In the diagram, Load A is rated at 10 amperes, 120 volts. Load B is rated at 5 amperes, 120 volts.
- a. When connected to the 3-wire branch circuit as indicated, how much current will flow in the neutral conductor? __________________
- b. If the neutral conductor should open, to what voltage would each load be subjected, assuming both loads were operating at the time the neutral conductor opened? Show all calculations.
a.
Find the amount of current that flows in a neutral conductor when a circuit is connected to a 3-wire branch circuit.
Answer to Problem 4R
The amount of current that flows in the neutral conductor is
Explanation of Solution
Given data:
The values of current and voltage at Load A are
The values of current and voltage at Load B are
The total voltage of the system is
Calculation:
From the given data, the values of current to Load A and Load B are not equal. Therefore, it is an unbalanced load.
For an unbalanced load, the current through the neutral conductor is calculated as follows:
Substitute
Conclusion:
Thus, the amount of current that flows in the neutral conductor is
b.
Find the voltage of each load when the neutral conductor is open.
Answer to Problem 4R
The voltage of Load A is
Explanation of Solution
Formula used:
Write an expression to calculate the resistance.
Here,
Calculation:
Substitute
Substitute
When the neutral conductor is open, Load A and Load B are connected in series. Therefore, the total resistance is calculated as follows:
Substitute
Rearrange equation (2) to find
Substitute
Rearrange equation (4) to find
For the series connected load, the current is same for both Load A and Load B.
Substitute
Substitute
Conclusion:
Thus, the voltage of Load A is
Want to see more full solutions like this?
Chapter 17 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Additional Engineering Textbook Solutions
ELECTRICITY FOR TRADES (LOOSELEAF)
Programmable Logic Controllers
Introductory Circuit Analysis (13th Edition)
Microelectronics: Circuit Analysis and Design
Fundamentals of Applied Electromagnetics (7th Edition)
Electrical Engineering: Principles & Applications (7th Edition)
- How far are the insulator chairs of the 3rd Rail spaced from one another along the tracks?arrow_forwardWhat precautions must be utilized and maintained when setting up or using a Delata 4 wire system that is to serve both 240 V and 120 V single phase loads?arrow_forwardIn the conduit diagram shown in Figure 1–3, determine how many wires are in each conduit between each piece of equipment. Identify each wire terminal connection and the quantity of wires, as shown in the example, above the disconnect switch.arrow_forward
- a. Does the circuit for the Master Bedroom have a grounded circuit conductor? ____________________ b. Does it have an equipment grounding conductor? ____________________ c. Explain the difference between a grounded conductor and an equipment grounding conductor. ____________________ ____________________arrow_forwardexplain substation earthing with diagramarrow_forwardFour No. 12 and four No. 10 conductors are to be installed in a EMT conduit 600 V jacketed. What size EMT conduit is required if a. The conductors are Type T90 Nylon? b. The conductors are Type RW90?arrow_forward
- 5. How many system bonding jumpers normally are there for a separately derived system that's grounded? A. ThreeB. TwoC. One D. Zero 6. How many grounded neutral conductors are in a 208Y/120 volt, 3-phase, 4-wire system? A. ThreeB. TwoC. One D. Four 7. Which of the following are sometimes installed as an emergency system, legally required standby system, or optional standby power system for a building or structure? A. GeneratorsB. Surge protection devices C. Surge arrestersD. Transformers 8. If the system bonding jumper in a DC system is a screw, what color must the screw be? A. WhiteB. RedC. Orange D. Green 9. If overcurrent protection is provided in the transformer of a separately derived system, which of the following statements is correct? A. An equipment grounding conductor must be run with the conductors between the transformer and the building's disconnect. B. There's no need for service equipment or a panelboard in the separate building.C. A ground electrode must…arrow_forwardWhich of the following statements about equipment grounding conductors (EGCs) is true?A. The National Electrical Code permits the EGC to also perform as a grounding electrode conductor.B. More than one EGC must be used if multiple circuits are installed in a single raceway, cable, or cable tray.C. No current should be present in the EGC during normal operation.D. EGCs are required to be decreased in size to address voltage drop.arrow_forwardWhat is the rated ampacity per phase for six No. 3/0 THHN copper current-carrying conductors with two conductors per phase ( parallel) and all conductors installed in the same conduit? a. 280 b. 315 c. 320 d. 360 Please show work/code references to go with if possible!arrow_forward
- What is grading of cables.Explain?arrow_forwardEquipment Grounding 10. Which of the following statements about ground faults is true?A. They usually occur between any grounded circuit conductor and the equipment grounding conductor. B. They're often normal and typically intentional.C. They can't result from human error.D. They can happen if a conductive tool is dropped in an energized equipment's electrical enclosure.arrow_forwardWhat size conductor should be used in a 2-wire system to service a load of 6,500 watts, 150 feet from the generator? The voltage at the load is 120 volts, and the voltage drop should not exceed 2.5 volts. Round to a whole number. value of K for copper is 10.8arrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT