The following data were obtained from space cooling load survey of an Air-Conditioning (AC) system of a Conference Hall: Sensible Heat Load Latent heat Load 10.5 tons 2.0 tons Design inside condition is set at 22 C dry bulb temperature and 60 percent relative humidity. Cold air is supplied to the Hall at 14 °C. The AC system is designed with mass ratio of 4:1 total supplied cooled air to required minimum outdoor ventilation air. Outdoor air is 30 °C dry bulb and 70% relative humidity. Determine: a) Recommend an AC system suitable to the set-up above. b) What is the air-cooling apparatus SHF? c) What is the probable Apparatus Dewpoint (ADP)? d) What is the probable cooling coil Bypass Factor (BPF) of the cooling apparatus? e) Fan capacity needed that supplies air to the hall in liters/hour

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter42: Heat Gains And Heat Losses In Structures
Section: Chapter Questions
Problem 1RQ: An oversized air-conditioning system will A. cost more to install and operate. B. be more efficient...
icon
Related questions
Question
100%
The following data were obtained from space cooling load survey of an Air-Conditioning (AC)
system of a Conference Hall:
Sensible Heat Load
Latent heat Load
10.5 tons
2.0 tons
Design inside condition is set at 22 C dry bulb temperature and 60 percent relative humidity. Cold
air is supplied to the Hall at 14 °C. The AC system is designed with mass ratio of 4:1 total supplied
cooled air to required minimum outdoor ventilation air. Outdoor air is 30 °C dry bulb and 70 %
relative humidity.
Determine:
a) Recommend an AC system suitable to the set-up above.
b) What is the air-cooling apparatus SHF?
c) What is the probable Apparatus Dewpoint (ADP)?
d) What is the probable cooling coil Bypass Factor (BPF) of the cooling apparatus?
e) Fan capacity needed that supplies air to the hall in liters/hour
f)
Refrigeration capacity of the Air-Cooling Apparatus in tons
Transcribed Image Text:The following data were obtained from space cooling load survey of an Air-Conditioning (AC) system of a Conference Hall: Sensible Heat Load Latent heat Load 10.5 tons 2.0 tons Design inside condition is set at 22 C dry bulb temperature and 60 percent relative humidity. Cold air is supplied to the Hall at 14 °C. The AC system is designed with mass ratio of 4:1 total supplied cooled air to required minimum outdoor ventilation air. Outdoor air is 30 °C dry bulb and 70 % relative humidity. Determine: a) Recommend an AC system suitable to the set-up above. b) What is the air-cooling apparatus SHF? c) What is the probable Apparatus Dewpoint (ADP)? d) What is the probable cooling coil Bypass Factor (BPF) of the cooling apparatus? e) Fan capacity needed that supplies air to the hall in liters/hour f) Refrigeration capacity of the Air-Cooling Apparatus in tons
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning