Question
In a balanced delta connected 3-phase circuit, has resistance 25 ohm and inductive reactance 40 ohm,
connected to a 400V,50HZ 3-phase supply voltage, then total power delivered to load is
Select one:
a. 5397.76W
b. 1635.34KW
c. 7593.26W
d. NONE OF THESE
Transcribed Image Text:In a balanced delta connected 3-phase circuit, has resistance 25 ohm and inductive reactance 40 ohm, connected to a 400V,50HZ 3-phase supply voltage, then total power delivered to load is Select one: a. 5397.76W b. 1635.34KW c. 7593.26W d. NONE OF THESE
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Measuring instrument
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning