The missing values in the table.
Answer to Problem 2PP
ET = 54 V | ER = 54 V | EC = 54 V |
IT = 2.5 A | IR = 1.5 A | IC = 2 A |
Z = 21.6 Ω | R = 36 Ω | XC = 27 Ω |
VA = 135 | P = 81 W | VARSC = 108 |
PF = 60 % | ∠θ =53.13 ° | C =14.736 µF |
Explanation of Solution
Given data:
The capacitive reactance XC is calculated as,
The value of the capacitor is,
The voltage drop across the capacitor,
Since the circuit is parallel R-C,
The current flowing through resistance IR will be,
The total current flowing in the parallel R-C network is,
The apparent power VA is given as,
The true power P is given as,
The reactive power VARSC is calculated as,
Power factor (PF) is calculated as,
Power factor angle θ will be,
Want to see more full solutions like this?
Chapter 22 Solutions
Delmar's Standard Textbook Of Electricity
- A single phase, 50Hz transmission line connected between two buses having line resistance of 3Ω, inductive reactance of 0.2 Henry. Both the ends of transmission lines are connected with series capacitors of 400microfarads each for series compensation. Then series impedance of the line is a.(3-j31) Ω b.(3-j59.6) Ω c.(3+j31)Ω d.(3+j59.6) Ω 2- Fast decoupled algorithm is not as accurate as the exact Newton Raphson algorithm for Variable number of iteration Fixed number of iteration Variable time per iteration Fixed time per iterationarrow_forwardA power transmission line of 33kV (maximum) carries a maximum current of 1200A is connecting the two areas. A PMMC voltmeter of (0-600V) range and a PMMC ammeter of (0-25A) range are to be used for measurement of voltage and currents of the transmission line. 1.Design and draw a circuit with suitable instrument transformers for the measurement. Use sample values for winding turns. 2.On a particular day, the readings shown by the meters were 17.5A and 440V. Calculate the actual voltage and current in the transmission line.arrow_forwardThe electrical power supply system of a particular country is made of the following. Draw asingle line diagram of the electrical power supply system of the country based on the informationbelow using any computer-aided software.Power supply from an infinite bus bar S connected to bus bar A, through a circuit breakerconnected between isolators and a three-phase delta/star solidly earthed transformer T1.Powersupply source from a generator G1 connected to bus bar B through a circuit breaker connectedbetween isolators, and a three- phase delta/star solidly earthed transformer T2. power supplysources from two generators G2 and G3. Each of the generators are connected to a reactor.Furthermore, each of the generators connected to a common bus bar C through a circuit breakerconnected between isolators and a three-phase star/star solidly earthed transformer T3 and T4respectively. bus bar F to bus bar A by means of two isolators, one at each end of transmissionline L6; bus bar A to bus bar E by…arrow_forward
- Electric Machine; Check image, all question there. Consider the above approximate equivalent circuit for IM. A six-pole, 220Volt (line to line), 50Hz, Y connected, three phase IM has the following on a per phase basis: R1=0.5Ω , R2=0.25 Ω, X1=0.75 Ω, X2=0.5 Ω, Xm=100 Ω, Rc=500 Ω The friction and windage loss is 150 W. Determine the following at its rated slip of 3.5% a)Total Impedance(Zt) b)Rotor Copper Loss c)Core loss(Pm) d)Shaft Power(P0) e)Efficiencyarrow_forwardElectric Machine-check image, all question there. Consider the above equivalent circuit of IM, A six pole, 250 volt(line to line), 60Hz, Y connected , three phase IM has the following parameters on a per phase basis: R1=0.125Ω , R2=0.45 Ω, X1=0.5 Ω, X2=0.75 Ω, Xm=50 Ω, Rc=225 Ω The friction and windage loss is 115 W. Determine the following at its rated slip of 1.5% a)Excitation Circuit b)Power developed by motor(Pd) c)Shaft Power(Pshaft) d)Shaft Torque(Tshaft) e)Efficiencyarrow_forwardElectric Machine - Check image, all question there. Consider the above equivalent circuit of IM, A six pole, 250 volt(line to line), 60Hz, Y connected , three phase IM has the following parameters on a per phase basis: R1=0.125Ω , R2=0.45 Ω, X1=0.5 Ω, X2=0.75 Ω, Xm=50 Ω, Rc=225 Ω The friction and windage loss is 115 W. Determine the following at its rated slip of 1.5% a)Excitation Circuit b)Power developed by motor c)Shaft Power(Pshaft) d)Shaft Torque(Tshaft) e)Efficiencyarrow_forward
