Calculate the number of luminaires required in the room of length 12.46m and Width 5.91m. If 100 W, 1356lm bulb is selected to install in that room with a required illuminance level of 169lx and each luminaire is equipped with 3 bulbs. Assume Utilisation and maintenance factor around 0.71.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter13: Transmission Lines: Transient Operation
Section: Chapter Questions
Problem 13.9P
icon
Related questions
Question

Calculate the number of luminaires required in the room of length 12.46m and Width 5.91m. If 100 W, 1356lm bulb is selected to install in that room with a required illuminance level of 169lx and each luminaire is equipped with 3 bulbs. Assume Utilisation and maintenance factor around 0.71. 