Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN: 9781305632134
Author: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher: Cengage Learning
expand_more
expand_more
format_list_bulleted
Concept explainers
Textbook Question
Chapter 3, Problem 3.24P
For Problem 3.18, the motor operates at full load, at 0.8 power factor leading, and at a terminal voltage of 10.45 kV. Determine (a) the voltage at bus 1, which is the generator bus, and (b) the generator and motor internal EMFs.
Expert Solution & Answer
Trending nowThis is a popular solution!
Students have asked these similar questions
Power system protection
The one-line diagram of a simple power
system is shown in Figure below. The neutral
of each generator is grounded through a
current-limiting reactor of 0.25/3 per unit on a
100-MVA base. The system data expressed in
per unit on a common 100-MVA base is
tabulated below. The generators are running on
no-load at their rated voltage and rated
frequency with their emfs in phase.
G
Stark
Item Base MVA Voltage Rating X' x²
20 kV
20 kV
20/220 kV
20/220 kV
100
0.05
0.15
0.15
0.10
0.10
220 kV 0.125 0.125 0.30
0.15
0.25 025 0.7125
0.15
100
100
0.15
0.05
0.10
0.10
0.10
100
0.10
100
100
Lu
La
220 kV 0.15
220 kV
0.35
100
A balanced three-phase fault at bus 3 through a
fault impedance Zf= jo.I per unit.
The magnitude of the fault current in amperes
in phase b for this fault is:
Select one:
A. 345.3
B. 820.1
C. 312500
3888888
产产
-The sum of the armature reactance and.............reactance is the reactance of the synchronous generator after the short circuit fault is cleared.
-The selection of number of generating sources to meet the expected load is called as economic dispatch.
Select one:
True
False
Chapter 3 Solutions
Power System Analysis and Design (MindTap Course List)
Ch. 3 - The Ohms law for the magnetic circuit states that...Ch. 3 - For an ideal transformer, the efficiency is (a) 0...Ch. 3 - For an ideal 2-winding transformer, the...Ch. 3 - An ideal transformer has no real or reactive power...Ch. 3 - For an ideal 2-winding transformer, an impedance...Ch. 3 - Consider Figure 3.4. For an ideal phase-shifting...Ch. 3 - Consider Figure 3.5. Match the following, those on...Ch. 3 - The units of admittance, conductance, and...Ch. 3 - Match the following: (i) Hysteresis loss (a) Can...Ch. 3 - For large power transformers rated more than 500...
Ch. 3 - For a short-circuit test on a 2-winding...Ch. 3 - The per-unit quantity is always dimensionless. (a)...Ch. 3 - Consider the adopted per-unit system for the...Ch. 3 - The ideal transformer windings are eliminated from...Ch. 3 - To convert a per-unit impedance from old to new...Ch. 3 - In developing per-unit circuits of systems such as...Ch. 3 - Prob. 3.17MCQCh. 3 - Prob. 3.18MCQCh. 3 - With the American Standard notation, in either a...Ch. 3 - Prob. 3.20MCQCh. 3 - In order to avoid difficulties with third-harmonic...Ch. 3 - Does an open connection permit balanced...Ch. 3 - Does an open- operation, the kVA rating compared...Ch. 3 - It is stated that (i) balanced three-phase...Ch. 3 - In developing per-unit equivalent circuits for...Ch. 3 - In per-unit equivalent circuits of practical...Ch. 3 - Prob. 3.27MCQCh. 3 - Prob. 3.28MCQCh. 3 - For developing per-unit equivalent circuits of...Ch. 3 - Prob. 3.30MCQCh. 3 - Prob. 3.31MCQCh. 3 - Prob. 3.32MCQCh. 3 - The direct electrical connection of the windings...Ch. 3 - Consider Figure 3.25 of the text for a transformer...Ch. 3 - (a) An ideal single-phase two-winding transformer...Ch. 3 - An ideal transformer with N1=1000andN2=250 is...Ch. 3 - Consider an ideal transformer with...Ch. 3 - A single-phase 100-kVA,2400/240-volt,60-Hz...Ch. 3 - Prob. 3.5PCh. 3 - Prob. 3.6PCh. 3 - Consider a source of voltage v(t)=102sin(2t)V,...Ch. 3 - Prob. 3.8PCh. 3 - Prob. 3.9PCh. 3 - A single-phase step-down transformer is rated...Ch. 3 - For the transformer in Problem 3.10. The...Ch. 3 - Prob. 3.12PCh. 3 - A single-phase 50-kVA,2400/240-volt,60-Hz...Ch. 3 - A single-phase 50-kVA,2400/240-volt,60-Hz...Ch. 3 - Rework Problem 3.14 if the transformer is...Ch. 3 - A single-phase, 50-kVA,2400/240-V,60-Hz...Ch. 3 - The transformer of Problem 3.16 is supplying a...Ch. 3 - Using the transformer ratings as base quantities,...Ch. 3 - Using the transformer ratings as base quantities....Ch. 3 - Using base values of 20 kVA and 115 volts in zone...Ch. 3 - Prob. 3.21PCh. 3 - A balanced Y-connected voltage source with...Ch. 3 - Figure 3.32 shows the oneline diagram of a...Ch. 3 - For Problem 3.18, the motor operates at full load,...Ch. 3 - Consider a single-phase electric system shown in...Ch. 3 - A bank of three single-phase transformers, each...Ch. 3 - A three-phase transformer is rated...Ch. 3 - For the system shown in Figure 3.34. draw an...Ch. 3 - Consider three ideal single-phase transformers...Ch. 3 - Reconsider Problem 3.29. If Va,VbandVc are a...Ch. 3 - Prob. 3.31PCh. 3 - Determine the positive- and negative-sequence...Ch. 3 - Consider the three single-phase two-winding...Ch. 3 - Three single-phase, two-winding transformers, each...Ch. 3 - Consider a bank of this single-phase two-winding...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - Consider a three-phase generator rated...Ch. 3 - The leakage reactance of a three-phase,...Ch. 3 - Prob. 3.40PCh. 3 - Consider the single-line diagram of the power...Ch. 3 - For the power system in Problem 3.41, the...Ch. 3 - Three single-phase transformers, each rated...Ch. 3 - A 130-MVA,13.2-kV three-phase generator, which has...Ch. 3 - Figure 3.39 shows a oneline diagram of a system in...Ch. 3 - The motors M1andM2 of Problem 3.45 have inputs of...Ch. 3 - Consider the oneline diagram shown in Figure 3.40....Ch. 3 - With the same transformer banks as in Problem...Ch. 3 - Consider the single-Line diagram of a power system...Ch. 3 - A single-phase three-winding transformer has the...Ch. 3 - The ratings of a three-phase three-winding...Ch. 3 - Prob. 3.52PCh. 3 - The ratings of a three-phase, three-winding...Ch. 3 - An infinite bus, which is a constant voltage...Ch. 3 - A single-phase l0-kVA,2300/230-volt,60-Hz...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - A two-winding single-phase transformer rated...Ch. 3 - A single-phase two-winding transformer rated...Ch. 3 - Prob. 3.59PCh. 3 - PowerWorid Simulator case Problem 3_60 duplicates...Ch. 3 - Rework Example 3.12 for a+10 tap, providing a 10...Ch. 3 - A 23/230-kV step-up transformer feeds a...Ch. 3 - The per-unit equivalent circuit of two...Ch. 3 - Reconsider Problem 3.64 with the change that now...Ch. 3 - What are the advantages of correctly specifying a...Ch. 3 - Why is it important to reduce the moisture within...Ch. 3 - What should be the focus of transformer preventive...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- The given zero sequence matrix is known. .At bus 1 there is a single generator connected with sequence reactance O of. j2 ohms. At bus 2, there are two motors connected, M1 and M2, each with zero sequence reactance of j2 ohms. j2 ohms zero sequence reactance. Motor M2 at bus 2 is solidly grounded.. For these conditions: a. Determine whether or not the generator at bus 1 is grounded. b. Establish the value of the grounding of motor M1. ZBUS (0) Z11 =j 11.42857 Z12 =j 1.42657 Z22 j1.42857 =arrow_forwardThe figure below shows the one-line diagram of a four- bus power system. The voltages, the scheduled real power and reactive powers, and the reactances of transmission lines are marked at this one line diagram (The voltages and reactances are in PU referred to 100 MW base. The active power P2 in MW is the last three digits (from right) of your registration number (i.e for the student that has a registration number 202112396, P2 =396). [10] Starting from an estimated voltage at bus 2, bus 3, and bus 4 equals V2 (0) = 1.15<0°, V3 = 1.15 < 0°, V4 1.1< 0°. 1- Specify the type of each bus and known & unknown quantities at each bus. 2- Find the elements of the second row of the admittance matrix (i.e. [Y21 Y22 Y23 Y24]). 3- Using Gauss-Siedal fınd the voltage at bus 2 after the first iteration. 4- Using Newton-Raphson, calculate: |- The value of real power (P2), at bus 2 after the first iteration. Il- The second element in the first row of the Jacobian matrix after the first iteration. 2 P2…arrow_forwardtwo alternators A and B having 5% speed regulation are working in parallel at a station. Alternator A is rated at 15 MW while B is at 20 MW. When the total load to be shared is 12 MW, then how much of the load will be shared by the alternator B?arrow_forward
- A (500 MW) generator is delivering (180 MW) to infinite bus through the unit transformer and double transmission lines. The per-unit ractances for a given system are shown in figure below andall the reactances are based on (100 MW) base. The generator emf is ( 1.35p .u.). Determine whether the system remains stable after one circuit of the lines is switch off?arrow_forward2.2. The figure below shows a radial transmission system with a generator having a per-unit voltage of 1.3 at an angle of 9 degree p.u. The load demand is 47MW at a power factor of 0.96lagging. Use the nameplate values of Transformer 2 as base values and calculate the following: Correct answers to three decimal places : 25..Per unit impedance of transformer and it's angle 26.Per unit voltage of the line and its angle 27.Per unit impedance of the line and its angle. And Reactance of the transmission line when the load consumes full-load (Ω).arrow_forwardProblem 2 Two shunt generators A and B operate in parallel and their load characteristics maybe taken as straight lines. The voltage falls from 240V at no load to 200V at200A, while that of B falls from 245V at no load to 220V at 150A. Determine the bus bar voltage when supplying 66.9KW load. How is the load divided between two generators?arrow_forward
- Assign the following statements by "Agree", or “Disagree". 1- It is better to use ferrite core instead of iron core in power transformer. 2- The no-load losses are smaller in power transformers as compared with that of the distribution transformers. 3- The core cooling in core-type transformers is better as compared with that of the shell-type. 4- The inrush current can be reduced in transformers by using hard magnetic material core. 5- The inrush current can be reduced in transformers by using soft magnetic material core. 6- The inrush current can be reduced in transformers by using hard magnetic material core with low residual magnetization. 7- The inrush current can be reduced in transformers by using soft magnetic material core with low residual magnetization. 8- Increasing the stacking factor will increase the weight of the transformer. 9- The hysteresis losses is the most effective part of iron losses in transformer. 10- The transformer design procedure is still depending on…arrow_forwardA synchronous generator is connected through a transformer and a transmission line to synchronous motor. The rated voltage and apparent power of the generator serve as the base quantities for this power system. On the system base, the per-unit sub transient reactance of the generator and the motor are 0.15 and 0.40 respectively, the series reactance of the transformer is 0.10, and the series reactance of the transmission line is 0.20. All resistances may be ignored. The generator is supplying rated apparent power and voltage at a power factor of 0.85 lagging when a three-phase synchronous fault occurs at the terminals of the motor. Find the per-unit sub transient current at the fault, in the generator, and in the motor.arrow_forwardb) Two synchronous generators, G2 and G2, are connected parallelly supplying a load. Generator G1 has a no-load frequency of 50.5 Hz and a slope of 300 MW/Hz. Generator G2 has a no-load frequency of 50.2 Hz and a slope of 500 MW/Hz. The load consumes 250 MW real power. (1) At what frequency does this system operate, and how much power is supplied by each of the two generators? (ii) An additional 100 MW load is added to this power system. What is the new system frequency, and how much power do G1 and G2 supply? (iii) The governor set point of G2 is changed to control system frequency back to 50 Hz. Determine the G2 governor set point.arrow_forward
- A 600 KVA generator with X"a = 0.22 per unit is connected to a bus through a circuit breaker, as shown in the following figure. Connected through circuit breakers to the same bus are three synchronous motors rated 200 KVA, 2.5 KV, 1.0 power factor, with X"a = 0.15 per unit. The motors are operating at full load, unity power factor and rated voltage, with the load equally divided among the machines. (a) Find the rated symmetrical short-circuit current in Amperes, which must be interrupting breakers A and B for a fault at point P. Simplify the calculations by neglecting the Prefault current. M. GHA Barrow_forwardDiscuss the role of FACTS (Flexible Alternating Current Transmission Systems) devices in power system control and optimization.arrow_forwardb) A fault occurs at bus 3 of the network shown in Figure Q4. Pre-fault nodal voltages throughout the network are of 1 p.u. and the impedance of the electric arc is neglected. Sequence impedance parameters of the generator, transmission lines, transformer and load are given in Figure Q4. V₁ = 120° p.u. V₂ = 120° p.u. V₂ = 1/0° p.u. V₂= 120° p.u. jXj0.1 p.u. JX2) 0.1 p.u. jX0j0.15 p.u. jXn-j0.2 p.u. 1 JX(2)-j0.2 p.u. 2 jX)=j0.25 p.u. JX20-10.15 p.u. jXa(z)-j0.2 p.u. 4 jX2(0)=j0.2 p.u. jXT(1) j0.1 p.u. jXT(2)=j0.15 p.u. jXT(0)=j0.1 p.u. Figure Q4. Circuit for problem 4b). = jXj0.1 p.u. j0.1 p.u. - JX(2) JXL(0) 10.1 p.u. = (i) Assuming a balanced excitation, draw the positive, negative and zero sequence Thévenin equivalent circuits as seen from bus 3. (ii) Determine the positive sequence fault current for the case when a three- phase-to-ground fault occurs at bus 3 of the network. (iii) Determine the short-circuit fault current for the case when a one-phase- to-ground fault occurs at bus…arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
How does a Transformer work - Working Principle electrical engineering; Author: The Engineering Mindset;https://www.youtube.com/watch?v=UchitHGF4n8;License: Standard Youtube License