- The resistance and reactance of the single-phase 60Hz transmission line conductors are 8.8 ohm and 10.4 ohm respectively. The transmission line delivers 55MW at a power factor of 0.78 lagging to the load with 50kV receiving end voltage. Determine the following a) The inductance of the transmission line in mH Answer for part 1 b) Sending end power factor Answer for part 2 c) Percentage voltage regulation Answer for part 3 d) Percentage Efficiency Answer for part 4arrow_forwardDEGREE: ELECTRICAL ENGINEERING SUBJECT/COURSE: AC CIRCUITS NOTE: Please solve in this way. 1. Please have a good handwriting, some of the answers are not readable. Thank you! 2. GIVEN.(include symbols and units) 3. REQUIRED/FIND/MISSING (with symbol/s) 4. ILLUSTRATION (Required). 5. STEP-by-STEP SOLUTION with Formulas and Symbols. No Shortcut, No skipping, and detailed as possible 6. FINAL ANSWERS must be rounded up to three decimal places PROBLEM: • A delta-connected load whose phase impedances are ZAB=50 Ω, ZBc=-j50 Ω, and ZcA=j50Ω is fed by a balanced wye-connected three phase source with Vp=100 V. Find the phase currents.arrow_forwardGiven a 400sq.m single family dwelling unit to be provided with 230V, 1-phase, 2-wire service, and having the following loads: 2-1.5hp A/C, 2-1.0hp A/C, 1-0.5hp water pump, 4-800W water heater, 2-6kW electric range and 2-1kW microwave oven, determine the total connected load in volt-ampere (VA). Write your answer in numerical format without decimal places.arrow_forward
- A short 3, 3 wire transmission line has an impedance per wire of 15+j20 Ω. The sending end line to line voltage is 13,200 V and the receiving end load takes 1,000 kW at a lagging power factor and the current per conductor is 70 A. What is the receiving end voltage and power factor? Note: draw the current and voltage vector diagram to facilitate your solution.arrow_forward-In distribution substation, the shunt compensation used is of ----------- in nature. -The sample large power system network data's are given below, The total number of buses is 5 Three-phase short circuit fault subjected at the bus 5 The initial voltage of the faulted bus is 1.0 p.u The Zbus matrix element Z55 is 0.774 p.u Fault impedance Zf= 0.41 p.u Fault current (If )in p.u Answer....?arrow_forwardThe single line diagram of a power system is shown below. Load represented as impedance, (13.2) kV voltage It draws 60 MVA power from the system when it is below and (0.9) back power factor. Generators and transformers The related electrical parameters are given below. According to this; a) Calculate all impedances in this given circuit in pu and draw the equivalent impedance diagram of the circuit. (Select the base values as 100 MVA and 13.8 kV.) b) Since the voltage values of the generators are given as E1=1.1∟0° pu and E2=1.25∟10° pu, Calculate the value of the voltage (V1).arrow_forward
- Introductory Circuit Analysis (13th Edition)Electrical EngineeringISBN:9780133923605Author:Robert L. BoylestadPublisher:PEARSONDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningProgrammable Logic ControllersElectrical EngineeringISBN:9780073373843Author:Frank D. PetruzellaPublisher:McGraw-Hill Education
- Fundamentals of Electric CircuitsElectrical EngineeringISBN:9780078028229Author:Charles K Alexander, Matthew SadikuPublisher:McGraw-Hill EducationElectric Circuits. (11th Edition)Electrical EngineeringISBN:9780134746968Author:James W. Nilsson, Susan RiedelPublisher:PEARSONEngineering ElectromagneticsElectrical EngineeringISBN:9780078028151Author:Hayt, William H. (william Hart), Jr, BUCK, John A.Publisher:Mcgraw-hill Education,