The load in milling factory is having active and reactive power of 100 kW and 59.33 kVAr, respectively at voltage supply of 415 V. A capacitor bank system (PFC) with voltage rating 515 V is to be installed with the target to increase the power factor to 95%. The PFC has the step arrangement of 1:1:2:2:3 :3 with 5 kVAr for each capacitor unit. (1) Analyse the average power factor and the minimum effective reactive power, O, injected into supply system. (ii) Examine the effective reactive power, Qceff to be supplied by capacitor bank and the total unit steps of power factor corrector to be switched 'ON'. (iii) Estimate the actual average power factor for the system based on the unit step recommended in Q(e)(ii). (iv) Justify the implication of total unit steps of power factor corrector if 3.3kVAr per unit of capacitor is to be used in the factory.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter6: Power Flows
Section: Chapter Questions
Problem 6.61P
icon
Related questions
icon
Concept explainers
Question
(e) The load in milling factory is having active and reactive power of 100 kW and 59.33
kVAr, respectively at voltage supply of 415 V. A capacitor bank system (PFC) with
voltage rating 515 V is to be installed with the target to increase the power factor to
95%. The PFC has the step arrangement of 1:1:2:2:3:3 with 5 kVAr for each
capacitor unit.
(i) Analyse the average power factor and the minimum effective reactive power,
Os injected into supply system.
(ii) Examine the effective reactive power, Qceff to be supplied by capacitor bank
and the total unit steps of power factor corrector to be
(iii) Estimate the actual average power factor for the system based on the unit step
recommended in Q(e)(ii).
(iv) Justify the implication of total unit steps of power factor corrector if 3.3kVAr
per unit of capacitor is to be used in the factory.
Transcribed Image Text:(e) The load in milling factory is having active and reactive power of 100 kW and 59.33 kVAr, respectively at voltage supply of 415 V. A capacitor bank system (PFC) with voltage rating 515 V is to be installed with the target to increase the power factor to 95%. The PFC has the step arrangement of 1:1:2:2:3:3 with 5 kVAr for each capacitor unit. (i) Analyse the average power factor and the minimum effective reactive power, Os injected into supply system. (ii) Examine the effective reactive power, Qceff to be supplied by capacitor bank and the total unit steps of power factor corrector to be (iii) Estimate the actual average power factor for the system based on the unit step recommended in Q(e)(ii). (iv) Justify the implication of total unit steps of power factor corrector if 3.3kVAr per unit of capacitor is to be used in the factory.
Expert Solution
steps

Step by step

Solved in 5 steps

Blurred answer
Knowledge Booster
Synchronous Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning