EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN: 9781337516549
Author: Simmons
Publisher: CENGAGE LEARNING - CONSIGNMENT
expand_more
expand_more
format_list_bulleted
Textbook Question
Chapter 26, Problem 17R
Circle the correct answer from the following statements:
- a. Conductors for fire alarm systems are not permitted to be installed in the same raceways, cables, or electrical boxes as the light and power conductors.
- b. It is permissible to install fire alarm conductors in the same raceways, cables, or electrical boxes as the light and power conductors because the conductors for fire alarm systems covered in Article 760 are small and would easily fit into other electrical raceways and boxes.
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
7.B. The size of a grounding electrode conductor for a service or separately derived system is generally basedon the size of the largestA. ungrounded supply conductor.B. equipment grounding conductor.C. grounded electrode.D. bonding jumper.7.C. Which of the following statements about bonding is true?A. The joint or termination must offer opposition in the circuit for effective electrical connections.B. Effective bonding keeps impedance high if a fault should occur.C. The entire electrical safety circuit is only as good as its strongest bonded link.D. Bonding connections must endure high levels of fault current until overcurrent protective devices can operate.
5. Which of the following descriptions of a ground ring is correct?A. A ground ring is a circular formation that's made up of six or more grounding electrodes.B. A ground ring is a coiled conductor that's buried underneath a utility pole.C. A ground ring is a device that's used to clamp a conductor to a water pipe.D. A ground ring is a bare copper conductor that will encircle an entire structure underground.
h.1. In an alternating-current system, the maximum size for a copper grounding electrode conductor isA. 250 kcmil.B. 3/0.C. 500 kcmil.D. 4/0.
h.2. The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.
Chapter 26 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Ch. 26 - In your own words, explain the terms alarm and...Ch. 26 - The requirements for household fire alarm systems...Ch. 26 - Do heat alarms and carbon monoxide alarms take the...Ch. 26 - Name two basic ways that smoke alarms are powered.Ch. 26 - Name the two types of smoke alarms.Ch. 26 - List the absolute minimum level of smoke alarm...Ch. 26 - Circle the correct answer from the following...Ch. 26 - Circle the correct answer from the following...Ch. 26 - Circle the correct answer from the following...Ch. 26 - Prob. 10R
Ch. 26 - Prob. 11RCh. 26 - An important but often overlooked requirement in...Ch. 26 - Carbon monoxide is ____________, and is...Ch. 26 - Circle the correct answer from the following...Ch. 26 - The wiring of more complex household fire alarm...Ch. 26 - Circle the correct answer from the following...Ch. 26 - Circle the correct answer from the following...Ch. 26 - Fire alarm cable generally used in more complex...Ch. 26 - When installing a fire alarm system or a complete...Ch. 26 - Residential sprinkler fire protection systems are...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- a.2. Which of the following statements about grounding electrode conductors is true?A. They restrict the ground connection.B. They eliminate potential differences between conductive objects and the Earth electrode.C. They facilitate operation of overcurrent protective devices.D. They perform bonding between the Earth and grounded conductors.a.3. Main bonding jumpers are required to be made of _______ or other corrosion-resistant material.A. brassB. aluminumC. copperD. copper-clad aluminumarrow_forward12. Which of the following statements about ground faults is true?A. They can happen if a conductive tool is dropped in an energized equipment's electrical enclosure.B. They usually occur between any grounded circuit conductor and the equipment grounding conductor.C. They can't result from human error.D. They're often normal and typically intentional.arrow_forwardThe purpose of Informative Annex H is toA. safeguard persons and property from hazards arising from the use of electricity.B. list the requirements for the removal of wiring and systems.C. provide a set of administrative and enforcement provisions that supplements the Code. D. explain the process of mandatory plan design review.arrow_forward
- 18. What should be done with light sources that are connected at each end of a cable while it's being repaired?A. They should be turned off and disconnected.B. They should be turned off only.C. Nothing, they can be left alone.D. They should be disconnected only.arrow_forwardThis is done to ensure that no potential difference can appear between any of exposed metal parts of electrical and non-electrical installations under fault conditions. a. Earthing & Bonding b. Bonding only c. Earthing only d. Either bonding or earthingarrow_forward4.A. If a bonding jumper is installed from a grounded metal box to a grounding-type receptacle, the length ofthe bonding jumper will be betweenA. 2 and 4 feet.B. 2 and 4 inches.C. 6 and 10 feet.D. 6 and 10 inches.4.B. Why isn't solder permitted to be relied on for grounding electrode connections?A. The solder increases the chances of a ground-fault event occurring.B. The heat from the solder weakens the connection and exposes it to physical damage.C. The use of solder doesn't meet the requirements for corrosive influences.D. The connection's integrity can be negatively affected by heat during a ground-fault event.4>c. Which of the following statements about bonding is true?A. The strike terminals of a lightning protection system must be bonded to the building or structure grounding electrode system.B. Bonding requirements on the supply side of the service disconnect are less restrictive.C. Wire-type supply-side bonding jumpers are usually short in length and installed from the…arrow_forward
- 20.a. What's the primary disadvantage of using copper conductors?A. DurabilityB. CostC. AvailabilityD. Weight20.b. The NEC requires that each service-disconnecting means be suitable forA. hazardous locations.B. disconnecting the meter.C. wet conditions.D. the prevailing conditions 20.c. As a general rule, each building or structure is limited to a single service. What's an automatic exceptionto this rule?A. A second service deemed suitable for useB. A second service having the proper markingsC. Emergency systems or fire pumpsD. Higher building occupancyarrow_forwardc.1. Which of the following is one of the three essential functions of an equipment grounding conductor?A. Provide an arc-fault current pathB. Establish groundingC. Establish bondingD. Ensure the system is groundedc.2. What's another name for the three-point method of Earth resistance testing?A. Fall-of-potentialB. Line surgeC. Spatial shieldingD. Leakage current c.3. If the National Electrical Code provides a requirement to ground equipment, it generally implies thatthere will be a direct connection to the Earth of a connection through a/anA. grounding electrode conductor.B. equipment grounding conductor.C. equipotential bonding conductor.D. bonding conductor.arrow_forward3List out common electrical hazards and give risk level for each of themarrow_forward
- Most residential general lighting circuits are wired with 14-AWG copper conductors and are protected by 15-amp circuit breakers. However, there are many electricians who install 12-AWG copper conductors and protect them with 20-amp circuit breakers. How will you know which conductor size and which circuit breaker size will be used for the general lighting branch circuits in the house you are wiring?arrow_forward5 a) Discuss Electricity power generation and distribution to residential properties. b) with diagrams explain how a Distribution Board is wired to provide electricity to a residential property. c) Explain the following materials and Accessories. i. Male and female bushings. ii male and female adaptors iii. Couplings. iv. Wire/cable sizes and their usarrow_forward19. Which of the following statements about securing and protecting grounding electrode conductors istrue? A. Grounding electrode conductors should not be installed on or run through wood framing members.B. Grounding electrode conductors aren't required to comply with burial depths.C. There's no acceptable method to splice grounding electrode conductors together.D. The electrical worker is typically responsible for judging whether a grounding electrode conductor is exposed to potentialdamage.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENTElectricity for Refrigeration, Heating, and Air C...Mechanical EngineeringISBN:9781337399128Author:Russell E. SmithPublisher:Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Electricity for Refrigeration, Heating, and Air C...
Mechanical Engineering
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Cengage Learning
Types of Protective Relays and Design Requirements, Part 1a.; Author: GeneralPAC: Power System Tutorials;https://www.youtube.com/watch?v=JYil4T5VSDM;License: Standard Youtube License