Textbook Question
100%
Book Icon
Chapter 16, Problem 13R

In the spaces provided, fill in the cover (depth) for the following residential underground installations. See NEC Table 300.5.

  1. a. Type UF. No other protection. ______________________ in.
  2. b. Type UF below driveway. ______________________ in.
  3. c. Rigid metal conduit under lawn. ______________________ in.
  4. d. Rigid metal conduit under driveway. ______________________ in.
  5. e. Electrical metallic tubing between house and detached garage. ______________________ in.
  6. f. UF cable under lawn. Circuit is 120 volts, 20 amperes, GFCI protected. ______________________ in.
  7. g. Rigid PVC conduit approved for direct burial. No other protection. ______________________ in.
  8. h. Rigid PVC conduit. Circuit is 120 volts, 20 amperes, GFCI protected. ______________________ in.
  9. i. Rigid conduit passing over solid rock and covered by 2 in. (50 mm) of concrete extending down to rock. ______________________ in.

a.

Expert Solution
Check Mark
To determine

Find the cover (depth) for Type UF with no other protection.

Answer to Problem 13R

The cover (depth) for Type UF with no other protection is 24in.(600mm).

Explanation of Solution

Discussion:

The National Electrical Code committee develops NEC – the standard electrical Code and the main objective for the origin of the Code is to protect and safeguard people and elements from electrical hazards. The codes for explaining underground installations are defined in an article NEC 300.5.

According to the table NEC Table 300.5, the depth for the circuits used for control of the irrigation and landscape lighting with Type UF for non-protected areas like streets, driveways, highways, parking lots, and roads is 24in.(600mm).

Conclusion:

Thus, the cover (depth) for Type UF with no other protection is 24in.(600mm).

b.

Expert Solution
Check Mark
To determine

Find the cover (depth) for Type UF below driveway.

Answer to Problem 13R

The cover (depth) for Type UF below driveway is 18in.(450mm).

Explanation of Solution

Discussion:

According to the table NEC Table 300.5, the depth for the circuits used for control of the irrigation and landscape lighting with Type UF for outdoor parking areas, areas used for dwelling purposes and dwelling driveways for one and two families is 18in.(450mm).

Conclusion:

Thus, the cover (depth) for Type UF below driveway is 18in.(450mm).

c.

Expert Solution
Check Mark
To determine

Find the cover (depth) for the rigid metal conduit under lawn.

Answer to Problem 13R

The cover (depth) for the rigid metal conduit under lawn is 6in.(150mm).

Explanation of Solution

Discussion:

According to the table NEC Table 300.5, the depth for the rigid or intermediate metal conduit under lawn areas is 6in.(150mm).

Conclusion:

Thus, the cover (depth) for the rigid metal conduit under lawn is 6in.(150mm).

d.

Expert Solution
Check Mark
To determine

Find the cover (depth) for the rigid metal conduit under driveway.

Answer to Problem 13R

The cover (depth) for the rigid metal conduit under driveway is 18in.(450mm).

Explanation of Solution

Discussion:

According to the table NEC Table 300.5, the depth for the rigid or intermediate metal conduit for parking areas in outdoor section, areas for dwelling purposes and dwelling driveways for one and two families is 18in.(450mm).

Conclusion:

Thus, the cover (depth) for the rigid metal conduit under driveway is 18in.(450mm).

e.

Expert Solution
Check Mark
To determine

Find the cover (depth) for electrical metallic tubing between house and detached garage.

Answer to Problem 13R

Electric metallic tubing is not permitted for underground installations.

Explanation of Solution

Discussion:

Electrical metallic tubing is an unthreaded thin-wall raceway of the circular cross section which is designed for physical protection purposes and routing purposes for the cables and conductors. When utilizing appropriate fittings are installed, this tubing is used as an equipment grounding conductor.

Electrical metallic tubing cannot be used for residential underground installations.

Conclusion:

Thus, the electric metallic tubing is not permitted for underground installations.

f.

Expert Solution
Check Mark
To determine

Find the cover (depth) for the UF cable under lawn, circuit with 120volts, 20amperes and GFCI protection.

Answer to Problem 13R

The cover (depth) for the UF cable under lawn, circuit with 120volts, 20amperes and GFCI protection is 12in.(300mm).

Explanation of Solution

Discussion:

According to the table NEC Table 300.5, the depth for the residential branch circuits rated with 120volts, GFCI protection and maximum overcurrent protection of 20amperes under lawn areas is 12in.(300mm).

Conclusion:

Thus, the cover (depth) for the UF cable under lawn, circuit with 120volts, 20amperes and GFCI protection is 12in.(300mm).

g.

Expert Solution
Check Mark
To determine

Find the cover (depth) for the rigid PVC conduit approved for direct burial with no other protection.

Answer to Problem 13R

The cover (depth) for the rigid PVC conduit approved for direct burial with no other protection is 18in.(450mm).

Explanation of Solution

Discussion:

The rigid PVC is a non-metal. According to the table NEC Table 300.5, the depth for the nonmetallic raceways that are listed for non-burial without the concrete encasement with no other protection is 18in.(450mm).

Conclusion:

Thus, the cover (depth) for the rigid PVC conduit approved for direct burial with no other protection is 18in.(450mm).

h.

Expert Solution
Check Mark
To determine

Find the cover (depth) for the rigid PVC conduit circuit with 120volts, 20amperes and GFCI protection.

Answer to Problem 13R

The cover (depth) for the rigid PVC conduit circuit with 120volts, 20amperes and GFCI protection is 12in.(300mm).

Explanation of Solution

Discussion:

According to the table NEC Table 300.5, the depth for the residential branch circuits rated with 120volts, GFCI protection and maximum overcurrent protection of 20amperes for the rigid PVC conduit is 12in.(300mm).

Conclusion:

Thus, the cover (depth) for the rigid PVC conduit circuit with 120volts, 20amperes and GFCI protection is 12in.(300mm).

i.

Expert Solution
Check Mark
To determine

Find the cover (depth) for the rigid conduit passing over the solid rock.

Answer to Problem 13R

The cover (depth) for the rigid conduit passing over the solid rock is 2in.(50mm).

Explanation of Solution

Discussion:

According to an article NEC 300.5, Note 5 to Table 300.5, the wiring should be installed in metal raceway or the nonmetallic raceway that are permitted for direct burial where the solid rock prevents the compliances with the cover values. The cover of the raceway should be covered by minimum of 2in.(50mm) of the concrete extending down to rock.

Conclusion:

Thus, the cover (depth) for the rigid conduit passing over the solid rock is 2in.(50mm).

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
7.A. Ferrous metal raceways or enclosures are made with _______ content.A. steel or brassB. aluminum or ironC. brass or aluminumD. iron or steel7.B. The size of a grounding electrode conductor for a service or separately derived system is generally basedon the size of the largestA. ungrounded supply conductor.B. equipment grounding conductor.C. grounded electrode.D. bonding jumper.7.C. Which of the following statements about bonding is true?A. The joint or termination must offer opposition in the circuit for effective electrical connections.B. Effective bonding keeps impedance high if a fault should occur.C. The entire electrical safety circuit is only as good as its strongest bonded link.D. Bonding connections must endure high levels of fault current until overcurrent protective devices can operate.
7.B. The size of a grounding electrode conductor for a service or separately derived system is generally basedon the size of the largestA. ungrounded supply conductor.B. equipment grounding conductor.C. grounded electrode.D. bonding jumper.7.C. Which of the following statements about bonding is true?A. The joint or termination must offer opposition in the circuit for effective electrical connections.B. Effective bonding keeps impedance high if a fault should occur.C. The entire electrical safety circuit is only as good as its strongest bonded link.D. Bonding connections must endure high levels of fault current until overcurrent protective devices can operate.
1.A. When a grounding electrode conductor is connected to the grounded conductor within a serviceequipment enclosure, it's required to be connected to the _______ terminal bus.A. service bonding jumperB. equipment groundingC. grounded conductorD. main bonding jumper1.B. The grounding electrode conductor for a DC system will have that conductor sized no smaller than_______ AWG aluminum.A. 8B. 6C. 10D. 121.C. What are the two key aspects of the installation of the grounding electrode conductor?A. Sizing and protectionB. Bonding and accessibilityC. Materials and placementD. Location and safety
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Types of House Wiring - Types of Electrical Wiring - Electrical Wiring; Author: Learning Engineering;https://www.youtube.com/watch?v=A5P-buWX-dA;License: Standard Youtube License