Question

An electrical load operates at 240 V rms. The load absorbs an average power of 8 kW at a lagging power factor of 0.8.
a) Calculate the complex power load. (Answer: (8 + j6) kVA)
b) Calculate the impedance of the load. (Answer: (4.608 + j3.456) Ω

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer