A bank of three single-phase transformers, each rated 3 0 MVA , 38 . 1 / 3 . 81 kV , are connected in Y-Δ with a balanced load of three 1 Ω , Y-connected resistors. Choosing a base of 9 0 MVA , 66 kV for the high-voltage side of the three-phase transformer. spify the base for the low-voltage side. Compute the per-unit resistance of the load on the base for the low-voltage side. Also, determine the load resistance in ohms referred to the high-voltage side and the per-unit value on the chosen base.
A bank of three single-phase transformers, each rated 3 0 MVA , 38 . 1 / 3 . 81 kV , are connected in Y-Δ with a balanced load of three 1 Ω , Y-connected resistors. Choosing a base of 9 0 MVA , 66 kV for the high-voltage side of the three-phase transformer. spify the base for the low-voltage side. Compute the per-unit resistance of the load on the base for the low-voltage side. Also, determine the load resistance in ohms referred to the high-voltage side and the per-unit value on the chosen base.
A bank of three single-phase transformers, each rated
3
0
MVA
,
38
.
1
/
3
.
81 kV
,
are connected in
Y-Δ
with a balanced load of three
1
Ω
, Y-connected resistors. Choosing a base of
9
0
MVA
,
66 kV
for the high-voltage side of the three-phase transformer. spify the base for the low-voltage side. Compute the per-unit resistance of the load on the base for the low-voltage side. Also, determine the load resistance in ohms referred to the high-voltage side and the per-unit value on the chosen base.
The rated voltages of a single-phase transformer are 2000 V and 200 V in its
primary and secondary respectively. The shunt impedance can be modelled with a
resistance of 14000 ohms in parallel with a reactance of 1100 ohm, both refer to
primary side. The primary and secondary series impedances are (0.12+j 0.35) ohms
and (0.0012+j 0.0035) ohms respectively. A load is connected to the secondary
side of transformer, draws 810 KVA with a lagging power factor of 0.85. The load
voltage is same as rated voltage, that is 200 V.
▪ Use per unit method for analysis and find the voltage on primary side in pu.
A 50 Hz, Scott connected transformer supplies an unbalanced two phase load at ( 400 V) per phase. For the leading phase the load has a resistance of (13.3 ohm) and capacitor of (318) micro farad in series. For the other phase the load consists of resistance (10) ohm and an inductance of (42.3) mH. Calculate both mathematically and graphically the lines currents on 3-phase side. The main transformer primary to secondary turns ratio is (12/1).
3. Single-phase T1-transformer with a power of 500 kVA and a single-phase T2- with a power of 400 kVAtransformers are connected in parallel and load 1000 kVA with 0.8-back power factor.they are feeding. The equivalent circuit winding resistance of T1 is 0.025 b and the equivalent circuit reactance is 0.06is b. The equivalent winding resistance of T2 is 0.016 b and the equivalent circuit reactance is 0.07 b. Bothhas the same conversion ratio in the transformer.a. Draw the connection diagram given in the question. b. Obtain the power sharing expression over the parameters given in the question. c. Calculate the kVA values and power factors of the transformers.
Chapter 3 Solutions
Power System Analysis and Design (MindTap Course List)
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
How does a Transformer work - Working Principle electrical engineering; Author: The Engineering Mindset;https://www.youtube.com/watch?v=UchitHGF4n8;License: Standard Youtube License