Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN: 9780133923605
Author: Robert L. Boylestad
Publisher: PEARSON
expand_more
expand_more
format_list_bulleted
Concept explainers
Question
Chapter 24, Problem 25P
To determine
(a)
Phase voltage of generator.
To determine
(b)
Phase voltage of load.
To determine
(c)
Phase current of load.
To determine
(d)
Value of line current.
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
Consider the three phase generator below: a) If the stator rotates at 2400 rpm, what is the frequency of the voltage generated? b) If the generator is connected to a balanced, wye-connected, resistive load as shown below and a phase current of 100 A is required, what is the phase voltage that the generator must supply? What is the minimum power rating (in MVA) the three phase generator can have?
A wye-connected, 3-phase generator is rated 90 MW, 13.8kV and 0.9 pf. The dc resistance of the armature is obtained by connected two of its terminals to a 6 Vdc source. The current drawn by the armature is 87.6 A. What is the percent effective resistance of the armature of the generator?
A wye-connected, 3-phase generator is rated 90 MW, 13.8kV and 0.9 pf. The dc resistance of the armature
is obtained by connected two of its terminals to a 6 Vdc source. The current drawn by the armature is 87.6
A. What is the percent effective resistance of the armature of the generator?
b. 2.2
d. 4.5
a. 2.7
c. 3.1
Chapter 24 Solutions
Introductory Circuit Analysis (13th Edition)
Ch. 24 - A balanced V load having a 10 resistance in each...Ch. 24 - Repeat Problem 1 if each phase impedance is...Ch. 24 - Repeat Problem 1 if each phase impedance is...Ch. 24 - The phase sequence for the Y-Y system in Fig....Ch. 24 - Repeat Problem 4 if each phase impedance are...Ch. 24 - Repeat Problem 4 if each phase impedance is...Ch. 24 - For the system in Fig. 24.43, find the magnitude...Ch. 24 - Computer the magnitude of the voltage EAB for the...Ch. 24 - For the Y-Y system in Fig. 24.45: a. Find the...Ch. 24 - For the Y-Y system of Fig. 24.46 the impedance of...
Ch. 24 - A balanced load having a 20 resistance in each...Ch. 24 - Repeat Problem 11 if each phase impedance is...Ch. 24 - Repeat Problem 11 if each phase impedance is...Ch. 24 - The phase sequence for the Y- system in Fig....Ch. 24 - Repeat Problem 14 if each phase impedance is...Ch. 24 - Repeat Problem 14 if each phase impedance are...Ch. 24 - Prob. 17PCh. 24 - For the connected load in Fig. 24.49: a. Find the...Ch. 24 - A balanced V load having a 30 resistance in each...Ch. 24 - Repeat Problem 19 if each phase impedance is...Ch. 24 - Prob. 21PCh. 24 - Prob. 22PCh. 24 - Prob. 23PCh. 24 - Repeat Problem 22 if each phase impedance is...Ch. 24 - Prob. 25PCh. 24 - Prob. 26PCh. 24 - Prob. 27PCh. 24 - The phase sequence for the - system in Fig....Ch. 24 - Repeat Problem 28 if each phase impedance is...Ch. 24 - Repeat Problem 28 if each phase impedance is...Ch. 24 - Prob. 31PCh. 24 - Prob. 32PCh. 24 - Prob. 33PCh. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - Prob. 35PCh. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - Prob. 38PCh. 24 - Prob. 39PCh. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - A balanced, three-phase, -connected load has a...Ch. 24 - A balanced, three-phase, Y-connected load has a...Ch. 24 - Find the total watts, volt-amperes reactive,...Ch. 24 - The Y-Y system in Fig. 24.53 has a balanced load...Ch. 24 - Prob. 45PCh. 24 - Prob. 46PCh. 24 - Repeat Problem 46 for the network in Fig. 24.47.Ch. 24 - For the three-wire system in Fig. 24.55, properly...Ch. 24 - Sketch three different ways that two wattmeters...Ch. 24 - For the Y- system in Fig. 24.56: Determine the...Ch. 24 - For the system in Fig. 24.57: Calculate the...Ch. 24 - For the three-phase, three-wire system in Fig....
