EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN: 9781337516549
Author: Simmons
Publisher: CENGAGE LEARNING - CONSIGNMENT
expand_more
expand_more
format_list_bulleted
Textbook Question
Chapter 23.1, Problem 17R
Electric heating cable embedded in plaster, or sandwiched between layers of dry wall, creates heat. Therefore, any nonmetallic-sheathed cable run above these ceilings and buried in insulation must have its current-carrying capacity derated according to the (40°C) (50°C) (60°C) correction factors found in Table 310.15(B)(2)(a) in the NEC. (Circle the correct answer.)
Expert Solution & Answer
Trending nowThis is a popular solution!
Students have asked these similar questions
We are running 3 wires in an IMC to a control panel with a 150 amp circuit breaker disconnect in the control panel. The conduit is run 12 inches above the roof on a strut rack. The ambient air temperature is 88 degrees. This control panel feeds the #1 cooling fan. What sized ungrounded conductors do we need? All conductors have typeTHHN insulation.
A #1 AWG
B 100 Kcmil
C #1/0 AWG
D #10 AWG
What sized IMC do we need?
A 3/4"
B 1 1/4"
C 1"
D 1 1/2"
UPVOTE WILL BE GIVEN. WRITE THE COMPLETE SOLUTIONS LEGIBLY (HANDWRITTEN) NO LONG EXPLANATION NEEDED. SOLVE IN 3 DECIMAL PLACES. BOX THE FINAL ANSWER.
Most residential general lighting circuits are wired with 14-AWG copper conductors and are protected by 15-amp circuit breakers. However, there are many electricians who install 12-AWG copper conductors and protect them with 20-amp circuit breakers. How will you know which conductor size and which circuit breaker size will be used for the general lighting branch circuits in the house you are wiring?
Chapter 23 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Ch. 23.1 - a. What is the allowance in watts made for...Ch. 23.1 - What are some of the advantages of electric...Ch. 23.1 - List the different types of electric heating...Ch. 23.1 - There are two basic voltage classifications for...Ch. 23.1 - What device is required when the total connected...Ch. 23.1 - Prob. 6RCh. 23.1 - Prob. 7RCh. 23.1 - A certain type of control connects electric...Ch. 23.1 - What advantages does a 240-volt heating unit have...Ch. 23.1 - The white wire of a cable may be used to connect...
Ch. 23.1 - Receptacle outlets furnished as part of a...Ch. 23.1 - The branch circuit supplying a fixed electric...Ch. 23.1 - Prob. 13RCh. 23.1 - For ballpark calculations, the wattage output of a...Ch. 23.1 - A central electric furnace heating system is...Ch. 23.1 - What section of the Code provides the correct...Ch. 23.1 - Electric heating cable embedded in plaster, or...Ch. 23.2 - Prob. 1RCh. 23.2 - Prob. 2RCh. 23.2 - Prob. 3RCh. 23.2 - a. Must an air conditioner installed in a window...Ch. 23.2 - Prob. 5RCh. 23.2 - What is the Code requirement for receptacles...Ch. 23.2 - Prob. 7RCh. 23.2 - When the nameplate on an air-conditioning unit...Ch. 23.2 - Prob. 9RCh. 23.2 - Match the following terms with the statement that...Ch. 23.2 - The disconnect for an air conditioner or heat pump...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- 5. A DC motor that draws 7.2A is located 85 feet from its 240VDC source. The copper conductors supplying the motor operate at 68°F. Voltage drop on the conductors must be limited to 2% for the motor to properly operate. What size, in circular mils, copper conductors are required for this installation?arrow_forwardQUESTION 8 We are running 3 wires in an IMC to a control panel with a 150 amp circuit breaker disconnect in the control panel. The conduit is run 12 inches above the roof on a strut rack. The ambient air temperature is 88 degrees. This control panel feeds the #1 cooling fan. What sized ungrounded conductors do we need? All conductors have typeTHHN insulation.arrow_forwarda. Does the circuit for the Master Bedroom have a grounded circuit conductor? ____________________ b. Does it have an equipment grounding conductor? ____________________ c. Explain the difference between a grounded conductor and an equipment grounding conductor. ____________________ ____________________arrow_forward
- What assumptions can you make regarding the following receptacle wiring? Check all that apply. White neutral wire Grounding screw Brass screw terminal Silver screw terminal Black hot wire Red hot wire Grounding wires Grounding screw terminal O device is at end-of-run device box does not need a ground connection this is a split-circuit receptacle neutral side receptacle tab must be removedarrow_forwardSix 1/0 aluminum conductors are to be run in a conduit. Each conductor has type THWN insulation's, and the ambient air temperature is 30 degrees celcius. What is the ampacity of each conductor?arrow_forwardGrounding lighting fixtures. Threre are specific requirements for grounding lighting fixtures. How must they be grounded and with what size conductors?arrow_forward
- Calculate the minimum copper conductor size needed for 120/240 V electric range branch circuit the electric range has a nameplate rating of 12 KW?arrow_forwardA feeder is installed to feed a sub panel. The feeder starts at a 400-amp breaker, utilizing (2) parallel 4/0 THWN-2 copper conductors in the same conduit. What size is the copper equipment grounding conductor required to be? OA. Parallel (2) #1/0 B. #3 OC. #1/0 OD. Parallel (2) #4/0arrow_forwardit's urgent please solve asaparrow_forward
- We are running 3 wires and a ground in a RMC to a control panel with a 60 amp circuit breaker disconnect in the control panel. The conduit is run along the ceiling where the ambient air temperature is 100 degrees. The control panel feeds our secondary cooling pump. What size are the ungrounded conductors? All conductors have typeTHHN insulation. A #6 AWG B 600 Kcmil C #8 AWG D #2 AWG What size RMC do we need? A 3" B 3/4" C 1" D 1 1/2"arrow_forwardA free-standing electric range is rated 11.8 kW, 120/240 volts. The wiring method is nonmetallic-sheathed cable. Use the 60°C column of Table 310.16 in conformance to 110.14(C). Answer the following questions: According to Column C, Table 220.55, what is the maximum demand? What is the minimum size for the ungrounded copper conductors? What is the minimum size neutral copper conductor? What is the correct rating for the branch-circuit overcurrent protection?arrow_forwardHow many lighting branch circuits are provided in this dwelling? __________ a. What is the minimum load allowance for small-appliance circuits for dwellings? See NEC 220.52(A). __________ b. An individual 15-ampere branch circuit is run to the receptacle outlet behind the refrigerator instead of connecting it to one of the two 20-ampere small-appliance branch circuits that are required in kitchens. For this separate circuit, an additional 1500 volt-amperes (shall) (does not have to) be added to the load calculations for dwellings. (Circle the correct answer.)arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Introduction to 8051 Microcontroller | Part 1 | Bharat Acharya Education; Author: Bharat Acharya Education;https://www.youtube.com/watch?v=2-geyR_aM28;License: Standard Youtube License