Q1) I. A 100 kVA, three-phase ideal transformer has 4950 turns on the primary and 180 turns on the secondary winding. The primary is connected to 11000-volt. Calculate: Power Loss ,Secondary e. m. f., maximum flux in the core, Primary and Secondary currents on full-load.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.28MCQ
icon
Related questions
Question
Q1) I. A 100 kVA, three-phase ideal transformer has 4950
turns on the primary and 180 turns on the secondary winding.
The primary is connected to 11000-volt. Calculate: Power Loss
, Secondary e. m. f., maximum flux in the core, Primary and
Secondary currents on full-load.
Transcribed Image Text:Q1) I. A 100 kVA, three-phase ideal transformer has 4950 turns on the primary and 180 turns on the secondary winding. The primary is connected to 11000-volt. Calculate: Power Loss , Secondary e. m. f., maximum flux in the core, Primary and Secondary currents on full-load.
Expert Solution
steps

Step by step

Solved in 4 steps with 3 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning