Q2/The positive-sequence reactances for the power system shown in Figure are in per unit on a common MVA base. Resistances are neglected and the negative-sequence impedances are assumed to be the same as the positive-sequence impedances. A bolted line-to-line fault occurs between phases b and c at bus 2. Before the fault occurrence, all bus voltages are 1.0 per unit. Obtain the positive sequence bus impedance matrix. Find the fault current, the three-phase bus voltages during fault, and the line currents in each phase. T₁ 1 X=j0.05 0.15 3 GTOCO 14 G₁ j0.6 j0.3 2 T2 j0.05 X=j0.05 B8 (G₂) HXD

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter8: Symmetrical Components
Section: Chapter Questions
Problem 8.34P
icon
Related questions
icon
Concept explainers
Question
Q2/The positive-sequence reactances for the power system shown in Figure are in per unit on
a common MVA base. Resistances are neglected and the negative-sequence impedances are
assumed to be the same as the positive-sequence
impedances. A bolted line-to-line fault occurs between phases b and c at bus 2. Before the fault
occurrence, all bus voltages are 1.0 per unit. Obtain the positive sequence bus impedance
matrix. Find the fault current, the three-phase bus voltages during fault, and the line currents
in each phase.
T₁ 1
0.15
उह
3
X=j0.05
G₁
j0.6
j0.3
2 T2
j0.05 X=j0.05
G₂
Transcribed Image Text:Q2/The positive-sequence reactances for the power system shown in Figure are in per unit on a common MVA base. Resistances are neglected and the negative-sequence impedances are assumed to be the same as the positive-sequence impedances. A bolted line-to-line fault occurs between phases b and c at bus 2. Before the fault occurrence, all bus voltages are 1.0 per unit. Obtain the positive sequence bus impedance matrix. Find the fault current, the three-phase bus voltages during fault, and the line currents in each phase. T₁ 1 0.15 उह 3 X=j0.05 G₁ j0.6 j0.3 2 T2 j0.05 X=j0.05 G₂
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning