Fundamentals of Electric Circuits
6th Edition
ISBN: 9780078028229
Author: Charles K Alexander, Matthew Sadiku
Publisher: McGraw-Hill Education
expand_more
expand_more
format_list_bulleted
Textbook Question
Chapter 12, Problem 76P
Show that the I2R losses will be higher for a 120-V appliance than for a 240-V appliance if both have the same power rating.
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
In a given system of base power of 250 MW, and bus 3 is taken as reference. The per-unit reactances are X12 = 0.2 p.u., X13 = X23 = 0. 1
p.u. The power flow in the system is given as: PF12 = 50 MW, PF13 = 150 MW, PF23 = 50 MW. Based on readings from 2 meters (not
including M12 meter), M13 = 145 MW (not calibrated), and M23 = 50 MW (well calibrated), deduce the flow on line 1-2.
Select one:
O a. PF12 = - 47.5 MW.
O b. None of these
O c. PF12 = 67.5 MW.
O d.
PF12 = 47.5 MW.
O e. PF12 =- 57.5 MW.
O f.
PF12 = 57 MW.
There are 144 fuel cells are joined in a series through interconnects.there will be 4 stacks having 36 cell in each stack.these stacks are then oragnised in series and parallel combination to form a single module to deliver required voltage and output power.this SOFCs module then combined with CHP system to get thermal .
From this data answer the following questions.
a)Calculate voltage losses of module?.this question is very compulsory.
b)Electrical efficiency of module?
C)Thermal efficiency when module combine with CHP system?
D)Combined electrical and thermal efficiency?
The input parameters of single cell are given below:
Ocv=1.020
Current density=2250mA/cm2
Power density=850mw/cm2
Cell active area= 121cm2
Net power=15kw
System fuel utilization=80%
Operating temp=550°c
Cell voltage=0.8v
Power of single cell=103 watt.
(5)
Primary
AC Source
Transformer
Secondary
AC/DC Full-wave
Rectifier
Capaictor
in
Non-
linear
Load
Figure 6
Analyse different methods of harmonics mitigation to eliminate the harmonic, which you have
identify in above power system circuit. You can use harmonic filters, K or equivalent
transformers or oversized neutral method depending upon the harmonic sources.
Chapter 12 Solutions
Fundamentals of Electric Circuits
Ch. 12.2 - Given that Vbn=22030V, find Van and Vcn, assuming...Ch. 12.3 - A Y-connected balanced three-phase generator with...Ch. 12.4 - One line voltage of a balanced Y-connected source...Ch. 12.5 - A positive-sequence, balanced -connected source...Ch. 12.6 - In a balanced -Y circuit, Vab=44015 and ZY = (12 +...Ch. 12.7 - For the Y-Y circuit in Practice Prob. 12.2,...Ch. 12.7 - Calculate the line current required for a 30-kW...Ch. 12.7 - Assume that the two balanced loads in Fig....Ch. 12.8 - The unbalanced -load of Fig. 12.24 is supplied by...Ch. 12.8 - Find the line currents in the unbalanced...
Ch. 12.9 - Prob. 11PPCh. 12.9 - For the unbalanced circuit in Fig. 12.32, use...Ch. 12.10 - Repeat Example 12.13 for the network in Fig. 12.24...Ch. 12.10 - Let the line voltage VL = 208 V and the wattmeter...Ch. 12.10 - If the load in Fig. 12.35 is delta-connected with...Ch. 12 - What is the phase sequence of a three-phase motor...Ch. 12 - If in an acb phase sequence, , then Vcn is:Ch. 12 - Which of these is not a required condition for a...Ch. 12 - Prob. 4RQCh. 12 - Prob. 5RQCh. 12 - In a Y-Y system, a line voltage of 220 V produces...Ch. 12 - In a - system, a phase voltage of 100 V produces a...Ch. 12 - When a Y-connected load is supplied by voltages in...Ch. 12 - Prob. 9RQCh. 12 - Prob. 10RQCh. 12 - If Vab = 400 V in a balanced Y-connected...Ch. 12 - What is the phase sequence of a balanced...Ch. 12 - Given a balanced Y-connected three-phase generator...Ch. 12 - A three-phase system with abc sequence and VL =...Ch. 12 - For a Y-connected load, the time-domain...Ch. 12 - Using Fig. 12.41, design a problem to help other...Ch. 12 - Obtain the line currents in the three-phase...Ch. 12 - In a balanced three-phase Y-Y system, the source...Ch. 12 - A balanced Y-Y four-wire system has phase voltages...Ch. 12 - For the circuit in Fig. 12.43, determine the...Ch. 12 - In the Y- system shown in Fig. 12.44, the source...Ch. 12 - Using Fig. 12.45, design a problem to help other...Ch. 12 - In the balanced three-phase Y- system in Fig....Ch. 12 - Obtain the line currents in the three-phase...Ch. 12 - The circuit in Fig. 12.48 is excited by a balanced...Ch. 12 - A balanced delta-connected load has a phase...Ch. 12 - A positive sequence wye-connected source where ,...Ch. 12 - If Van = 22060 V in the network of Fig. 12.49,...Ch. 12 - For the - circuit of Fig. 12.50, calculate the...Ch. 12 - Prob. 20PCh. 12 - Three 440-V generators form a delta-connected...Ch. 12 - Find the line currents IaA, IbB, and IcC in the...Ch. 12 - A balanced delta connected source is connected to...Ch. 12 - A balanced delta-connected source has phase...Ch. 12 - In the circuit of Fig. 12.54, if , , , find the...Ch. 12 - Using Fig. 12.55, design a problem to help other...Ch. 12 - A -connected source supplies power to a...Ch. 12 - The line-to-line voltages in a Y-load have a...Ch. 12 - A balanced three-phase Y- system has V rms and Z =...Ch. 12 - In Fig. 12.56, the rms value of the line voltage...Ch. 12 - A balanced delta-connected load is supplied by a...Ch. 12 - Design a problem to help other students better...Ch. 12 - A three-phase source delivers 4.8 kVA to a...Ch. 12 - A balanced wye-connected load with a phase...Ch. 12 - Three equal impedances, 60 + j30 each, are...Ch. 12 - A 4200-V, three-phase transmission line has an...Ch. 12 - The total power measured in a three-phase system...Ch. 12 - Given the circuit in Fig. 12.57 below, find the...Ch. 12 - Find the real power absorbed by the load in Fig....Ch. 12 - For the three-phase circuit in Fig. 12.59, find...Ch. 12 - A balanced delta-connected load draws 5 kW at a...Ch. 12 - A balanced three-phase generator delivers 7.2 kW...Ch. 12 - Refer to Fig. 12.48. Obtain the complex power...Ch. 12 - A three-phase line has an impedance of 1 + j3 per...Ch. 12 - A balanced wye-connected load is connected to the...Ch. 12 - A three-phase load consists of three 100-...Ch. 12 - The following three parallel-connected three-phase...Ch. 12 - A balanced, positive-sequence wye-connected source...Ch. 12 - Each phase load consists of a 20- resistor and a...Ch. 12 - A balanced three-phase source with VL = 240 V rms...Ch. 12 - Consider the wye-delta system shown in Fig. 12.60....Ch. 12 - A four-wire wye-wye circuit has...Ch. 12 - Using Fig. 12.61, design a problem that will help...Ch. 12 - A balanced three-phase Y-source with VP = 880 V...Ch. 12 - A three-phase supply, with the line-to-line...Ch. 12 - Using Fig. 12.63, design a problem to help other...Ch. 12 - Determine the line currents for the three-phase...Ch. 12 - Solve Prob. 12.10 using PSpice or MultiSim. For...Ch. 12 - The source in Fig. 12.65 is balanced and exhibits...Ch. 12 - Use PSpice or MultiSim to determine Io in the...Ch. 12 - Given the circuit in Fig. 12.67, use PSpice or...Ch. 12 - Using Fig. 12.68, design a problem to help other...Ch. 12 - Use PSpice or MultiSim to find currents IaA and...Ch. 12 - For the circuit in Fig. 12.58, use PSpice or...Ch. 12 - A balanced three-phase circuit is shown in Fig....Ch. 12 - A three-phase, four-wire system operating with a...Ch. 12 - As shown in Fig. 12.72, a three-phase four-wire...Ch. 12 - Meter readings for a three-phase wye-connected...Ch. 12 - A certain store contains three balanced...Ch. 12 - The two-wattmeter method gives P1=1200W and...Ch. 12 - In Fig. 12.73, two wattmeters are properly...Ch. 12 - If wattmeters W1 and W2 are properly connected...Ch. 12 - For the circuit displayed in Fig. 12.74, find the...Ch. 12 - Predict the wattmeter readings for the circuit in...Ch. 12 - Prob. 75PCh. 12 - Show that the I2R losses will be higher for a...Ch. 12 - A three-phase generator supplied 10 kVA at a power...Ch. 12 - Prob. 78CPCh. 12 - A balanced three-phase generator has an abc phase...Ch. 12 - A balanced three-phase source furnishes power to...Ch. 12 - A professional center is supplied by a balanced...Ch. 12 - A balanced three-phase system has a distribution...Ch. 12 - A commercially available three-phase inductive...Ch. 12 - Figure 12.76 displays a three-phase...Ch. 12 - Design a three-phase heater with suitable...Ch. 12 - For the single-phase three-wire system in Fig....Ch. 12 - Consider the single-phase three-wire system shown...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- What is the purpose of power factor correction to a given load? O To reduce the amount of voltage to the load. O To reduce the amount of dependence on automated machinery. O To reduce the amount of current to the load. O To reduce the amount of resistance of the load.arrow_forwardA generator operating at 50 Hz delivers 1 p.u. power to an infinite bus through a transmission circuit in which resistance is ignored. A fault takes place reducing the maximum power transferable to 0.5 p.u. Where as before the fault, this power was 2.5 p.u. and after the clearance of the fault, it is 2 p.u. The value of 8 is maxarrow_forwardWhat effects are produced by change in voltage? 1. Iron los..........varies approximately as V². 2. Cu loss..........it also varies as V² but decreases with an increase in voltage if constant kVA output is assumed. 3. Efficiency...........for distribution transformers, efficiency at fractional loads decreases with in- crease in voltage while at full load or overload it increases with increase in voltage and vice- versa. 4. Regulation..........it varies as but decreases with increase in voltage if constant kVA output is assumed. 5. Heating.........for constant kVA output, iron temperatures increase whereas Cu temperatures decrease with increase in voltages and vice-versa.arrow_forward
