EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN: 9781337516549
Author: Simmons
Publisher: CENGAGE LEARNING - CONSIGNMENT
expand_more
expand_more
format_list_bulleted
Concept explainers
Question
thumb_up100%
Electrical engineering
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution
Trending nowThis is a popular solution!
Step by stepSolved in 2 steps with 2 images
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- Most residential general lighting circuits are wired with 14-AWG copper conductors and are protected by 15-amp circuit breakers. However, there are many electricians who install 12-AWG copper conductors and protect them with 20-amp circuit breakers. How will you know which conductor size and which circuit breaker size will be used for the general lighting branch circuits in the house you are wiring?arrow_forwardThe following problems refer to grounding requirements. Give the source of yourresponses. 1. What is the minimum size copper grounding electrode conductor for a service withthree sets of parallel 350 kcmil conductors (three conductors per phase)?arrow_forwardThe following problems refer to grounding requirements. Give the source of yourresponses.1. What is the proper size copper grounding electrode conductor for a 100-ampere service that consists of 3/0 AWG ungrounded conductors?arrow_forward
- 20.a. What's the primary disadvantage of using copper conductors?A. DurabilityB. CostC. AvailabilityD. Weight20.b. The NEC requires that each service-disconnecting means be suitable forA. hazardous locations.B. disconnecting the meter.C. wet conditions.D. the prevailing conditions 20.c. As a general rule, each building or structure is limited to a single service. What's an automatic exceptionto this rule?A. A second service deemed suitable for useB. A second service having the proper markingsC. Emergency systems or fire pumpsD. Higher building occupancyarrow_forwardThe voltage drop percentage for a panel feeder with a no continuous load of 180A, using 3/0 THWN copper conductors at 480V, three-phase, and a length of 248' isarrow_forwardThe following problems refer to grounding requirements. 1. What is the minimum size copper grounding electrode conductor for a service with three sets of parallel 350 kcmil conductors (three conductors per phase)?arrow_forward
- 13. If the largest ungrounded service-entrance conductor for a service is 750-kcmil copper, what is the minimum size required for a wire-type main bonding jumper for the service? a) 2/0 AWG copper b) 1/0 AWG copper c) 3/0 AWG copper d) 1 AWG copper 14. If the total circular mil area of the largest ungrounded service-entrance conductor for a service is 2000-kcmil copper, what is the minimum size required for a wire-type main bonding jumper for the service? a) 4/0 AWG copper b) 250-kcmil copper c) 350-kcmil copper d) 500-kcmil copper 15. The minimum-size grounded conductor for a service supplied by a grounded system shall not be smaller than the minimum size required for a(n)______. a) Equipment grounding conductor b) System bonding jumper c) Ungrounded conductor d) Grounding-electrode conductorarrow_forwardof p o How many conductors enter the ceiling fan/light wall box? Switch ond out let boxes s tirst 10. What type and size of box may be used for the ceiling fan/light wall box?. 11. What type of covers are used with 4 in. square outlet boxes? 12. a. Does the circuit for the Master Bedroom have a grounded circuit conductor? b. Does it have an equipment grounding conductor? c. Explain the difference between a "grounded" conductor and an "equipment grounding" conductor. 13. Approximately how many feet (meters) of 2-wire cable and 3-wire cable are needed to ft complete the circuit supplying the Master Bedroom? Two-wire cable: ft (- m). m). Three-wire cable: 14. If the cable is laid in notches in the corner studs, what protection for the cable must be provided? 15. How high are the receptacles mounted above the finished floor in this bedroom? 16. Approximately how far from the bedroom door is the first receptacle mounted? (See the plans.) 17. What is the distance from the finished floor to…arrow_forwardHANDWRITTEN needed.arrow_forward
- 11. Which of the following statements about the use of structural steel as an equipment grounding conductor (EGC) in an AC system is correct? A. Structural steel can be used as an EGC when it's bonded at both ends.B. Structural steel isn't allowed for use as an EGC.C. Structural steel must have an EGC bonding jumper every three feet of structure. D. Structural steel can be used as an EGC bonding jumper between panelboards. 12. Which of the following statements about equipment grounding conductors is true? A. They increase voltages above ground potential on conductors and equipment enclosures during normal operation. B. Unacceptable equipment grounding conductors include conduit, tubing, and cable armor. C. They must be capable of withstanding the higher level of ground-fault current to perform their safety function. D. When they're far from their associated circuit conductors, impedance values are kept as low as possible during ground-fault conditions. 13. Imagine that…arrow_forward2.a. What's defined as an assembly consisting of a service raceway, guy wires or braces, service head, andany fittings necessary for the termination and support of overhead service conductors?A. Drip loopB. Service lateralC. Service dropD. Service mast 2.b. What's likely to happen when connected parallel conductors are different lengths?A. An NEC violationB. Misidentification of conductor cablesC. An uneven distribution of currentD. Conductor terminationarrow_forwardh.1. In an alternating-current system, the maximum size for a copper grounding electrode conductor isA. 250 kcmil.B. 3/0.C. 500 kcmil.D. 4/0. h.2. The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENTDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning