Chapter 29, Problem 4PP
To determine

The missing values in the given table.

Expert Solution & Answer
Check Mark

Answer to Problem 4PP

Primary Secondary Load
EP = 23000 V EP = 120 V EP = 208 V
IP = 0.626A IP = 120.08 A IP = 69.33 A
EL = 23000 V EL = 208 V EL = 208 V
IL = 1.084 A IL = 120.08 A IL = 120.08 A
Ratio = 191.52:1 Z = 3 Ω

Explanation of Solution

EBK DELMAR'S STANDARD TEXTBOOK OF ELECT, Chapter 29, Problem 4PP

In the figure, three single-phase transformers have been connected to form a delta–wye bank.

The primary is connected to a three-phase line of 23000 V.

The secondary voltage is 208 V.

A three-phase resistive load with an impedance of 3 Ω per phase is connected to the secondary of the transformer.

The primary windings of the three single-phase transformers are connected to form a delta connection. In a delta connection, the phase voltage is equal to line voltage.

EP(PRIMARY)=EL(PRIMARY)=23000 V

The secondary windings are connected as a wye. In a wye connection, the phase voltage is less than the line voltage by a factor of 1.732 (the square root of 3). Therefore, the phase value of the primary voltage can be calculated using the formula

EP(SECONDARY)=EL(SECONDARY)1.732=2081.732=120 V

The turns ratio can be calculated by comparing the phase voltage of the primary with the phase voltage of the secondary:

Ratio=Primary VoltageSecondary Voltage=23000120.09=191.521Ratio=191.52:1

The load is connected directly to the output of the secondary. The line voltage applied to the load must therefore be the same as the line voltage of the secondary:

EL(LOAD)=208 V

The load bank is connected in a delta connection. The voltage across the phase of the load bank will equal to the line voltage.

EP(LOAD)=EL(LOAD)=208 V

The phase current of the load can be calculated using Ohm’s law:

IP(LOAD)=EP(LOAD)Z=2083= 69.33 A

The amount of line current supplying a delta-connected load will be 1.732 times the phase current of the load:

IL(LOAD)=1.732×IP(LOAD)           =1.732×69.33           =120.08 A

Since the secondary of the transformer is supplying current to only one load, the line current of the secondary will be the same as the line current of the load:

IL(SECONDARY)=120.08 A

The phase current in a wye connection is equal to the line current.

IP(SECONDARY)=IL(SECONDARY)=120.08 A

The phase current of the transformer primary can now be calculated using the phase current of the secondary and the turns ratio. Because the primary has a higher voltage than the secondary, it will have a lower current. (Volts times amperes input must equal volts times amperes output.)

IP(PRIMARY)=IP(SECONDARY)Turns Ratio=120.08191.52= 0.626 A

All the transformed values of voltage and current take place across the phases, the primary has a phase current of 6.68 A. In a delta connection, the line current is 1.732 times the phase current:

IL(PRIMARY)=1.732×IP(PRIMARY)              =1.732×0.626              =1.084 A

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
In transformer, the power will _________________________________ with decrease in voltage. be doubled remain same increases decreases
Write in Briefly about circuit breaker, current transformer and voltage transformer
Belonging to a phase measured from a 220/48 V phase transformer, no-load (no load) operation and short-circuit test. values are given in the table below. Low voltage by applying rated voltage to the high voltage (primary) winding. voltage (secondary) winding ends were left unloaded and the results of the no-load operation test were obtained. low voltage By applying nominal current to the windings, the high voltage windings are short-circuited and short-circuit test results are obtained. has been done. In addition, the transformer with 5 V direct voltage applied to the high voltage winding is 2.2 A direct current. attracts. Calculate all equivalent circuit elements moved to the high voltage side. Boşta çalışma testi Gerilim 220 V Güç 80 W Akım 0,44 A Kısa devre testi Gerilim 12 V Güç Akım 65 W 16,1 A
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:PEARSON
Text book image
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
Text book image
Programmable Logic Controllers
Electrical Engineering
ISBN:9780073373843
Author:Frank D. Petruzella
Publisher:McGraw-Hill Education
Text book image
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:9780078028229
Author:Charles K Alexander, Matthew Sadiku
Publisher:McGraw-Hill Education
Text book image
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:9780134746968
Author:James W. Nilsson, Susan Riedel
Publisher:PEARSON
Text book image
Engineering Electromagnetics
Electrical Engineering
ISBN:9780078028151
Author:Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:Mcgraw-hill Education,
How does a Transformer work - Working Principle electrical engineering; Author: The Engineering Mindset;https://www.youtube.com/watch?v=UchitHGF4n8;License: Standard Youtube License