The single-line diagram of a three-phase power system is shown in below Figure. Equipment ratings are given as follows: Synchronous generators: 1000 MVA 1000 MVA 500 MVA 750 MVA GI G2 G3 G4 Transformers: TI T2 T3 T4 1000 MVA 1000 MVA 500 MVA 750 MVA Transmission lines: 1-2 1-3 2-3 b) c) 500 kV 500 kV 500 kV d) 15 kV 15 kV 13.8 kV 13.8 kV Xd=X₂= 0.18, Xo = 0.07 per unit Xd=X₂=0.20, Xo = 0.10 per unit Xd=X₂-0.15, Xo = 0.05 per unit Xa=0.30, X₂=0.40, Xo= 0.10 per unit 15 kV A/500 kV Y 15 kV A/500 kV Y 15 kV Y/500 kVY 15 kV Y/500 kV Y a) The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence reactance diagrams using a 1000-MVA, 500-kV base in the zone of line 1-2. Neglect the A-Y transformer phase shifts. X=0.10 per unit X=0.10 per unit X=0.12 per unit X=0.11 per unit Χι = 50 Ω, Χ@ = 150 Ω Χρ = 40 Ω, Χο = 100 Ω Χι = 40 Ω, Χ@ = 100 Ω Faults at bus 1 are of interest. Determine the Thévenin equivalent of each sequence network as viewed from the fault bus 1. Prefault voltage is 1.0 per unit. Prefault load currents and A-Y transformer phase shifts are neglected. (Hint: Use the Y-A conversion.) Determine the subtransient fault current in per-unit and in kA during a bolted three-phase fault at the fault bus 1. Determine the subtransient fault current in per-unit and in kA, as well as the per-unit line-to-ground voltages at the fault bus for bolted single line-to-ground fault at the fault bus 1.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.32P: Determine the positive- and negative-sequence phase shifts for the three- phase transformers shown...
icon
Related questions
icon
Concept explainers
Question

Just part D

The single-line diagram of a three-phase power system is shown in below Figure.
Equipment ratings are given as follows:
Synchronous generators:
1000 MVA
1000 MVA
500 MVA
750 MVA
GI
G2
G3
G4
Transformers:
TI
T2
T3
T4
1000 MVA
1000 MVA
500 MVA
750 MVA
Transmission lines:
500 kV
500 kV
500 kV
1-2
1-3
2-3
a)
b)
c)
d)
15 kV
15 kV
13.8 kV
13.8 kV
Xd = X2= 0.18, Xo = 0.07 per unit
Xd = X2=0.20, Xo = 0.10 per unit
Xd = X2= 0.15, Xo = 0.05 per unit
Xd 0.30, X₂=0.40, Xo = 0.10 per unit
15 kV A/500 kV Y
15 kV A/500 kV Y
15 kV Y/500 kV Y
15 kV Y/500 kV Y
X = 0.10 per unit
X= 0.10 per unit
X = 0.12 per unit
X=0.11 per unit
Χρ = 50 Ω, Χ@ = 150 Ω
X₁40 S2, Xo= 100 2
X₁40 2, Xo 100 2
The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit
using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence
reactance diagrams using a 1000-MVA, 500-kV base in the zone of line 1-2. Neglect
the A-Y transformer phase shifts.
Faults at bus 1 are of interest. Determine the Thévenin equivalent of each
sequence network as viewed from the fault bus 1. Prefault voltage is 1.0 per unit.
Prefault load currents and A-Y transformer phase shifts are neglected. (Hint: Use the
Y-A conversion.)
Determine the subtransient fault current in per-unit and in kA during a bolted
three-phase fault at the fault bus 1.
Determine the subtransient fault current in per-unit and in kA, as well as the
per-unit line-to-ground voltages at the fault bus for a bolted single line-to-ground
fault at the fault bus 1.
Transcribed Image Text:The single-line diagram of a three-phase power system is shown in below Figure. Equipment ratings are given as follows: Synchronous generators: 1000 MVA 1000 MVA 500 MVA 750 MVA GI G2 G3 G4 Transformers: TI T2 T3 T4 1000 MVA 1000 MVA 500 MVA 750 MVA Transmission lines: 500 kV 500 kV 500 kV 1-2 1-3 2-3 a) b) c) d) 15 kV 15 kV 13.8 kV 13.8 kV Xd = X2= 0.18, Xo = 0.07 per unit Xd = X2=0.20, Xo = 0.10 per unit Xd = X2= 0.15, Xo = 0.05 per unit Xd 0.30, X₂=0.40, Xo = 0.10 per unit 15 kV A/500 kV Y 15 kV A/500 kV Y 15 kV Y/500 kV Y 15 kV Y/500 kV Y X = 0.10 per unit X= 0.10 per unit X = 0.12 per unit X=0.11 per unit Χρ = 50 Ω, Χ@ = 150 Ω X₁40 S2, Xo= 100 2 X₁40 2, Xo 100 2 The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence reactance diagrams using a 1000-MVA, 500-kV base in the zone of line 1-2. Neglect the A-Y transformer phase shifts. Faults at bus 1 are of interest. Determine the Thévenin equivalent of each sequence network as viewed from the fault bus 1. Prefault voltage is 1.0 per unit. Prefault load currents and A-Y transformer phase shifts are neglected. (Hint: Use the Y-A conversion.) Determine the subtransient fault current in per-unit and in kA during a bolted three-phase fault at the fault bus 1. Determine the subtransient fault current in per-unit and in kA, as well as the per-unit line-to-ground voltages at the fault bus for a bolted single line-to-ground fault at the fault bus 1.
Line 1-2
Line 1-3
2
2
T₂
Line 2-3
3
T3
38
TA
38
21 Ý
3
4
youthiy
Transcribed Image Text:Line 1-2 Line 1-3 2 2 T₂ Line 2-3 3 T3 38 TA 38 21 Ý 3 4 youthiy
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 10 steps with 14 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning