780133923605
Author: Robert L. Boylestad
Publisher: PEARSON
expand_more
expand_more
format_list_bulleted
Concept explainers
Textbook Question
Chapter 24, Problem 42P
A balanced, three-phase, Y-connected load has a line voltage of 208 and a total power consumption of 1200 W at a leading power factor of 0.6. Find the impedance of each phase in rectangular coordinates.
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
Three Impedances each of (9 - j18)N are
connected in mesh across a three-phase 415V ac
supply. Determine the phase current, line current,
active power, reactive power drawn from supply.
Also draw the Phasor diagram for the mesh
connection and marks the Line current ,phase
current line voltage and phase angle between
phase current and pahse voltage.
phase current (Ip)
Line current
real power
reactive power
Two delta connected loads are connected in parallel and powered by a balanced Y-connectedsource. The smaller of two loads draws 10 kVA at a lagging power factor of 0.75 and the largerdraws 25 kVA at a leading power factor of 0.8. The line voltage is 400 V. Calculate a) The powerfactor at which the source is operating. b) The total power drawn by the two loads. c) The phasecurrent of each load.
A 30-0 resistor, a 15-02 inductive reactance, and a 12-02 capacitive reactance
are connected in parallel across a 120-V 60-Hz line. Find (a) the phasor
branch currents, (b) total current and phase angle, (c) impedance, and (d)
power drawn by the circuit.
Chapter 24 Solutions
Introductory Circuit Analysis (13th Edition)
Ch. 24 - A balanced V load having a 10 resistance in each...Ch. 24 - Repeat Problem 1 if each phase impedance is...Ch. 24 - Repeat Problem 1 if each phase impedance is...Ch. 24 - The phase sequence for the Y-Y system in Fig....Ch. 24 - Repeat Problem 4 if each phase impedance are...Ch. 24 - Repeat Problem 4 if each phase impedance is...Ch. 24 - For the system in Fig. 24.43, find the magnitude...Ch. 24 - Computer the magnitude of the voltage EAB for the...Ch. 24 - For the Y-Y system in Fig. 24.45: a. Find the...Ch. 24 - For the Y-Y system of Fig. 24.46 the impedance of...
Ch. 24 - A balanced load having a 20 resistance in each...Ch. 24 - Repeat Problem 11 if each phase impedance is...Ch. 24 - Repeat Problem 11 if each phase impedance is...Ch. 24 - The phase sequence for the Y- system in Fig....Ch. 24 - Repeat Problem 14 if each phase impedance is...Ch. 24 - Repeat Problem 14 if each phase impedance are...Ch. 24 - Prob. 17PCh. 24 - For the connected load in Fig. 24.49: a. Find the...Ch. 24 - A balanced V load having a 30 resistance in each...Ch. 24 - Repeat Problem 19 if each phase impedance is...Ch. 24 - Prob. 21PCh. 24 - Prob. 22PCh. 24 - Prob. 23PCh. 24 - Repeat Problem 22 if each phase impedance is...Ch. 24 - Prob. 25PCh. 24 - Prob. 26PCh. 24 - Prob. 27PCh. 24 - The phase sequence for the - system in Fig....Ch. 24 - Repeat Problem 28 if each phase impedance is...Ch. 24 - Repeat Problem 28 if each phase impedance is...Ch. 24 - Prob. 31PCh. 24 - Prob. 32PCh. 24 - Prob. 33PCh. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - Prob. 35PCh. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - Prob. 38PCh. 24 - Prob. 39PCh. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - A balanced, three-phase, -connected load has a...Ch. 24 - A balanced, three-phase, Y-connected load has a...Ch. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - The Y-Y system in Fig. 24.53 has a balanced load...Ch. 24 - Prob. 45PCh. 24 - Prob. 46PCh. 24 - Repeat Problem 46 for the network in Fig. 24.47.Ch. 24 - For the three-wire system in Fig. 24.55, properly...Ch. 24 - Sketch three different ways that two wattmeters...Ch. 24 - For the Y- system in Fig. 24.56: Determine the...Ch. 24 - For the system in Fig. 24.57: Calculate the...Ch. 24 - For the three-phase, three-wire system in Fig....
