We have 10kVA, 4800/240 V, 50Hz single phase transformer. R1 is measured as R1 = 20 Ω From the short circuit test (secondary short circuited) : Usc = 179V, Psc = 181W, Isc = 2A From the no load test (secondary open circuited) : U20 = 240V, P20 = 60W, I20 = 1,5A When the output power is 10kVA with cosφ2=0,9 inductive, find: Calculate the transformer parameters Iron loss and Copper loss Output power Efficiency
Three-Phase Transformers
Three-segment transformers are a type of transformer used to transform voltages of electrical systems into three ranges. Two type transformers are shell-type transformer and core type transformer. In brief, it could be described because of the exquisite kinds of configurations.
Transformer
Ever since electricity has been created, people have started using it in its entirety. We see many types of Transformers in the neighborhoods. Some are smaller in size and some are very large. They are used according to their requirements. Many of us have seen the electrical transformer but they do not know what work they are engaged in.
We have 10kVA, 4800/240 V, 50Hz single phase transformer. R1 is measured as R1 = 20 Ω
From the short circuit test (secondary short circuited) :
Usc = 179V, Psc = 181W, Isc = 2A
From the no load test (secondary open circuited) :
U20 = 240V, P20 = 60W, I20 = 1,5A
When the output power is 10kVA with cosφ2=0,9 inductive, find:
- Calculate the transformer parameters
- Iron loss and Copper loss
- Output power
- Efficiency