Power System Analysis and Design (MindTap Course List)
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN: 9781305632134
Author: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher: Cengage Learning
bartleby

Concept explainers

bartleby

Videos

Textbook Question
Book Icon
Chapter 9, Problem 9.34P

At the general three-phase bus shown in Figure 9.7(a) of the text, consider a simultaneous single line-to-ground fault on phase a and line-to-line fault between phases b and c, with no fault impedances. Obtain the sequence-network interconnection satisfying the current and voltage constraints.

Chapter 9, Problem 9.34P, At the general three-phase bus shown in Figure 9.7(a) of the text, consider a simultaneous single

Blurred answer
Students have asked these similar questions
sequence networks are to be connected fault terminals through the impedance components of the fault current are at the the sequence Fill in the blanks. For a line-to-line fault with a fault impedance ZF, the positive and negative sequence networks are to be connected at the fault terminals through the impedance ; the positive and negative sequence components of the fault current are and the zero-sequence current is Fill in the blanks. For a double-line-to-ground fault with a fault impedance ZF, the sequence networks are to be connected fault terminals; additionally, with the zero-sequence network. Fill in the blanks. at the is to be included in series
Consider the system shown in the single-line diagram of Figure (3). All reactances are shown in per unit to the same base. Assume that the voltage at both sources is 1 p.u. a Find the fault current due to a bolted- three-phase short circuit at bus 3 b- Find the fault current supplied by each generator and the voltage at each of the buses 1 and 2 under fault conditions 0.06 p.u. 0.2 p.u. 0.04 p.u. 0.25 p.u. 0.2 p.u. 0.2 p.. 0.2 p.u. 0.06 p.u. 0.25 p.u. Figure (3) Single-line diagram ele ver ele 888 ele 0.06 p.u. 0.25 p.u.
Consider the single-line diagram of a power system shown below. The transient reactance of cach part of the system is as shown in table and expressed in p.u. on a common 100 MVA base. A three-phase fault with impedance of 0.16 p. occurs at bus (5). Determine short- circuit capacity (fault level) and short circuit current? Assume the fault voltage at bus (5) equal 112 KV
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Fault Analysis in Power Systems part 1a; Author: GeneralPAC: Power System Tutorials;https://www.youtube.com/watch?v=g8itg4MOjok;License: Standard youtube license