In problem 35, it is desired to keep the voltage drop to 3% maximum. What minimum size wire would be installed to accomplish this 3% maximum voltage drop? See 210.19(A), Informational Note No. 4 and 215.2(A)(1), Informational Note No. 2.
Find the minimum size wire that should be installed to accomplish 3% maximum voltage drop.
Answer to Problem 36R
10 AWG or larger value conductor should be installed to accomplish 3% maximum voltage drop.
Explanation of Solution
Given data:
Supply voltage is 120-volt.
Current is 10 A.
The distance between panel and heater is approximately 140 ft.
14 AWG, 12 AWG, 10AWG, and 8 AWG copper conductor.
Calculation:
Write the expression for voltage drop in a single-phase circuit.
Here,
K is the approximate resistance in ohms per circular-mil foot at
I is the current, and
CMA is cross-sectional area of the conductors.
Modify Equation (1) for 14 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 14 AWG is 4110.
Substitute
Modify Equation (1) for 12 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 12 AWG is 6530.
Substitute
Modify Equation (1) for 10 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 10 AWG is 10,380.
Substitute
Modify Equation (1) for 8 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 8 AWG is 16,510.
Substitute
Tabulate the calculated value of the voltage drop as shown in Table 1.
Table 1
Sl. No. | Conductor Size | Voltage drop |
1 | 14 AWG | |
2 | 12 AWG | |
3 | 10 AWG | |
4 | 8 AWG |
Find the value of
Compare the obtained value of 3% voltage drop of applied voltage with voltage drops of each conductor as tabulated in Table 1.
A voltage drop of 8AWG conductor (that is 2.19 Volts drop) is less than
Conclusion:
Thus, 10 AWG or larger value conductor should be installed to accomplish 3% maximum voltage drop.
Want to see more full solutions like this?
Chapter 4 Solutions
Electrical Wiring: Residental - With Plans (Paperback) Package
Additional Engineering Textbook Solutions
Electric Circuits (10th Edition)
Electric Motors and Control Systems
Principles Of Electric Circuits
Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
Electric Circuits. (11th Edition)
Programmable Logic Controllers
- 2. A cable one mile long and 0.50 inch in diameter is composed of a steel core 0.25 inch in diameter and the is Ps and Pa 57.4 and 17.5 ohm Cmil/ft, outside shell is aluminum. The resistance of the cable is respectively a. 0.447 ohm c. 0.625 ohm b. 0.893 ohm d. 5.3 ohmsarrow_forwardHow does the skin effect phenomenon affect the performance of copper cables?arrow_forwardWhat is the minimum trade size PVC conduit to contain 201 #12AWG TW75 Copper conductors.arrow_forward
- What is the voltage rating of the conductors in Type NMC cable? _______________arrow_forwardThe three bus-bar conductors in an outdoor sub-station are supplied by units of post insulators. Each unit consists of a stack of 3-pin insulators fixed one on the top of the other. The voltage across the lowest insulator is 8-45 kV and that across the next is 7-25 kV. Find the bus-bar voltage of the station.arrow_forwardExplain the procedure involved to determine core loss and copper loss with neat diagrams (Scan and upload handwritten report)arrow_forward
- h.1. In an alternating-current system, the maximum size for a copper grounding electrode conductor isA. 250 kcmil.B. 3/0.C. 500 kcmil.D. 4/0. h.2. The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.arrow_forwardWhy ACSR Conductors are preferred over Copper Conductors?arrow_forwardWhich of the following Surge Diverter use non-linear resistances in its fabrication? Rod - Gape SD. Lightning Arrester SD. Expulsion Tube SD. O All of the above.arrow_forward
- 1. Describe the physics of the eddy current testing technique;arrow_forwardMost residential general lighting circuits are wired with 14-AWG copper conductors and are protected by 15-amp circuit breakers. However, there are many electricians who install 12-AWG copper conductors and protect them with 20-amp circuit breakers. How will you know which conductor size and which circuit breaker size will be used for the general lighting branch circuits in the house you are wiring?arrow_forward2. Which of the symbols in Figure A6 represents a circuit breaker with thermal overload protection?A. CB. DC. AD. Barrow_forward
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage LearningEBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT