When connected to 230 V (rms) ,50 Hz power line, a load absorbs 4 kW at a lagging power factor of 0.8. Find the supply current in phasor form and the value of capacitance necessary to raise the power factor to 0.95 lagging.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.7P: Let a 100V sinusoidal source be connected to a series combination of a 3 resistor, an 8 inductor,...
icon
Related questions
Question
When connected to 230 V (rms),50 Hz power line, a load absorbs 4 kW at a lagging power
factor of 0.8. Find the supply current in phasor form and the value of capacitance
necessary to raise the power factor to 0.95 lagging.
Transcribed Image Text:When connected to 230 V (rms),50 Hz power line, a load absorbs 4 kW at a lagging power factor of 0.8. Find the supply current in phasor form and the value of capacitance necessary to raise the power factor to 0.95 lagging.
Expert Solution
steps

Step by step

Solved in 4 steps with 4 images

Blurred answer
Knowledge Booster
Single phase AC circuit
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning