Textbook Question
Chapter 12, Problem 41P
A balanced delta-connected load draws 5 kW at a power factor of 0.8 lagging. If the three-phase system has an effective line voltage of 400 V, find the line current.
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
Answer all
1.) In a three phase Delta-Wye connection
a.) What is the relationship between the line to line voltage at the source and the load?
b.) What is the relationship between the Phase to Phase voltage at the load and source?
c.) What is the relationship between the line Currents and phase currents going into the load?
d.) What is the relationship between the power being dissipated as seen from the source compared to the load?
A delta connected load of impedances (6 + j9) ohms each is supplied through a line having an impedance of (1 + j2) ohms. The supply voltage is balanced 3-phase, 400 V, 60 Hz mains. Find the total power drawn by the load.
In the circuit in the figure; L1 load draws 15 kVA with lagging power factor 0.6. The L2 load draws 6 kVA with a leading power factor of 0.8. According to this; What is the value of the complex power for the L2 load?
Chapter 12 Solutions
Fundamentals of Electric Circuits
Ch. 12.2 - Given that Vbn=22030V, find Van and Vcn, assuming...Ch. 12.3 - A Y-connected balanced three-phase generator with...Ch. 12.4 - One line voltage of a balanced Y-connected source...Ch. 12.5 - A positive-sequence, balanced -connected source...Ch. 12.6 - In a balanced -Y circuit, Vab=44015 and ZY = (12 +...Ch. 12.7 - For the Y-Y circuit in Practice Prob. 12.2,...Ch. 12.7 - Calculate the line current required for a 30-kW...Ch. 12.7 - Assume that the two balanced loads in Fig....Ch. 12.8 - The unbalanced -load of Fig. 12.24 is supplied by...Ch. 12.8 - Find the line currents in the unbalanced...
Ch. 12.9 - Prob. 11PPCh. 12.9 - For the unbalanced circuit in Fig. 12.32, use...Ch. 12.10 - Repeat Example 12.13 for the network in Fig. 12.24...Ch. 12.10 - Let the line voltage VL = 208 V and the wattmeter...Ch. 12.10 - If the load in Fig. 12.35 is delta-connected with...Ch. 12 - What is the phase sequence of a three-phase motor...Ch. 12 - If in an acb phase sequence, , then Vcn is:Ch. 12 - Which of these is not a required condition for a...Ch. 12 - Prob. 4RQCh. 12 - Prob. 5RQCh. 12 - In a Y-Y system, a line voltage of 220 V produces...Ch. 12 - In a - system, a phase voltage of 100 V produces a...Ch. 12 - When a Y-connected load is supplied by voltages in...Ch. 12 - Prob. 9RQCh. 12 - Prob. 10RQCh. 12 - If Vab = 400 V in a balanced Y-connected...Ch. 12 - What is the phase sequence of a balanced...Ch. 12 - Given a balanced Y-connected three-phase generator...Ch. 12 - A three-phase system with abc sequence and VL =...Ch. 12 - For a Y-connected load, the time-domain...Ch. 12 - Using Fig. 12.41, design a problem to help other...Ch. 12 - Obtain the line currents in the three-phase...Ch. 12 - In a balanced three-phase Y-Y system, the source...Ch. 12 - A balanced Y-Y four-wire system has phase voltages...Ch. 12 - For the circuit in Fig. 12.43, determine the...Ch. 12 - In the Y- system shown in Fig. 12.44, the source...Ch. 12 - Using Fig. 12.45, design a problem to help other...Ch. 12 - In the balanced three-phase Y- system in Fig....Ch. 12 - Obtain the line currents in the three-phase...Ch. 12 - The circuit in Fig. 12.48 is excited by a balanced...Ch. 12 - A balanced delta-connected load has a phase...Ch. 12 - A positive sequence wye-connected source where ,...Ch. 12 - If Van = 22060 V in the network of Fig. 12.49,...Ch. 12 - For the - circuit of Fig. 12.50, calculate the...Ch. 12 - Prob. 20PCh. 12 - Three 440-V generators form a delta-connected...Ch. 12 - Find the line currents IaA, IbB, and IcC in the...Ch. 12 - A balanced delta connected source is connected to...Ch. 12 - A balanced delta-connected source has phase...Ch. 12 - In the circuit of Fig. 12.54, if , , , find the...Ch. 12 - Using Fig. 12.55, design a problem to help other...Ch. 12 - A -connected source supplies power to a...Ch. 12 - The line-to-line voltages in a Y-load have a...Ch. 12 - A balanced three-phase Y- system has V rms and Z =...Ch. 12 - In Fig. 12.56, the rms value of the line voltage...Ch. 12 - A balanced delta-connected load is supplied by a...Ch. 12 - Design a problem to help other students better...Ch. 12 - A three-phase source delivers 4.8 kVA to a...Ch. 12 - A balanced wye-connected load with a phase...Ch. 12 - Three equal impedances, 60 + j30 each, are...Ch. 12 - A 4200-V, three-phase transmission line has an...Ch. 12 - The total power measured in a three-phase system...Ch. 12 - Given the circuit in Fig. 12.57 below, find the...Ch. 12 - Find the real power absorbed by the load in Fig....Ch. 12 - For the three-phase circuit in Fig. 12.59, find...Ch. 12 - A balanced delta-connected load draws 5 kW at a...Ch. 12 - A balanced three-phase generator delivers 7.2 kW...Ch. 12 - Refer to Fig. 12.48. Obtain the complex power...Ch. 12 - A three-phase line has an impedance of 1 + j3 per...Ch. 12 - A balanced wye-connected load is connected to the...Ch. 12 - A three-phase load consists of three 100-...Ch. 12 - The following three parallel-connected three-phase...Ch. 12 - A balanced, positive-sequence wye-connected source...Ch. 12 - Each phase load consists of a 20- resistor and a...Ch. 12 - A balanced three-phase source with VL = 240 V rms...Ch. 12 - Consider the wye-delta system shown in Fig. 12.60....Ch. 12 - A four-wire wye-wye circuit has...Ch. 12 - Using Fig. 12.61, design a problem that will help...Ch. 12 - A balanced three-phase Y-source with VP = 880 V...Ch. 12 - A three-phase supply, with the line-to-line...Ch. 12 - Using Fig. 12.63, design a problem to help other...Ch. 12 - Determine the line currents for the three-phase...Ch. 12 - Solve Prob. 12.10 using PSpice or MultiSim. For...Ch. 12 - The source in Fig. 12.65 is balanced and exhibits...Ch. 12 - Use PSpice or MultiSim to determine Io in the...Ch. 12 - Given the circuit in Fig. 12.67, use PSpice or...Ch. 12 - Using Fig. 12.68, design a problem to help other...Ch. 12 - Use PSpice or MultiSim to find currents IaA and...Ch. 12 - For the circuit in Fig. 12.58, use PSpice or...Ch. 12 - A balanced three-phase circuit is shown in Fig....Ch. 12 - A three-phase, four-wire system operating with a...Ch. 12 - As shown in Fig. 12.72, a three-phase four-wire...Ch. 12 - Meter readings for a three-phase wye-connected...Ch. 12 - A certain store contains three balanced...Ch. 12 - The two-wattmeter method gives P1=1200W and...Ch. 12 - In Fig. 12.73, two wattmeters are properly...Ch. 12 - If wattmeters W1 and W2 are properly connected...Ch. 12 - For the circuit displayed in Fig. 12.74, find the...Ch. 12 - Predict the wattmeter readings for the circuit in...Ch. 12 - Prob. 75PCh. 12 - Show that the I2R losses will be higher for a...Ch. 12 - A three-phase generator supplied 10 kVA at a power...Ch. 12 - Prob. 78CPCh. 12 - A balanced three-phase generator has an abc phase...Ch. 12 - A balanced three-phase source furnishes power to...Ch. 12 - A professional center is supplied by a balanced...Ch. 12 - A balanced three-phase system has a distribution...Ch. 12 - A commercially available three-phase inductive...Ch. 12 - Figure 12.76 displays a three-phase...Ch. 12 - Design a three-phase heater with suitable...Ch. 12 - For the single-phase three-wire system in Fig....Ch. 12 - Consider the single-phase three-wire system shown...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- A balanced three-phase load requires 1.8kW and power factor 0.5. If the line voltage at the terminals of the load is 230 V. the magnitude of line current is: Select one: a. 7.82 A O b. 9.03A O c. 15.65 A O d. 4.51 Aarrow_forwardA balanced delta-connected load is supplied by a 60 Hz 3-phase source with a line voltage of 240 V. Each load phase draws 6kW at a lagging power factor of 0.8. Calculate: a. The load impedance per phase b. The line current c. The value of the capacitance needed to be connected in parallel with each load to minimize the current from the source (PF=1)arrow_forwardIn a balanced delta connected 3-phase circuit, has resistance 25 ohm and inductive reactance 40 ohm, connected to a 400V,50HZ 3-phase supply voltage, then total power delivered to load is Select one: a. 5397.76W b. 1635.34KW c. 7593.26W d. NONE OF THESEarrow_forward
- A symmetrical three-phase, three-wire 440 V supply is connected to a star-connected load as shown. Find its equivalent delta-connected load. The phase sequence is negative sequence.arrow_forwardA balanced purely resistive delta load has a phase voltage of 208 v and line current of 24.65 A. What is the total real power of this load in kW?arrow_forwardI need to know how to get the last three parts of this problem. A line voltage of 208 V is connected to a balanced three-phase delta-connected inductive load consisting of a phase resistance of 8 ohms in series with an inductive reactance of 6 ohms. Determine the phase impedance, the circute power factor, the load phase voltage, the phase current, the line current, the total power consumed and the kilovoltampere input.arrow_forward
- 1. The following are the given for the circuit below: VRY = 220 cis 0°, VYB = 220 cis -120° and VBR = 220 cis -240°. IR = 10 cis 0°. The load is balanced and delta connected. Determine the: (a) Impedance per phase (b) Current per phase (c) Line currents. B R reellle relllle momm Y RY Iy IB ĪR B R ZBR VYB ZRYarrow_forward3.3 The active power of a 440-V, 3-phase lagging power factor load is measured by two-wattmeter method and the readings of the meters are found as 40 kW and 10 kW. Determine the load power factor and line current. Another 3-phase load of 30 kVA at 0.85 lagging power factor is now added in parallel with the previous load. Determine the new meter readings. [0.693, 94.6 A, 57.3 kW, 18.2 kW]arrow_forwardObtain the equivalent circuit of a 200/400 V, 50 Hz, single-phase transformcr from the following test data: O.C. test : 200 V, 0-7 A, 70 W .. on L.V. side S.C. test : 15 V, 10 A, 85 W Calculate the secondary voltage when delivering S kW at 08 p.f. lagging, the primary voltage being . on H.V. side 200 V. (R, = 57-14 Q ; X, = 330 2; R = 0-21 Q ; Xg, = 0-31 Q ; 3778 V)arrow_forward
- A three-phase supply, with the line voltage 240 V rms positively phased, has an unbalanced delta-connected load as shown in the figure below. Find the phase currents and the total complex power.arrow_forward5. The figure below shows two star connected loads with three phase power. The voltage source is 120Z0°. The loads are Z₁ = 10 + j4 № and Z₂ = 2 +j3 №. The cables are negligible. Calculate: a) the line and phase current. b) the real power from the source. c) the reactive power of the circuit. Is V N Z₁ Z₁ Z₁ Z₂ Z₂ N N Z₂arrow_forwardA balanced three-phase load requires 1.8kW and power factor 0.5. If the line voltage at the terminals of the load is 230 V, the magnitude of line current is: Select one: Ⓒa. 9.03A Ob. 7.82 A O c. 15,65 A d. 4.51 Aarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
What is the Difference Between Single Phase and Three Phase???; Author: Electrician U;https://www.youtube.com/watch?v=FEydcr4wJw0;License: Standard Youtube License