A 3-Phase,3 Wire secondary distribution system with balanced per phase loads at a,b and c feeding from a 11kV/415 V transformer as shown in fig.2. Determine the following: a. the total voltage drop of the feeder in p.u.; b. the total per phase real power (P); c. the total per phase reactive power(Q); d. the total (3-phase) kVA output of transformer and its load power factor. 415 V 11kV 0.04 + j0.012 0.08 + j0.042 0.08 + j0.042 30 A 0.707 40 A UPF 50 A 0.8 lag lag Fig. 2 None of these (a) 36.56 V (b) 54.3 kW (c) 72.3 KVAR (d) 101.72 kVA, 0.80 lagging (a) 26.56 V (b) 34.3 kW (c) 22.3 KVAR (d) 71.72 kVA, 0.98 lagging (a) 16.56 V (b) 24.3 kW (c) 12.3 KVAR (d) 81.72 kVA, 0.89 lagging

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.65P: Reconsider Problem 3.64 with the change that now Tb includes both a transformer of the same turns...
icon
Related questions
icon
Concept explainers
Question
A 3-Phase,3 Wire secondary distribution system with balanced per phase loads at a,b and c feeding from a
11kV/415 V transformer as shown in fig.2. Determine the following:
a. the total voltage drop of the feeder in p.u.;
b. the total per phase real power (P);
c. the total per phase reactive power(Q);
d. the total (3-phase) kVA output of transformer and its load power factor.
415 V
11kV
0.04 + j0.012 0,08 + j0.042 0.08 + j0.042
30 A
0.707
40 A
UPF
50 A
0.8 lag
lag
Fig. 2
None of these
(a) 36.56 V
(b) 54.3 kW
(c) 72.3 KVAR (d) 101.72 kVA, 0.80 lagging
(а) 26.56 V
(b) 34.3 kW
(c) 22.3 KVAR (d) 71.72 kVA, 0.98 lagging
(а) 16.56 V
(b) 24.3 kW (c) 12.3 KVAR (d) 81.72 kVA, 0.89 lagging
Transcribed Image Text:A 3-Phase,3 Wire secondary distribution system with balanced per phase loads at a,b and c feeding from a 11kV/415 V transformer as shown in fig.2. Determine the following: a. the total voltage drop of the feeder in p.u.; b. the total per phase real power (P); c. the total per phase reactive power(Q); d. the total (3-phase) kVA output of transformer and its load power factor. 415 V 11kV 0.04 + j0.012 0,08 + j0.042 0.08 + j0.042 30 A 0.707 40 A UPF 50 A 0.8 lag lag Fig. 2 None of these (a) 36.56 V (b) 54.3 kW (c) 72.3 KVAR (d) 101.72 kVA, 0.80 lagging (а) 26.56 V (b) 34.3 kW (c) 22.3 KVAR (d) 71.72 kVA, 0.98 lagging (а) 16.56 V (b) 24.3 kW (c) 12.3 KVAR (d) 81.72 kVA, 0.89 lagging
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning