3. An overhead 3-phase transmission line delivers 5000 kW at 22 kV at 0•8 p.f. lagging. The resistance and reactance of each conductor is 42 and 6 2 respectively. Determine: (i) sending end voltage (ii) percentage regulation (iii) transmission efficiency.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.29P: Consider three ideal single-phase transformers (with a voltage gain of ) put together as ...
icon
Related questions
Question
100%
3. An overhead 3-phase transmission line delivers 5000 kW at 22 kV at 0•8 p.f. lagging. The resistance and
reactance of each conductor is 4 N and 6 N respectively. Determine:
(i) sending end voltage (ii) percentage regulation (iii) transmission efficiency.
Transcribed Image Text:3. An overhead 3-phase transmission line delivers 5000 kW at 22 kV at 0•8 p.f. lagging. The resistance and reactance of each conductor is 4 N and 6 N respectively. Determine: (i) sending end voltage (ii) percentage regulation (iii) transmission efficiency.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Analysis of Single Phase and Three Phase System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning