The following table shows the boring log at a site where a multi-story shopping center would be constructed. Soil classification and the standard penetration number, N60, are provided in the boring log. All columns of the building are supported by square footings which must be placed at a depth of 1.5 m. Additionally, the settlement (elastic) of each footing must be restricted to 20 mm. Since the column loads at different location can vary, a design chart is helpful for quick estimation of footing size required to support a given load.
- a. Prepare a chart by plotting the variation of maximum allowable column loads with footing sizes, B = 1 m, 1.5 m, 2 m, and 3 m. Use a factor of safety of 3.
- b. If the gross column load from the structure is 250 kN, how would you use this chart to select a footing size?
- c. What would be the design footing size for the column in Part (b) if you use Terzaghi’s bearing capacity equation? For the well graded sand, assume that ϕ′ = 33°. Use Fs = 3.
- d. Compare and discuss the differences in footing sizes obtained in Parts b and c.
(a)
Plot the variation of maximum allowable column loads with size of footings to prepare a chart.
Explanation of Solution
Given information:
The location of depth of footing
The given size of the footing B is 1 m, 1.5 m, 2 m, and 3 m.
The settlement of each footing
The given factor of safety
Calculation:
For B value is 1 m:
Determine the depth factor using the relation.
Substitute 1.5 m for
The
The field standard penetration number
Determine the depth of foundation for the field standard penetration number gets averaged.
Substitute 1.5 m for
Determine the averaged
Here,
Substitute 12 for
Determine the net allowable bearing capacity of the soil
Substitute 10 for
Determine the maximum allowable column load
Substitute
For B value is 1.5 m:
Determine the depth factor using the relation.
Substitute 1.5 m for
The field standard penetration number
Determine the depth of foundation for the field standard penetration number gets averaged.
Substitute 1.5 m for
Determine the averaged
Here,
Substitute 7 for
Determine the net allowable bearing capacity of the soil
Substitute 8 for
Determine the maximum allowable column load
Substitute
For B value is 2 m:
Determine the depth factor using the relation.
Substitute 1.5 m for
The field standard penetration number
Determine the depth of foundation for the field standard penetration number gets averaged.
Substitute 1.5 m for
Determine the averaged
Substitute 12 for
Determine the net allowable bearing capacity of the soil
Substitute 9 for
Determine the maximum allowable column load
Substitute
For B value is 3 m:
Determine the depth factor using the relation.
Substitute 1.5 m for
The field standard penetration number
Determine the depth of foundation for the field standard penetration number gets averaged.
Substitute 1.5 m for
Determine the averaged
Here,
Substitute 12 for
Determine the net allowable bearing capacity of the soil
Substitute 12 for
Determine the maximum allowable column load
Substitute
Summarize the calculated values as in Table (1).
Width B (m) | Column load (kN) |
1 | 71 |
1.5 | 115 |
2 | 198 |
3 | 507.5 |
Plot the graph between the size of the footing and the column load as in Figure (1).
(b)
Find the footing size for the given gross column load of 250 kN.
Answer to Problem 16.1CTP
The footing size for the given gross column load of 250 kN is
Explanation of Solution
Given information:
The location of depth of footing
The given size of the footing B is 1 m, 1.5 m, 2 m, and 3 m.
The settlement of each footing
The given factor of safety
Calculation:
Refer Figure (1).
The size of the footing is 2.25 m for the gross column load of 250 kN.
Therefore, the footing size for the given gross column load of 250 kN is
(c)
Find the design column load for the footing size of 2.25 m using the Terzaghi’s bearing capacity equation.
Answer to Problem 16.1CTP
The design column load for the footing size of 2.25 m using the Terzaghi’s bearing capacity equation is
Explanation of Solution
Given information:
The value of cohesion
The soil friction angle
The location of depth of footing base
The width of the footing B is 2.25 m.
The given factor of safety
Calculation:
Determine the net ultimate bearing capacity of the soil
Here,
Take the unit weight of the soil
Refer Table 16.1, “Terzaghi’s bearing-capacity factors–
Take the
Substitute
Determine the net allowable bearing capacity
Substitute
Therefore, the design column load for the footing size of 2.25 m using the Terzaghi’s bearing capacity equation is
(d)
Compare and discuss the differences in footing sizes obtained in parts (b) and (c).
Explanation of Solution
Given information:
The soil friction angle
The location of depth of footing base
The width of the footing B is 2.25 m.
The given factor of safety
Calculation:
The net allowable column load obtained by using Terzaghi’s bearing capacity equation (2,173 kN) is significantly higher than the method based on the
Want to see more full solutions like this?
Chapter 16 Solutions
Bundle: Principles Of Geotechnical Engineering, Loose-leaf Version, 9th + Mindtap Engineering, 2 Terms (12 Months) Printed Access Card
- (b) A plate load test was carried out on a ground having a uniform sand stratum up to sufficient depth. The size of the plate was 40 cm x 40 cm Load (kN) 5 10 20 28 38 50 56 Settlement 0.8 1.3 2.25 3.6 6 8.25 11.5 (mm) Plot the load settlement curve. Also determine the bearing capacíty and load that can be taken by a column footing of size 2m x 2m in this soil for an allowable settlement of 25 mmarrow_forwardRectangular footing (4m x 5m) was supported by a saturated clay layer with a thickness of 5m. If the second layer (below the clay) was a saturated sand. The settlement that could be occurred in this site: a. Is only consolidation settlement b. None of the given answers are correct c. Is a short term settlement d. Is only long term settlementarrow_forward2 m 3m 75 EV 1 m A The footing plan is shown loaded uniformly in a rectangular area. What is the value of the increase of stress of the second or loaded area (Aσ₂) to be subtracted?arrow_forward
- A plate-load test was conducted on-site in Cavite in which the soil was found to be clay. PLT was conducted using a circular plate having a diameter of 718 mm. The ultimate load for the test was found to be 693 kN/m2. What should be the maximum allowable load of a footing having a diameter of 3.98 m? Use an FS of 3.89.arrow_forwardA plate load test was carried out on a ground having a uniform sand stratum upto sufficient depth. The size of the plate used was 40 cm x 40 cm. Load (kN) 10 20 30 40 50 Settlement (mm) 2 3.5 5.5 7.5 10.5 Calculate load that can be taken by a column footing of size 3.5 m x 3.5 m in this soil, for an allowable settlement of 1.95 cmarrow_forwardA plate-load test was conducted on-site in Bataan in which the soil was found to be clay. PLT was conducted using a circular plate having a diameter of 800 mm. The ultimate load for the test was found to be 520 kN/m2. What should be the maximum allowable load of a footing having a diameter of 1.5 m? Use an FS of 5. O 183.78 kN O 918.92 kN O 1828.13 kN O 365.63 kN O 261.38 kN O NOT IN THE CHOICES O 52.28 kNarrow_forward
- 5 The proposed design of the footing of a multi-storey shopping complex building consists of a 3m wide square footing subjected to a contact pressure of 0.9MN/m?. The unit weight of the soil supporting the footing is estimated to be 20KN/m' and ground water was expected to be at great depth. You are planning a site investigation for the project. If it is specified that the boring should be carried to a depth where the increase in stress due to the foundation loading is less than 20% of the effective overburden pressure, determine the minimum depth of test boring You may assume P (B+z)L+z)arrow_forwardDuring the subsurface investigation for design of foundation, a standard penetration test was conducted at 4.5 m below the ground surface. The record of number of blows observed on the fine sand at that location is given as in table below. Penetration depth (cm) Number of blows 0-75 75-150 150-225 225-300 300-375 375-450 6 6 14 15 18 20 Assume water table is at a level of 1 m below ground level and correction factor for overburden pressure is 1.2. The correct N-value for the soil would bearrow_forwardExplain how the Mohr-Coulomb failure criterion is used to determine soil shear strength?arrow_forward
- Following are the results obtained from a plate load test performed on a square plate of 30 cm x 30 cm size at a depth of 1.5 m below as, in a homogeneous sand bed. Determine ultimate load which a footing of size 2 mx 2 m placed at 1.5 m below G.L. of the same soil, if allowable settlement is 15 mm. Settlement, mm 0 10 20 30 40 50 60 50 100 Load, kN/m² 150 200 250 300 350 400arrow_forwardA strip footing carries a load 14506 lbs per foot of length. The footing has a width of 2.3 ft. Determine the increase in vertical stress directly below the center of the footing at a depth of 0.8 ft. Provide your answer in psf, to 2 decimal place. Do not include units in your response.arrow_forwardDescribe about the Strain influence factors for use with Schmertmann method to estimate settlement of foundations on sand.arrow_forward
- Principles of Geotechnical Engineering (MindTap C...Civil EngineeringISBN:9781305970939Author:Braja M. Das, Khaled SobhanPublisher:Cengage LearningPrinciples of Foundation Engineering (MindTap Cou...Civil EngineeringISBN:9781337705028Author:Braja M. Das, Nagaratnam SivakuganPublisher:Cengage Learning