In the system shown below, the generator is ideal (Xs = 0) and the magnitude of the load bus voltage, VL is to be held at 110 kV. Working on a system base of 100 MVA and a base voltage of 115 kV in the load circuit: a) b) draw the single-phase equivalent pu reactance diagram, and determine the necessary generator terminal voltage VG (kV).
Q: The yearly duration curve of a certain plant may be considered as a straight line from 100 MW to 40…
A: Maximum demand = 100 x 103kwMinimum demand = 40 x 103 kwInstalled capacity = 40 x 103 kw of 2 No⇒30…
Q: . Discuss about the excitation system of Synchronous generator.
A:
Q: Q.6: A (500 MW) synchronous generator is delivering (100 Mw) to infinite bus through the unit…
A:
Q: In power flow studies,if a network consists of a generator bus which elements of Jacobian Matrix…
A: The generator bus is also called PV or voltage controlled bus. The quantities specified for such…
Q: The single line diagram of figure below shows a generator connected through parallel transmission…
A: when a 3 phase fault occurs at any of the middles of one of the transmission line then the…
Q: Q1: For a medium line model, draw the circle diagram only and put the value of OR, OS and 0t If you…
A: Three-Phase Line: Three-phase alternating current is a popular form of alternating current used in…
Q: single-phase, 10-kVA, 200-V, generator has an internal impedance Z, of 2 Q. Using the ratings of the…
A:
Q: Discuss system demand and generator loading
A: System demand System demand management (SDM), also called as management control (DSM) or…
Q: Why it's imporctical carry out actual load test on large rating transformers ?
A: The explanation is as follows.
Q: Draw the phasor diagrams for a transmission line (modeled as short transmission line) when supplying…
A:
Q: 2- Why it's imporctical carry out actual load test on large rating transformers ?
A: For large-rated transformer, the value of the rated current is usually very high.
Q: Q2:- a synchronous generator is 25 MVA, 11kV, it is star- connected with the neutral point solidly…
A: Given:X1=X2=0.2puX0=0.08pu Consider power base is 25 MVA and voltage base is 11 KVVoltage PU =1
Q: . Contribution of load flow studies to erect new power station?
A:
Q: A 250 MVA, 25 kV, 3 phase synchronous generator has a synchronous reactance X, of 1.6 pu. It is…
A: According to company policy, i am solve only first 3 part. We can draw the given power system as a)…
Q: 4. Why we adopt open delta test instead of direct loading test to calculate the efficiency of large…
A: Transformer tests are performed to determine the performance of transformers. they are of two types,…
Q: A three phase synchronous generator with negligible resistance and Xs=20 ohm has induced voltage as…
A: Given: Per phase quantities, Induced voltage E=230 VTerminal voltage V=230 VSynchronous reactance…
Q: 6. Whether the value of synchronous impedance (Zs) is constant? State the conditions on which it…
A: We are authorized to answer one question at a time, since you have not mentioned which question you…
Q: Q3: A synchronous generator with peak generated voltage Vg which is connected to a lighting arrester…
A: Equivalent per phase diagram Apply KVL in loop 1)
Q: Q14. In paralleling of synchronous generators, the machines that are to be paralleled must have the…
A: Conditions for parallel operation of alternators (synchronous generators) : -Bus bar voltage of the…
Q: A three-phase, 250 MVA, 16 kV rated synchronous generator is feeding into an infinite bus bar at 15…
A: Synchronous generator rating 250MVA and 16 kV Synchronous reactance=1.62 up and E=24 kV a)The line…
Q: The torque angle of synchronous machine operating from a constant voltage bus, is usually defined as…
A: the torque angle of synchronous machine is operated from a constant voltage bus, is usually defined…
Q: Calculate the percent voltage regulation for a three-phase wye-connected 2500 kVA 6600-V…
A: In this question we need to find a voltage regulation of the given alternator.
Q: (a) Sketch the equivalent circuit and obtain the general equation for synchronous generator
A: Synchronous generator: It is an electromechanical device. This is called a synchronous generator…
Q: In the system shown below, the generator is ideal (Xs = 0) and the magnitude of the load bus…
A:
Q: A 25-bus power system has 5 generator buses and 20 load buses. For the load flow analysis using…
A: Given, Number of buses, n =25 Number of generator bus = 5 Number of load buses = 20
Q: 7. What is the nature of the generator-load frequency characteristics? 8. What is the effect of a…
A: Load-frequency characteristics: Under equilibrium conditions, but with equivalent primary control…
Q: following figure shows the one-line diagram of a power system. Bus 1 is selected as a reference bus…
A: Solution- Given, V1 = 1 + j(0) Z = 0.02+ j0.04 p.u. S2 = 280 MW + j60 Mvar
Q: Sketch the complete per-phase equivalent circuit of a symmetrical non-salient pole three-phase…
A: Synchronous generator: It is an electromechanical device. This is called a synchronous generator…
Q: ) the internal voltage of the generator and
A: Per unit (pu) system - Per unit (pu) system is used to express system quantity in the form of ratio…
Q: What are the quantities are specified for load bus? O Real Power and Reactive Power O Reactive Power…
A: What are the quantities are specified for load bus? Real and Reactive power Reactive power and…
Q: Illustrate the salient effect of a sudden symmetrical short circuit across the terminals of a…
A: We are authorized to answer one question at a time, since you have not mentioned which question you…
Q: advantages and limitations of Gauss-Seidal and Newton Raphson methods . Of this two, which method is…
A: 1st we discusse the comparison Between G.S and N.R method. Then we study about the advantages and…
Q: 6.1. A power system network is shown in Figure 47. The generators at buses 1 and 2 are represented…
A: The power system network is shown below,
Q: 916: The sending end and receiving end voltages of overhead line at 120 MWw load are equal at 110…
A:
Q: Q5 (b) A synchronous generator and a motor are both rated at 30MVA, 2kV and both have transient…
A: As per the guidelines of Bartley we supposed to answer first three subpart only for solution of…
Q: A 33 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 0.5%. The generator supplies a…
A:
Q: . Which one of the following method uses weak coupling between reactive power and voltage angle?. A.…
A:
Q: Derive emf equation of the synchronous generator.
A:
Q: How do we handle a PV bus in the Gauss Seidel Method? What will happen to the bus voltage if the…
A: PV bus is also known as Generator Bus . In guass siedel method , all the buses except slack bus are…
Q: Plot generator output voltage versus load current for operating conditions with and without…
A: Voltage regulator is a circuit designed to maintain constant voltage at the output. The following…
Q: 5/The phase angle between magnetizing component current and core loss component current is 180o…
A: The phase angle between magnetizing component current and core loss component current is 900.
Q: 6- Why it is possible to short circuit the differ tia generator and not the cumulative compound…
A: Compound generator consists of both series and shunt filed windings. If the flux produced by both…
Q: 5. Explain the effect of load power factor on the transmission efficiency?
A: Power factor expresses the ratio of true power used in a circuit to the apparent power delivered to…
Q: A MVA, 20 KV, three-phašė ģenēřātor has a subtransient reactance of 20%. The generator supplies a…
A: Solution- For generator, S = 300 MVA V = 20KV X = 20% For motor 1, S = 200 MVA V = 13.2 KV X= 20%…
Q: For the network shown, obtain the complex bus-bar voltage at bus 2 at the end of the fourth…
A:
Q: A 100-MVA, 20-kV synchronous generator is connected through a transmission line to a 100- MVA, 20-kV…
A:
Q: Explain load flow analysis of Radial distribution system by optimization technique with neat diagram
A: The load flow analysis of Radial distribution system by optimization techniques as follows: -…
Trending now
This is a popular solution!
Step by step
Solved in 3 steps with 3 images
- Three single-phase two-winding transformers, each rated 3kVA,220/110volts,60Hz, with a 0.10 per-unit leakage reactance, are connected as a three-phase extended autotransformer bank, as shown in Figure 3.36(c). The low-voltage winding has a 110 volt rating. (a) Draw the positive-sequence phasor diagram and show that the high-voltage winding has a 479.5 volt rating. (b) A three-phase load connected to the low-voltage terminals absorbs 6 kW at 110 volts and at 0.8 power factor lagging. Draw the per-unit impedance diagram and calculate the voltage and current at the high-voltage terminals. Assume positive-sequence operation.Three single-phase two-winding transformers, each rated 25MVA,54.2/5.42kV, are connected to form a three-phase Y- bank with a balanced Y-connected resistive load of 0.6 per phase on the low-voltage side. By choosing a base of 75 MVA (three phase) and 94 kV (line-to-line) for the high-voltage side of the transformer bank, specify the base quantities for the low-voltage side. Determine the per-unit resistance of the load on the base for the low-voltage side. Then determine the load resistance RL in ohms referred to the high-voltage side and the per-unit value of this load resistance on the chosen base.With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a generator, a step-up transformer bank, a transmission line, a stepown transformer bank, and an impedan load. The generator terminal voltage is 15 kV (line-to-line). (a) Draw the per-phase equivalent circuit, aounting for phase shifts for positive-sequence operation. (b) By choosing the line-to-neutral generator terminal voltage as the reference, determine the magnitudes of the generator current, transmiss ion-line current, load current, and line-to-line load voltage. Also, find the three-phase complex power delivered to the load.
- Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance Xeq=0.10perunit, are connected to form a three-phase bank. The high-voltage windings are connected in Y with a solidly grounded neutral. Draw the per-unit equivalent circuit if the low-voltage windings are connected (a) in with American standard phase shift or (b) in Y with an open neutral. Use the transformer ratings as base quantities. Winding resistances and exciting current are neglected.Consider a bank of this single-phase two-winding transformers whose high-voltage terminals are connected to a three-phase, 13.8-kV feeder. The low-voltage terminals are connected to a three-phase substation load rated 2.0 MVA and 2.5 kV. Determine the required voltage, current, and MVA ratings of both windings of each transformer, when the high-voltage/low- voltage windings are connected (a) Y-, (b) -Y, (c) Y-Y, and (d) -.The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same nominal voltage ratio and the same reactan of 0.1 per unit on the same base, is shown in Figure 3.43. Transformer Tb has a voltage-magnitude step-up toward the load of 1.05 times that of Ta (that is, the tap on the secondary winding of Tb is set to 1.05). The load is represented by 0.8+j0.6 per unit at a voltage V2=1.0/0 per unit. Determine the complex power in per unit transmitted to the load through each transformer, comment on how the transformers share the real and reactive powers.
- In developing per-unit circuits of systems such as the one shown in Figure 3.10. when moving across a transformer, the voltage base is changed in proportion to the transformer voltage ratings. (a) True (b) FalseThe ratings of a three-phase, three-winding transformer are Primary: Y connected, 66kV,15MVA Secondary: Y connected, 13.2kV,10MVA Tertiary: connected, 2.3kV,5MVA Neglecting resistances and exciting current, the leakage reactances are: XPS=0.09 per unit on a 15-MVA,66-kV base XPT=0.08 per unit on a 15-MVA,66-kV base XST=0.05 per unit on a 10-MVA,13.2-kV base Determine the per-unit reactances of the per-phase equivalent circuit using a base of 15 MVA and 66 kV for the primary.Consider three ideal single-phase transformers (with a voltage gain of ) put together as three-phase bank as shown in Figure 3.35. Assuming positive-sequence voltages for Va,Vb, and Vc find Va,Vb, and VC. in terms of Va,Vb, and Vc, respectively. (a) Would such relationships hold for the line voltages as well? (b) Looking into the current relationships, express IaIb and Ic in terms of IaIb and Ic respectively. (C) Let S and S be the per-phase complex power output and input. respectively. Find S in terms of S.
- The leakage reactance of a three-phase, 300-MVA,230Y/23-kV transformer is 0.06 per unit based on its own ratings. The Y winding has a solidly grounded neutral. Draw the per-unit equivalent circuit. Neglect the exciting admittance and assume the American Standard phase shift.The direct electrical connection of the windings allows transient over voltages to pass through the auto transfonner more easily, and that is an important disadvantage of the autotransformer. (a) True (b) FalseEquipment ratings for the five-bus power system shown in Figure 7.15 are as follows: Generator G1:    50 MVA, 12kV, X=0.2 per unit Generator G2: 100 MVA, 15 kV, X=0.2 per unit Transformer T1: 50 MVA, 10 kV Y/138kVY,X=0.10 per unit Transformer T2: 100 MVA, 15 kV /138kVY,X=0.10 per unit Each 138-kV line: X1=40 A three-phase short circuit occurs at bus 5, where the prefault voltage is 15 kV. Prefault load current is neglected. (a) Draw the positive-sequence reactance diagram in unit on a 100-MVA, 15-kV base in the zone of generator G2. Determine (b) the Thévenin equivalent at the fault, (c) the subtransient fault current in per unit and in kA rms, and (d) contributions to the fault from generator G2 and from transformer T2.