Problem To convert the power factor to 0.95 lagging, (given a load requiring 40kW with a power factor of 0.84 lagging, a load voltage of 220 Vrms at 60Hz, and a transmission line impedance of 0.1+j0.25 ohms), calculate the capacitance required.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.27P: An industrial load consisting of a bank of induction motors consumes 50 kW at a power factor of 0.8...
icon
Related questions
Question
Problem To convert the power factor to 0.95 lagging, (given a load requiring 40kW
with a power factor of 0.84 lagging, a load voltage of 220 Vrms at 60Hz, and a
transmission line impedance of 0.1+j0.25 ohms), calculate the capacitance required.
Answer
C=773μF
Transcribed Image Text:Problem To convert the power factor to 0.95 lagging, (given a load requiring 40kW with a power factor of 0.84 lagging, a load voltage of 220 Vrms at 60Hz, and a transmission line impedance of 0.1+j0.25 ohms), calculate the capacitance required. Answer C=773μF
Expert Solution
steps

Step by step

Solved in 6 steps with 11 images

Blurred answer
Knowledge Booster
Sinusoids and Phasors of Alternating Circuit
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning