Concept explainers
Find the Thevenin equivalent to the left of the load Z in the circuit of Fig. 13.87.
Calculate the Thevenin equivalent to the left side of load Z in the coupled coils circuit.
Answer to Problem 18P
The Thevenin equivalent circuit parameters are
Explanation of Solution
Given data:
Refer to Figure 13.87 in the textbook for the circuit with coupled coils.
Calculation:
To the Thevenin’s voltage, open-circuit the impedance Z. Then, the current
Modify the Figure 13.87 by convert the circuit into the frequency domain and convert the coupled inductors into their dependent source equivalent. The modified circuit as shown in Figure 1.
Apply Kirchhoff's voltage law to the loop 1 contains current
Substitute 0 for
Modify the Equation as follows.
Write the expression for the open-circuit voltage.
Substitute
Consider the expression for the Thevenin voltage.
Substitute
Modify the Figure 1 by short-circuiting the load side contains current
From Figure 2, consider that the loops 1 and 2 contain the currents
Apply Kirchhoff's voltage law to the loop 1 in Figure 1.
Apply Kirchhoff's voltage law to the loop 2 in Figure 1.
Write equations (1) and (2) in matrix form as follows.
Write the MATLAB code to solve the equation (3).
A = [(4+j*7) -(4+j*11);-(4+j*11) (4+j*28)];
B = [440; 0];
I = inv(A)*B
The output in command window:
I =
61.069 - 121.926i
14.369 - 54.571i
From the MATLAB output, the currents
And
The short-circuit current
Substitute
Write the expression for Thevenin’s equivalent impedance.
Substitute
Conclusion:
Thus, the Thevenin equivalent circuit parameters are
Want to see more full solutions like this?
Chapter 13 Solutions
Fundamentals of Electric Circuits
- An ideal auto-transformer has its secondary winding labelled as a, b and c. The primary winding has 100 turns. The number of turns on the secondary side are 400 turns between a and b and 200 turns between b and c. The total number of turns between a and c is 600 turns. The transformer supplies a resistive load of 6 kW between a and c. In addition, a load of impedance 1,000 cis (45°) ohms is connected between a and b. For a primary voltage of 1,000 V, find the primary current and primary input power.arrow_forwardThe diagram shown below is a typical tuning circuit. Considering this circuit comprises a transformer (with a coil ratio of 20:1 and an HV side voltage of 240V ), a capacitor of impedance -j20Ω, an inductor of impedance j40Ω, and a 50Ω resistor, determine: the current supplied by the source (0.2228) the impedance seen at the supply (HV side)(21540.55) the power dissipated by the resistor(2.482 watts) the operating power factor of the fitting(0.928 lagging) If the capacitor is now removed from the above circuit and is placed in parallel with the secondary of the transformer, redraw the circuit diagram and recalculate parts a. to d. in question (i). Draw the phasor diagram for both series and parallel RLC circuits in parts (i) and (ii). Discuss the effects of changing the capacitor connection in parallel on the power factor of the circuit. State the benefits of using the transformer in the above circuit. Explain the operating principle of the transformer with particular reference to…arrow_forward4.a. A demountable stud bushing on high-voltage leads eliminates the need fora. an oil stop.b. a gasket.c. a terminal lug. 4.a. A power transformer with standard insulation class of 69 kv will withstand an rms test voltage ofA. 140 kv.B. 440 kv.c. 69kv.arrow_forward
- A coil has resistance of 5 ohm and inductive reactance of 4 ohm. a) what is the impedance of the coil? b) what is the admittance of the coil?arrow_forwardA 15 KVA closet transformer lovated inside a building is used to step down the voltage for the buildinh. It is connected to a primary "Z800" V AC power source. The ratio of the number of primar windings to the number og secondary windings on the transforemer is 60 to 15. 1. what is the voltage provided to the building? 2. What is the amoung of current provided to the building? 3. If the building consymes 3200W of power, what is it's power factor? 4. What is the phase angle of the secondary power source in the building?arrow_forwardA network is composed of the utility having Ssc=500MVA, and an 800KVA transformer, rated at 20KV/410V (no load), whose voltage impedance is 5%, and whose load losses are 5400watts. the short circuit at the secondary of the transformer using the impedance method is: Select one: a)30.5KA b)None of these c)45.8KA d)21.83KAarrow_forward
- Given a 3KVA transformer with an efficiency of 95.5% at half load and unity power factor and a copper loss of 90 watts at full load. Calcuate the iron loss in watts.arrow_forwardA coil has resistance of 5 ohm and capacitive reactance of 6 ohm . a) what is the impedance of the coil? b) what is the admittance of the coil?arrow_forwardThe diagram shown below is a typical tuning circuit. Considering this circuit comprises a transformer (with a coil ratio of 20:1 and an HV side voltage of 240V ), a capacitor of impedance -j20Ω, an inductor of impedance j40Ω, and a 50Ω resistor, determine: the current supplied by the source the impedance seen at the supply (HV side) the power dissipated by the resistor the operating power factor of the fitting If the capacitor is now removed from the above circuit and is placed in parallel with the secondary of the transformer, redraw the circuit diagram and recalculate parts a. to d. in question (i). Draw the phasor diagram for both series and parallel RLC circuits in parts (i) and (ii). Discuss the effects of changing the capacitor connection in parallel on the power factor of the circuit. State the benefits of using the transformer in the above circuit. Explain the operating principle of the transformer with particular reference to electro-magnetic…arrow_forward
- You are given five light bulbs designed to operate on 160 mA current at 3.0 V (rms values), arid want to connect them in parallel, through an ideal transformer, to 120 V rms AC household power. a) Draw a circuit diagram showing the AC power source (a generator symbol ), the transformer, and resistors for the light bulbs. b) Is the required transformer step-up or step-down? What turns ratio N5/N is needed? e) Calculate the ruts current through both the primary and secondary coils of the trans former, in mA.arrow_forwardQ4/A 25 KVA transformer supplies a load of 12 KW at a power factor of 0.6 lagging. If additional unity power factor load are used to be served with the same transformer .How many KW may be added before the adding of the new load? Draw the phasor diagram?arrow_forwardA coil with an inductance of 100 mH is connected in series with a resistance of 20 Ω. To this system If 110 V AC with a frequency of 25 Hz is applied, the impedance, current, resistance and coil of the system Find the voltage at the terminals, active, reactive and apparent power values of the system.arrow_forward
- Introductory Circuit Analysis (13th Edition)Electrical EngineeringISBN:9780133923605Author:Robert L. BoylestadPublisher:PEARSONDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningProgrammable Logic ControllersElectrical EngineeringISBN:9780073373843Author:Frank D. PetruzellaPublisher:McGraw-Hill Education
- Fundamentals of Electric CircuitsElectrical EngineeringISBN:9780078028229Author:Charles K Alexander, Matthew SadikuPublisher:McGraw-Hill EducationElectric Circuits. (11th Edition)Electrical EngineeringISBN:9780134746968Author:James W. Nilsson, Susan RiedelPublisher:PEARSONEngineering ElectromagneticsElectrical EngineeringISBN:9780078028151Author:Hayt, William H. (william Hart), Jr, BUCK, John A.Publisher:Mcgraw-hill Education,