- Please help me with my homework. Thanks! The course subject is Fundamentals of Electronic Communications. 4. A 400 W carrier is amplitude modulated to a depth of 100%. Calculate the total power in case of SSB technique. How much power saving (in W) is achieved for SSB compared to standardarrow_forwardQ10-The full-load copper loss on the H.V. side of 100KVA, 11000/317 V, single-phase transformer is o.62 Kw and on the L.V. side is 0.48 kW. i) Calculate R1 ,R2 in ohms ii) Find X1 ,X2,if the total reactance is 4% ,and the reactance is divided in same proportion as resistance. Ans. (7.52, 0.00482 2 , 27.32,0.175 2)arrow_forwardA low voltage distribution transformer feeds two different loads with a three-phase line. The nominal voltage of the line is 400 Volt. The total length of the feeder is 500 m. The distance from the transformer to these loads is 140 m and 340 m, respectively. Their consumption is 11 kVA with a 0.8 lagging power factor and 10 kW with a 0.8 lagging power factor, respectively. The feeder's cross-section is 15 mm2 and the feeder's conductivity is 56 m/ohm.mm2. Find the following information. The distance from the transformer to the maximum voltage drop point is m The maximum voltage drop is Volt The power loss between the transformer and 11 kVA load is Watt.arrow_forward
- 7. TY Hat CHICL Ans. 1. Iron los.........varies approximately as V². 2. Cu loss..........it also varies as ² but decreases with an increase in voltage if constant kVA output is assumed. 3. Efficiency...........for distribution transformers, efficiency at fractional loads decreases with in- crease in voltage while at full load or overload it increases with increase in voltage and vice- versa. 4. Regulation..........it varies as but decreases with increase in voltage if constant kVA output is assumed. 5. Heating.........for constant kVA output, iron temperatures increase whereas Cu temperatures decrease with increase in voltages and vice-versa. quemsarrow_forwardTable Q2a Time (hours) 0-6 6-12 12-14 14-18 18-24 Load (MW) 45 90 135 150 75 Referring to the Table Q2a; i) Draw the load curve and the load duration curve [Use the graph paper provided] ii) Indicate the base load and the peak load on the graph. Determine the values for both loads. iii) Choose the suitable generating units to supply the load and list their operating schedules. Later, compute the total installed capacity. iv) Calculate the load factor and the plant capacity factor. Discuss the impact on the operating schedule if the plant capacity factor increases to 0.9.arrow_forwardDraw the circuit diagram of Two quadrant chopper which is having average load voltage might be positive or negative. Explain each quadrant operation with neat sketch. I want more than 350 words and I do not want it in handwritingarrow_forward
- 1. What is the ultimate objective of an interconnection? 2. What does it mean when the ACE of all areas in an interconnection is equal to ZERO? 3. Explain the difference between the ACE in a single-area power system and the ACE in two-area power system. 4. If there is a decrease in frequency of a two areas interconnection, but the net interchange power leaving balancing area 1 increases. This means: 5. If the monitoring system indicates a negative ACE, what does this means? 6. Briefly discuss the term Frequency Response. 2 2-1 LilAJ 11:06 PM 8/29/2021 A ENGarrow_forwardAdvantages of using per unit system in power system studies is O a. None of these O b. Both more informative and calculations are easy. O c. More informative O d. Calculations are easyarrow_forwardA parallel connection of a RL branch with a C branch is connected across a 100V AC mains. At first R = 10 ohms, L = 20mH and frequency of 1000rad / s, the current measured is 2.2361A at 89.44 leading power factor. A) Determine the initial capacitance. B) However, a fault occurs on the capacitor branch making its capacitance 20% lower and a resistance of 5 ohms is detected. If this faulty circuit is rerun but at a frequency of 500 rad / s, determine the new current that will flow through the circuit.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Power System Stability in C# Part 1: Fundamentals of Stability Analysis; Author: EETechStuff;https://www.youtube.com/watch?v=SaT9oWcHgKw;License: Standard Youtube License