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- Draw a 3-phase wye-connected generator with transmission lines connected to a 3-phase delta-connected load. Assume the lines connecting them have an inductance of j5 per phase. The generated voltages are 120 Vrms with phase 'a' having a phase angle of 0°. The loads are 10 Ohm resistors per phase. When drawing, make sure to label all 3 phases with voltage phasors, line inductances, and load resistances.arrow_forwardThree Impedances each of (12 – j20)Q are connected in mesh across a three-phase 415V ac supply. Determine the phase current, line current, active power, reactive power drawn from supply. Also draw the Phasor diagram for the mesh connection and marks the Line current ,phase current line voltage and phase angle between phase current and pahse voltage phase current (Ip) Line current real power reactive powerarrow_forwardA balanced delta-connected load is supplied by a 60 Hz 3-phase source with a line voltage of 240 V. Each load phase draws 6kW at a lagging power factor of 0.8. Calculate: a. The load impedance per phase b. The line current c. The value of the capacitance needed to be connected in parallel with each load to minimize the current from the source (PF=1)arrow_forward
- 10 Ω m I₁ j4 Ω + I₂ ~ Vs E₁ || 2:1 The load on the right is absorbing 650 W -j200 VAR. V₁ = 80 / 0° V. + V₁ Iarrow_forwardA balanced delta-connected load is supplied by a 50-Hz three-phase source with a line voltageof 240 V. Each load phase draws 6 kW at a lagging power factor of 0.8. Find:a) the load impedance per phaseb) the line currentc) the value of capacitance needed to be connected in parallel with each load phase tominimize the current from the sourcearrow_forwardA balanced load is connected in star across a 3 phasec415V 50Hz supply. The load consists of a coil of resistance 25 ohms and inducrance 0.5 henry in paeallel with a purw resistance of 28 ohms and a pure capaciror of 60microfarads capacitance ,in each branch. Calculate a. The line currentsarrow_forward
- There is an installation with two equal three-phase loads of 150 kW each and a power factor of 0.9 in lagging. By connecting a pure reactive element in parallel, the reactive power at the input of the installation is 160 kVARS, with a lagging power factor. It can be said that:A)Capacitors were connected and the fp improved. B) Capacitors were connected and the fp improved. C) Reactors were connected and the fp improved. D)Reactors were connected and fp improved. E) None of the abovearrow_forwardQuestion 1: Based on figure below: a. Find the total impedance Z, in polar form b. Draw the impedance diagram c. Find the current I and voltages VR, V, and Vc in phasor form d. Draw the phasor diagram of the voltages E, VR, Viand Vc, and the current I. e. Verify Kirchhoff's voltage law around the closed loop. f. Find the average power delivered to the circuit g. Find the power factor of the circuit, and indicate whether it is leading or lagging. h. What happened if Xc= 20 ? Please explain. R- 40 X, = 6N Xc = 10 N %3D + UR + UL + vc e = 70.7 sin 377t|arrow_forwardA delta connected load of impedances (6 + j9) ohms each is supplied through a line having an impedance of (1 + j2) ohms. The supply voltage is balanced 3-phase, 400 V, 60 Hz mains. Find the total power drawn by the load.arrow_forward
- For the given circuit below a. Calculate E, IR, and IL, in phasor form.b. Calculate the total power factor (leading or lagging) and the average power delivered to the circuit.c. Draw the admittance diagram and draw the phasor diagram of the currents Is, IR, and IL, and the voltage E.arrow_forward2. Three impedances Za , Zb and Ze are connected in parallel. If at 60 hz , Za = 3 + j4 , Zb = 4 – j4 and Ze = 0 + j3 ohms. Solve for the total impedance and power factor of the circuit.arrow_forwardThe following loads are served by a balanced three-phase source: Load 1: 18 kVA at 0.8 pf lagging Load 2: 8 kVA at 0.8 pf leading Load 3: 12 kVA at 0.75 pf lagging. Give the complex power expression for Load 3. Select one: O a. 29.80 +j13.94 O b. O c. 9.00+ j7.94 kVA 6.40 -j4.80 KVA O d. 32.90225.07° KVA O e. 14.40 +j10.80 kVAarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
What is the Difference Between Single Phase and Three Phase???; Author: Electrician U;https://www.youtube.com/watch?v=FEydcr4wJw0;License: Standard Youtube License