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- 1. What is the main direct cause of reactive power in AC system? A. Resistance of transmission lines B. Inductance and capacitance in the loads C. Ideal transformer connected in the system D. Power produced by generator 2. "Reactive power in a system is dissipated generally as thermal energy?" A. TRUE B. FALSE 3. Which of the following statements are correct for three phase circuit: A. Sum of all the three phase currents is zero in unbalanced network B. Total power transfer to load is constant with time C. Neutral conductor is same size in terms of material used as in single phase conductors D. Net apparent power consumed is equal to real powerarrow_forwardDoes an open connection permit balanced three-phase operation? - (a) Yes (b) Noarrow_forward1a)Analyze the circuit in Figure 1, consider R = 10 kQ and C = 10 nF. Obtain the mathematical equation for the equivalent impedance seen by the generator as a function of frequency. By voltage division obtain the mathematical relationship for the voltage across the capacitor and resistor as a function of VF and frequency. Perform all the circuit analysis (voltages, impedances, currents, waveforms). 1b) For the conditions in the previous item, deduce the value of the frequency that satisfies |XC| = R. Vf f=4 kHz R=1 kΩ C=10 nF Figure 1. Measurement circuit #1. Y X ORCarrow_forward
- Design a three-phase system such that the phase current in the generator, lines and charging phase is the same. The phase voltage in the generator must be 1000 [V] with ACB sequence. The connected load must be such that the phase current in each load is 10 [A] and its power factor is 0.97 “lagging”.arrow_forwardThe input power to a 3-phase load is measured as 16kW. If the line current and power factor of the load are 21 A and 0.8 , then the value of line voltage is The field winding of DC. generator has capable of carrying the full-load current and it is usually made few turns of heavy gauge wire. separately excited Compound Shunt O Seriesarrow_forwardIf the load is connected to the generator thgrough an inductive line and the voltage at the load side is the same as the voltage at the terminals of the generator, which of the following must be true? O A. The reactive power is flowing from the generator to the load and from load to the generator at the same time. O B. The load is disconnected, and no power is delivered to the load. O C. The load has a poor power factor and it's absorbing too much reactive power. O D. None of the other choices are correct O E. The generator is unable to produce reactive power; therefore, the reactive power is flowing from the load to the generator.arrow_forward
- Two generators operating in parallel supplying a total load current of 160 A. The terminal volage of generator A falls from 246 Von no load to 230 V when the current output is 100 A; The terminal volatge of generator B falls from 250 V on no load to 230 Vwhen the current output is 80 A. The external characteristics are rectilinear. determine the:a) busbar voltage. b) Current delivered by the generator A.c) kW shared by generator Aarrow_forwardThree phase alternators are invariably connected in star so as to a. Reduce the size of stator conductors usedb. Increase the terminal voltagec. Reduce magnetic losses d. All of the abovearrow_forwardA generator having emf 7sint Volts is connected in series with 8 Ohm resistor and an inductor of 2 Henrys. Find b) the current, I after 15 minutes.arrow_forward
- Can you explain the given questions in an original way? Single Phase and Three Phase Principles • Single Phase Generators • Two Phase Generatorsarrow_forwardA synchronous generator having ratings of 100 MVA operates on a full load at a frequency of 50 Hz. The load suddenly reduced to 60 MVA. The steam valve begins to close after 0.7 second due to time lag in the governor system. What would be the change in frequency that occurs in this time. Use generator capacity of H = 4 kW-s/kVA. Answer Choices: a. 1.72 Hz b. 1.02 Hz c. 1 Hz d. 0.72 Hzarrow_forward32. The incremental cost characteristics of two generators delivering a load of 200 MW are as follows: dF = 2.0 + 0.01 P, dP, dP dF, -= 1.6 + 0.02 P, For economic operation the generators P, and P, should be (a) 120 MW and 80 MW (b) 81 MW and 120 MW (c) 120 MW and 120 MW (d) 80 MW and 80 MWarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
What is the Difference Between Single Phase and Three Phase???; Author: Electrician U;https://www.youtube.com/watch?v=FEydcr4wJw0;License: Standard Youtube License