(a)
The mass flow rate of the refrigerant through the upper cycle.
(a)
Answer to Problem 59P
The mass flow rate of the refrigerant through the upper cycle is
Explanation of Solution
Express the specific enthalpy at state 2 using Carnot efficiency.
Here, specific enthalpy at state 1, 2 and 2s is
Express specific enthalpy at state 3.
Here, specific enthalpy at saturated liquid and pressure of
Write the specific enthalpy at state 3 is equal to state 4 due to throttling process.
Here, specific enthalpy at state 3 and 4 is
Express specific enthalpy at state 5.
Here, specific enthalpy at saturated vapor and pressure of
Express specific entropy at state 5.
Here, specific entropy at saturated vapor and pressure of
Express the specific enthalpy at state 6 using Carnot efficiency.
Here, specific enthalpy at state 5, 6 and 6s is
Express specific enthalpy at state 7.
Here, specific enthalpy at saturated liquid and pressure of
Write the specific enthalpy at state 7 is equal to state 8 due to throttling process.
Here, specific enthalpy at state 7 and 8 is
Express the mass flow rate of the refrigerant through the upper cycle.
Here, mass flow rate of the refrigerant through the lower cycle is
Conclusion:
Refer Table A-12, “saturated refrigerant-134a-pressure table”, and write the properties corresponding to pressure of
Here, specific entropy and enthalpy at state 1 is
Refer Table A-13, “superheated refrigerant 134a”, and write the specific enthalpy at state 2s corresponding to pressure at state 2 of
Write the formula of interpolation method of two variables.
Here, the variables denote by x and y is specific entropy at state 2 and specific enthalpy at state 2s respectively.
Show the specific enthalpy at state 2s corresponding to specific entropy as in Table (1).
Specific entropy at state 2 |
Specific enthalpy at state 2s |
0.9384 | 263.48 |
0.9420 | |
0.9704 | 273.03 |
Substitute
Thus, the specific enthalpy at state 2s is,
Substitute
Perform unit conversion of pressure at state 3 and 5 from
Refer Table A-12, “saturated refrigerant-134a-pressure table”, and write the property corresponding to pressure at state 3
Substitute
Substitute
Refer Table A-12, “saturated refrigerant-134a-pressure table”, and write the properties corresponding to pressure of
Substitute
Substitute
Perform unit conversion of pressure at state 6 from
Refer Table A-13, “superheated refrigerant 134a”, and write the specific enthalpy at state 6s corresponding to pressure at state 6 of
Show the specific enthalpy at state 6s corresponding to specific entropy as in Table (2).
Specific entropy at state 2 |
Specific enthalpy at state 6s |
0.9107 | 276.17 |
0.9271 | |
0.9389 | 285.47 |
Use excels and tabulates the values from Table (2) in Equation (X) to get,
Substitute
Refer Table A-12, “saturated refrigerant-134a-pressure table”, and write the property corresponding to pressure at state 7
Substitute
Substitute
Substitute
Hence, the mass flow rate of the refrigerant through the upper cycle is
(b)
The rate of heat removal from the refrigerated space.
(b)
Answer to Problem 59P
The rate of heat removal from the refrigerated space is
Explanation of Solution
Express the rate of heat removal from the refrigerated space.
Conclusion:
Substitute
Hence, the rate of heat removal from the refrigerated space is
(c)
The COP of the refrigerator.
(c)
Answer to Problem 59P
The COP of the refrigerator is
Explanation of Solution
Express the power input.
Express the COP of the refrigerator.
Conclusion:
Substitute
Substitute
Hence, the COP of the refrigerator is
Want to see more full solutions like this?
Chapter 11 Solutions
EBK THERMODYNAMICS: AN ENGINEERING APPR
- Refrigerators currently being manufactured in the United States are using______as their refrigerant.arrow_forwardConsider a two-stage cascade refrigeration system operating between the pressure limits of 0.8 and 0.14 MPa. Each stage operates on the ideal vapor-compression refrigeration cycle with refrigerant-134a as the working fluid. Heat rejection from the lower cycle to the upper cycle takes place in an adiabatic counter-flow heat exchanger where both streams enter at about 0.4 MPa. If the mass flow rate of the refrigerant through the upper cycle is 0.24 kg/s, determine (a) the mass flow rate of the refrigerant through the lower cycle, (b) the rate of heat removal from the refrigerated space and the power input to the compressor, (c) the coefficient of performance of this cascade refrigerator, and (d) the intermediate pressure of the cascade cycle. For full credit, accurately, neatly draw the cascade system on an electronic PDF p-h diagram. Please only solve part d. If possible, show the ph diagramarrow_forwardConsider a two-stage cascade refrigeration system operating between the pressure limits of 1.4 MPa and 280 kPa using refrigerant-134a as the working fluid. The heat rejection from the lower cycle to the upper cycle occurs in an adiabatic counterflow heat exchanger where the pressures in the upper and lower cycles are 0.5 MPa and 600 kPa, respectively. In both cycles, the refrigerant exits the condenser as a saturated liquid and enters the compressor as a saturated vapor. The isentropic efficiency of the compressors is 85 percent. Given the mass flow rate of the refrigerant through the lower cycle is 0.18 kg/s, calculate: (a) The mass flow rate of the refrigerant through the upper cycle. (b) The rate of heat extraction from the cooling area. (c) The Coefficient of Performance (COP) of this refrigeration system.arrow_forward
- Consider a two-stage cascade refrigeration system operating between 0.1MPa and 1MPa. Each stage operates on the ideal cycle with R-134a as the working fluid. Heat rejection from the lower to the upper cycle occurs at 0.4MPa. If the mass flow rate in the upper cycle is 0.1 kg/s, Determine:(a) the mass flow rate through the lower cycle and (b)the COP.arrow_forwardConsider a two-stage cascade refrigeration system operating between the pressure limits of 0.8 and 0.14 MPa. Each stage operates on an ideal vapor-compression refrigeration cycle with refrigerant-134a as the working fluid. Heat rejection from the lower cycle to the upper cycle takes place in an adiabatic counterflow heat exchanger where both streams enter at about 0.32 MPa. (In practice, the working fluid of the lower cycle is at a higher pressure and temperature in the heat exchanger for effective heat transfer.) If the mass flow rate of the refrigerant through the upper cycle is 0.05 kg/s, determine (a) The mass flow rate of the refrigerant through the lower cycle in kg/s, (b) The rate of heat removal from the refrigerated space in kW, (c) The power input to the compressor in kW, (d) The coefficient of performance of this cascade refrigerator.arrow_forwardConsider a two-stage cascade refrigeration system operating between -80 o C and 80 o C. Each stage operates on an ideal vapor-compression refrigeration cycle. Upper cycle use R- 12 as working fluid, lower cycle use R- 13. In the lower cycle refrigerant condenses at O o C, in the upper cycle refrigerant evaporates at -5 o C. If the mass flow rate in the lower cycle is 1 kg/s, determine what would with COP be if we consider a one-stage ideal vapor-compression system between -80 o C and 80 o C with R-13 as the working fluid? 1.21 O 1.51 1.48 O No COParrow_forward
- A refrigerator uses refrigerant-134a as the working fluid and operates on an ideal vapor-compression refrigeration cycle between 0.12 and 0.9 MPa. The mass flow rate of the refrigerant is 0.05 kg/s which exits the condenser as saturated liquid. (a) Show the cycle on a P-h and T-s diagram with respect to saturation lines. (b) Determine the rate of heat removal from the refrigerated space and the power input to the compressor, and (c) the coeifficient of performance.arrow_forward1) Consider a two-stage cascade refrigeration system operating on an ideal vapor-compression refrigeration cycle between the pressure limits of 1.2 MPa and 120 kPa with refrigerant-134a as the working fluid. Heat rejection from the lower cycle to the upper cycle takes place in an adiabatic counterflow heat exchanger where the pressure in the upper and lower cycles are 0.6 and 0.7 MPa, respectively. In both cycles, the refrigerant is a saturated liquid at the condenser exit and a saturated vapor at the compressor inlet. The mass flow rate of the refrigerant through the lower cycle is 0.27 kg/s. Find: a) The mass flow rate of the upper cycle b) The Heat removed from the refrigerated space c) The COPR Notes: The pressures of the adiabatic counterflow heat exchanger are different (upper 0.6 MPa and lower 0.7 MPa). Notice that the upper pressure is greater than the lower.arrow_forwardAn ideal refrigerant-134a vapor-compression refrigeration cycle operates between 0.14 MPa and 0.7 MPa. The mass flow rate of the refrigerant is 0.15 kg/s. Determine the rate of heat removal from the refrigerated space, kW.arrow_forward
- A vapor-compression refrigeration cycle with refrigerant-134a as the working fluid operates between pressure limits of 240 and 1600 kPa. The isentropic efficiency of the compressor is 78%. Determine (a) the heat absorption in the evaporator, (b) the heat rejection in the condenser, (c) the work input, and (d) the COParrow_forwardAs a new engineer at CoolTech, you have been assigned to evaluate the performance of a cutting-edge refrigeration unit that uses R-134a as the working fluid. This unit operates on an ideal vapor compression cycle between 0.2 MPa and 0.9 MPa, and the mass flow rate of the refrigerant is 0.08 kg/s. Your task is to analyze the cycle and determine the following key performance indicators: (a) Calculate the rate at which the refrigeration unit removes heat from the refrigerated space. (4 pts) (b) Determine the power input required for the compressor. (3 pts) (c) Evaluate the heat rejection rate in the condenser. (3 pts) Bonus (1 pts) Compute the Coefficient of Performance (COP).arrow_forwardA refrigerator uses refrigerant-134a as its working fluid and operates on the ideal vapor-compression refrigeration cycle. The refrigerant evaporates at 5.00°F and condenses at 180 psia. This unit serves a 45000 Btu/h cooling load. Determine the mass flow rate of the refrigerant and the power that this unit will require. (Take the required values from saturated refrigerant-134a tables.) (Round the final answers to three decimal places.) The mass flow rate of the refrigerant is Ibm/h, and the power requirement is kW.arrow_forward
- Refrigeration and Air Conditioning Technology (Mi...Mechanical EngineeringISBN:9781305578296Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill JohnsonPublisher:Cengage Learning