Problem 3 Consider a 100 kVA, 7200/240 V, 60 Hz transformer. Assume that the open-circuit and short-circuit tests were performed on the transformer and that the following data were obtained: Voltmeter Ammeter Wattmeter ii. iii. Open-Circuit Test (on Primary) Voc=7200 V Loc=0.65 A Poc=425 W Short-Circuit Test (on Primary) Vc=250V Isc=13.889 A Psc = 1420W Also assume that the transformer operates at full load with a 0.90 lagging power factor. If the given power factor belongs to the load, not to the transformer, determine the following: i. The equivalent impedance, resistance, and reactance of the transformer all referred to the primary side Total losses, including the copper and core losses, at full load The efficiency of the transformer

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.16P: A single-phase, 50-kVA,2400/240-V,60-Hz distribution transformer has the following parameters:...
icon
Related questions
Question
Please ? help o have no knowledge in this field With explanations
Problem 3
Consider a 100 kVA, 7200/240 V, 60 Hz transformer. Assume that the open-circuit and short-circuit
tests were performed on the transformer and that the following data were obtained:
ii.
iii.
iv.
Voltmeter
Ammeter
Wattmeter
V.
Open-Circuit Test
(on Primary)
Voc=7200 V
Loc=0.65 A
Poc=425 W
Also assume that the transformer operates at full load with a 0.90 lagging power factor. If the given
power factor belongs to the load, not to the transformer, determine the following:
i. The equivalent impedance, resistance, and reactance of the transformer all referred to the primary
side
Short-Circuit Test
(on Primary)
Vsc=250V
Isc=13.889 A
Psc = 1420W
Percent voltage regulation of the transformer
The phasor diagram of the transformer
Total losses, including the copper and core losses, at full load
The efficiency of the transformer
Transcribed Image Text:Problem 3 Consider a 100 kVA, 7200/240 V, 60 Hz transformer. Assume that the open-circuit and short-circuit tests were performed on the transformer and that the following data were obtained: ii. iii. iv. Voltmeter Ammeter Wattmeter V. Open-Circuit Test (on Primary) Voc=7200 V Loc=0.65 A Poc=425 W Also assume that the transformer operates at full load with a 0.90 lagging power factor. If the given power factor belongs to the load, not to the transformer, determine the following: i. The equivalent impedance, resistance, and reactance of the transformer all referred to the primary side Short-Circuit Test (on Primary) Vsc=250V Isc=13.889 A Psc = 1420W Percent voltage regulation of the transformer The phasor diagram of the transformer Total losses, including the copper and core losses, at full load The efficiency of the transformer
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 6 steps with 6 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning