.A balanced 40 Ohms Y-connected load is connected to a 480V (line voltage), three phase source. Find the rms value of the line current
Q: Determine the amplitude of the line current in a three-phase system with a line voltage of 207 V…
A:
Q: In the figure, each transmission line of the three-phase system has an impedance of 0.2 / 90° Q. In…
A: In this question, We need to determine the currents in the loads and neutral current? Power…
Q: 11.29 In a balanced three-phase wye-wye system, the total power loss in the lines is 400 W. VAN =…
A: Steps: First, write the per phase mode and calculate the current magnitude using the given power…
Q: A balanced star-connected source has phase voltage Vab = 416 230° V and a positive phase sequence.…
A:
Q: A 110-V rins, 60-Hz source is applied to a load impedance Z. The apparent power entering the load is…
A: In this question, We need to determine the complex power S If load is 120VA at the 0.707PF lagging.…
Q: A 60 Hz, 230 mile, three-phase overhead transmission line has a series impedance of o.8431…
A: As per Bartleby guidelines we are allowed to solve only one question, please ask the rest again.
Q: Q2/ A balanced three-phase source serves two loads, as follows: Load 1: 27 kW at 0.9 leading power…
A: In this question, Two loads are connected to the parallel. Load voltage V= 480V, Line impedance…
Q: A star connected 3-phase alternator gives the following test result Open circuit Test: open circuit…
A: Let us calculate the per phase synchronous impedance if the given three phase alternator as shown…
Q: For the circuit in the figure, Determine the complex power delivered to the three-phase load. The…
A:
Q: A star connected 3-phase alternator gives the following test result Open circuit Test: open circuit…
A: Third option is correct. The detailed solution is provided below.
Q: A balanced three-phase source furnishes power to the following three loads: Load 1: 6 kVA at 0.83…
A:
Q: H.W. An abc-phase-sequence three-phase voltage source connected in a balanced wye has a line voltage…
A: Given an abc phase sequence three phase voltage source connected in balanced wye connection has,…
Q: A load connected in star, with impedances of 24 ≮ 20°, has a voltage Vac = 208 ≮ 10°, Calculate: a-…
A: In this question, We need to determine the phase current, phase voltage and line voltage? Assume…
Q: Q) A balanced star-connected load is supplied from a symmetrical three-phase, 400 V (line-to-line)…
A: A balanced star connected load Voltage = VLL = 400V line to line Current in each phase = 50A…
Q: For a single phase ac voltage controller/chopper, which is d series R (=8[Ohm]) and L(=30 [mH])…
A:
Q: 11.46 An abc-phase-sequence three-phase balanced wye- connected source supplies power to a balanced…
A:
Q: A balanced three-phase generator delivers 7.2 kW to a wye-connected load with impedance 30- j40 N…
A:
Q: A 13.8-kV, single-phase generator supplies power to a load through a transmisson line. The load’s…
A: A Power System unit consist of generation unit, transmission unit and distribution unit. In…
Q: a transmission line has an impedance of 4 12 Ohms/phase, Find the per-unit impedance of this line on…
A:
Q: A balanced star connected load of (8+j 6)Ω per phase in connected to a balanced 3-phase 400 V supply…
A:
Q: Given ??? = 208 ∠ − 40° V in a three-phase ACB circuit, find the currents of the phasor line for a…
A: Given, a three-phase ACB circuit having Line voltage, VL = 208 ∠ − 40° V Active power, P = 10 kW…
Q: A load of 135 MW at a power factor of 0.65 lagging can be delivered by a 3-phase transmission line.…
A: Below are the answers calculated for the above given data
Q: Determine the amplitude of the line current in a three-phase system with a line voltage of 300 V…
A: In a three-phase system there are two ways to connect a three phase load. Star/Wye Connection Delta…
Q: A three-phase power source delivers a power of 30KVA at a lagging power factor of 0.6 to a…
A: Given:Power, P=30kVAPower factor=0.6Phase voltage, Vph=100V
Q: A balanced three phase A- connected load has a line voltage of 2500 Vrms , and absorbs an average…
A: The complex power in an AC system is defined as the product of rms value of applied voltage and…
Q: A 12,470-V, three-phase, three wire source supplies a balanced wye load having an impedance of 50…
A:
Q: The circuit shown below is excited by a balanced three-phase source with a line voltage Vab = 207.84…
A: Here, As shwon in the figure the source is a balanced three phase shource and the load is the delta…
Q: Quiz#3 A positive-sequence balanced three-phase wye-connected source supplies power to a balanced…
A: In the circuit, Positive sequence balance circuit, per phase impedance Z= 36+12j Line to line…
Q: Convert the wye-connected load to its delta equivalent. What is the per phase impedance of the delta…
A: Given
Q: Consider a three-phase Y-connected source feeding a balanced-Δ load. The phasor sum of the line…
A: Please find your answer below in step 2.
Q: 11.15 An abc-phase-sequence three-phase balanced wye-connected 60-Hz source supplies a balanced…
A: In this question we need to find a line current of the given system
Q: The total apparent power supplied in a balanced, three-phase Y-Δ system is 4800 VA. The line voltage…
A: the per phase apparent power, SP=ST3 =48003 =1600 VA Since connection is Y - delta…
Q: 3. A balanced star-connected source has phase voltage Vab 416 230° V and a positive phase sequence.…
A: Given Vab=416∠30° VD=50∠30° ΩE=7+j9 Ω Convert both the source and load to their WYE-equivalents.…
Q: For a three phase balanced Y-connected load having a magnitude of line voltage |VAB|=650V and total…
A: Given Values are:- Vab=650VPavg=22KWCosϕ=0.65 we are going to use formula's given below;…
Q: A balanced three-phase A-connected load with a phase impedance of 10-j16 Q. If the line voltage is…
A: The complex/ Apparent power in a system is defined as the product of rms value of applied voltage…
Q: A 12,470V, three-phase, three wire source supplies a balanced wye load having an impedance of 50…
A:
Q: A balanced delta-connected load has phase impedances of 4+j3 Ohms. It is connected to balanced…
A:
Q: A balanced delta load with impedances of 13 +j18 Q is connected to a 440-V, ACB source. Find the…
A:
Q: 3. In the circuit given below the load impedance Z, is adjusted for maximum average power transfer…
A: Given, the load impedance 'ZL' is adjusted to obtain maximum power transfer to load from the source.…
Q: In a balanced Y-Delta connection the magnitude of the line voltages VL = 1500 V (rms), the load…
A:
Q: Find the line current, power factor, a
A:
Q: A 3-phase Y-connected load draws power from a 3-phase Y-connected source. The source voltage,…
A: Since we only answer up to 3 sub-parts, we’ll answer the first 3. Please resubmit the question and…
Q: A balanced wye-connected load with a phase impedance of 5- j8 Q is connected to a balanced…
A: In this question we will find line currents in star connect system....
Q: 13 10+is 25 For the circuit shown below, Take Van = 100 Vrms and the transmission line impedance is…
A: In this question, choose the correct option What is the real power in the phase B.
Q: Solve only part c
A: As in question asked only for 3rd part so, first draw the per phase circuit, here, assume load…
Q: A balanced star-connected source has phase voltage Vab = 416 ∠30o V and a positive phase sequence.…
A: Given Source phase voltage is Vab=416∠300 The line impedance per phase is EΩ Load impedance per…
Q: E11.8 A 480-V rms line feeds two balanced three-phase loads. If the two loads are rated as follows,…
A: Let's considered load is connected in star.
Q: For the network shown below find: a) Zr. I. V, the power factor and the total average power…
A: Power factor: It tells how much active power is utilized by the circuit from apparent power.
clear and correct or dislike
![. A balanced 40 Ohms Y-connected load is connected to a 480V (line voltage),
three phase source. Find the rms value of the line current,](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2Fde7c2f12-82ee-4561-95d9-b8fe5e6d3493%2F1ce4541e-cf93-4585-a47e-ae145cc2d8c2%2Fr3ajumd_processed.jpeg&w=3840&q=75)
![](/static/compass_v2/shared-icons/check-mark.png)
Trending now
This is a popular solution!
Step by step
Solved in 2 steps
![Blurred answer](/static/compass_v2/solution-images/blurred-answer.jpg)
- The instantaneous power absorbed by the load in a single-phase ac circuit, for a general R LC load under sinusoidal-steady-state excitation. is (a) Nonzero constant (b) Zero (c) Containing double-frequency componentslši vl pir:10 Expert Q&A + 1. For the circuit in Figure: a. Determine I, VR, and Ve in phasor form. b. Calculate the total power factor, and indicate whether it is leading or lagging. c. Calculate the average power delivered to the circuit. d. Draw the impedance diagram. e. Find the voltages VR and Vcusing the voltage divider rule and compare them with the results of part(a) above. + Uc - + Ug - 30 2 L = 0.2 H L =0.2 H C = 4 µF e = V2(20) sin(377t + 40°) Expert Answer Home Search More IIConsider the circuit shown. Find the following: a. Total load impedance seen by the voltage source. b. Complex power delivered by the source. c. Average power delivered by the source. d. Reactive power delivered by the source. e. Load power factor and power factor angle.
- In the 3-phase circuit in the figure, f = 2000 Hz. Find line and phase voltages and currents for the load.(in amplitude and phase).Three Impedances each of (8 - j24)2 are connected in mesh across a three-phase 420V ac supply. Determine the phase current, line current, active power, reactive power drawn from supply. Also draw the Phasor diagram for the mesh connection and marks the Line current ,phase current line voltage and phase angle between phase current and pahse voltage. phase current (Ip) Line current real power reactive powerThere is an installation with two equal triphasic loads of 300 kVA each and a power factor of 0.9 lagging. When connecting a pure reactive element in parallel, the reactive power at the entrance of the installation is 150 kVARS, with a lagging power factor. We can say that: a) A bank of reactors was connected and the fp deteriorated. b) A capacitor bank was connected and the pf deteriorated. c) A bank of reactors was connected and the fp improved. d) A capacitor bank was connected and the pf improved. e) None of the above
- For the given circuit below a. Calculate E, IR, and IL, in phasor form.b. Calculate the total power factor (leading or lagging) and the average power delivered to the circuit.c. Draw the admittance diagram and draw the phasor diagram of the currents Is, IR, and IL, and the voltage E.The total power drawn by the two-impedance load in parallel is 26kW at 0.98 power factor lagging, it is being supplied by a 230-volts AC source. One of the loads (Load 1) takes 16kVA at 0.77 power factor lagging. What is the reactive power of the unknown impedance (Load 2)?Consider a 10 kVA, 200/400 V, 50 HZ: single-phase tranformer has the folloving test results:0.C. test: 200 V, 0.6A, 63 W (L.V.side)S.C. test : 20 V, 25A, 85 W (H.V. side)Deternine:i- The eficiengy at 75 % offiull-load at 0.9 leading power factor.ii -The secondary terminal voltage on fill-load at tunity power facton
- 1. a) Find the rms magnitude and the phase angle of ICA in the circuit shown. 2. b) What percent of the average power delivered by the three-phase source is dissipated in the three-phase load?Find the RMS line voltage VL at the source of the circuit. As shown the RMS load phase voltage is 100V and the line impedance is given in the figure.8. The total power supplied to a balance delta load is found in the same way as for a balance wye load. True False Either Neither 12. A load of 20 + j35 ohms is connected across a 220 V, 60 Hz supply. Find the reactive power of the load in var. 595 2420 1042 1382 13. A type of DC source where the characteristic output voltage has perfect unidirectional waveform and is based on electrochemical principle. Generator Inverter Converter Battery 14. Calculate the Rf of a circuit whose impedance is 20+j35 and current of 2A. 0.86 0.91 0.50 0.71 15. What capacitor shall be installed in parallel with a circuit to achieve a unity power factor if the reactive power of a circuit is 200VARS and the voltage is 100V. 80.45 microfarad 53.05 microfarad It's already in unity 62.45 microfarad