Power System Analysis and Design (MindTap Course List)
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN: 9781305632134
Author: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher: Cengage Learning
bartleby

Concept explainers

bartleby

Videos

Textbook Question
Book Icon
Chapter 9, Problem 9.13P

Consider the oneline diagram of a simple power system shown in Figure 9.20. System data in per-unit on a 100-MVA base are given as follows:

Chapter 9, Problem 9.13P, Consider the oneline diagram of a simple power system shown in Figure 9.20. System data in per-unit , example  1

Chapter 9, Problem 9.13P, Consider the oneline diagram of a simple power system shown in Figure 9.20. System data in per-unit , example  2

The neutral of each generator is grounded through a current-limiting reactor of 0.08333 per unit on a 100-MVA base. All transformer neutrals are solidly grounded. The generators are operating no-load at their rated voltages and rated frequency with their ENIFs in phase. Determine the fault current for a balanced three-phase fault at bus 3 through a fault impedance Z F = 0.1 per unit on a 100-MVA base. Neglect Δ -Y phase shifts.

Blurred answer
Students have asked these similar questions
Q2. The single-line diagram of a simple three-bus power system is shown in Figure-2. Each generator is represented by an emf behind the sub-transient reactance. All impedances are expressed in per unit on a common MVA base. All resistances and shunt capacitances are neglected. The generators are operating on no load at their rated voltage with their emfs in phase. A three-phase fault occurs at bus 3 through a fault impedance of Zf = j0.19 per unit. (i) Using Th'evenin's theorem, obtain the impedance to the point of fault and the fault current in (ii) Determine the bus voltages per unit. ) j0.05 j0.075 j0.75 2 j0.30 j0.45 Figure-2: Single line diagram of the power system network for Q2 3
Consider the three single-phase two-winding transformers shown in Figure. 3. The high-voltage windings are connected in Y. (a) For the low-voltage side, connect the windings in A, and label the terminals a, b, and c in accordance with the American standard. (b) Relabel the terminals a', b', and c' such that VAN is 90° out of phase with V₂'b' for positive sequence. DI H₂ Figure. 3: Three-Winding Transformer
Three zones of a single-phase circuit are identified in the figure. The zones are connected by transformers T₁ and T2, whose ratings are also shown. Using base values of 100 kVA and 240 volts in zone 1, draw the per-unit circuit and determine the per-unit impedances and the per-unit source voltage. Then calculate the load current both in per-unit and in amperes. Transformer winding resistances and shunt admittance branches are neglected. Zone 1 Zone 2 Vs = 220/0° volts 3---38 T, 30 KVA 240/480 volts M 0.10 p.u. Xoa Xune = 2 fl T T₂ 20 kVA 460/115 volts Xeg = 0.10 p.u. Zone 3 ww Zload = 0.9 - 10.20
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Text book image
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Fault Analysis in Power Systems part 1a; Author: GeneralPAC: Power System Tutorials;https://www.youtube.com/watch?v=g8itg4MOjok;License: Standard youtube license