POWER SYS. ANALYSIS+DESIGN
6th Edition
ISBN: 9780357700907
Author: Glover
Publisher: INTER CENG
expand_more
expand_more
format_list_bulleted
Concept explainers
Question
error_outline
This textbook solution is under construction.
Students have asked these similar questions
Two generating units rated for 500 MW and 400 MW have governor speed
regulation of 6.0 and 6.4 percent, respectively, from no-load to full-load,
respectively. The generators are operating in paral lel and share a load of 600 MW.
Use a common base of 1000 MVA and assuming free governor action, justify:
i) the new governor speed regulation.
ii) the load shared by each unit.
1.
FIGURE 52 shows the one-line diagram of a simple three-bus power system with
generation at bus I. The voltage at bus l is V1 = 1.0L0° per unit. The scheduled
loads on buses 2 and 3 are marked on the diagram. Line impedances are marked in
per unit on a 100 MVA base. For the purpose of hand calculations, line resistances
and line charging susceptances are neglected
a) Using Gauss-Seidel method and initial estimates of Va
0)-1.0+)0 and V o)-
(
1.0 +j0, determine V2 and V3. Perform two iterations
(b) If after several iterations the bus voltages converge to
V20.90-j0.10 pu
0.95-70.05 pu
determine the line flows and line losses and the slack bus real and reactive power.
2
400 MW
320 Mvar
Slack
0.0125
0.05
300 MW
270 Mvar
FIGURE 52
Solve numerical :
Following figure shows the one-line diagram of a two bus system. Take bus 1 as slack bus, bus 2 as load (PQ) bus. Neglect the shunt charging admittance. Obtain the bus admittance matrixYBUS and find V2 and δ2, power flows and line losses by using Fast decoupled power flow method.
All the values are given in per unit on 100MVA base. Use a tolerance of 0.001 for power mismatch.
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- The fuel-cost curves for two generators are given as follows: C1(P1)=600+18P1+0.04(P1)2C2(P2)=700+20P2+0.03(P2)2 Assuming the system is lossless, calculate the optimal dispatch values of P1 and P2 for a total load of 1000 MW, the incremental operating cost, and the total operating cost.arrow_forwardProblem 4: Consider an interconnected 50-Hz power system that contains four turbine-generator units rated 750 MW, 500 MW, 220 MW and 110 MW. The regulating constant of each unit is 0.05 per unit based on its own rating. Each unit is operating on 75% of its own rating when the load is suddenly dropped by 250 MW. We shall choose a common base of 500 MW. Calculate the rise in frequency and drop in the mechanical power output of each unit without Load Frequency Control.arrow_forwardDiscuss the role of FACTS (Flexible Alternating Current Transmission Systems) devices in power system control and optimization.arrow_forward
- Q6/ The per-unit reactance for a given system are shown in figure below. (1 MVA) is being delivered to the receiving end bus of the system at unity power factor and unit voltage. A three phase short circuit occurs at F. Find the critical clearing angle and the critical clearing time? Take H = 3 p. u. second tc X=j0.3 j0.1 w Peralat j0.25 j0.25 V20 x 1arrow_forwardFor the system in Figure 4 with given generation and load dispatch determine the voltages after two itterations of Gauss-Seidel method. Assume the initial voltage to be 1.01 at angle of 0◦ pu at bus 1, 1.015 at angle of 0◦ pu at bus 2, and 1.0 at angle of 0◦ pu at bus 3. All line impedances are in per unit on a common base, and charging is neglected. Take base power of 100 MVA.arrow_forwardthe amount of real and reactive power that flow between any two buses is determine by the relative difference in voltage magnitude and angle. derive an equation that clearly show this dependency and give a brief analysis of the nature of the relationship.arrow_forward
- A synchronous generator is connected to an infinite bus by a transmission line as shown in the figure. The field current IF = 900A when the unloaded generator is synchronized to the infinite bus. a.) P_M is increased to 0.5pu while I_F is held constant at 900A. Find the complex power S_Inf supplied to the infinite bus in per unit. b.) Determine S_Inf in per unit if IF increases to 1600A and PM is held fixed at 0.5pu.arrow_forward6.5 Consider the three-bus power system shown in Figure P6.5 The table below shows the data about the generators connected to this system. Calculate the unconstrained economic dispatch and the nodal prices for the loading conditions shown in Figure P6.5. 6.5 PROBLEMS 203 B 400 MW 80 MW 40 MW C D Figure P6.5 Three-bus power system for Problems 6.5 to 6.9 and 6.12 to 6.17 Сараcity (MW) Marginal cost ($/MWh) Generator A 150 12 В 200 15 C 150 10 D 400 8 2.arrow_forwardWhat is The amount of compensation to keep VR constant in power transmission line performance study?arrow_forward
- Q2. Figure Q2 shows the single-line diagram. The scheduled loads at buses 2 and 3 are as marked on the diagram. Line impedances are marked in per unit on 100 MVA base and the line charging susceptances are neglected. a) Using Gauss-Seidel Method, determine the phasor values of the voltage at load bus 2 and 3 according to second iteration results. b) Find slack bus real and reactive power according to second iteration results. c) Determine line flows and line losses according to second iteration results. d) Construct a power flow according to second iteration results. Slack Bus = 1.04.20° 0.025+j0.045 0.015+j0.035 0.012+j0,03 3 |2 134.8 MW 251.9 MW 42.5 MVAR 108.6 MVARarrow_forwardDescription The single line diagram of figure below shows a generator connected through parallel transmission line to a large metropolitan system considered as an infinite bus. The machine is delivering 1.0 per-unit power and both the terminal voltage and the infinite-bus voltage are 1.0 per unit. Numbers of the diagram indicate the values of the reactances on a common system base. The transient reactance of the generator is 0.2x per unit as indicated. Determine the power-angle equation for the given system operating conditions. When a three-phase fault occurs at point P, and the fault on the system is cleared by simultaneous opening of the circuit breakers at each end of the affected line, determine the power angle equation and the swing equation for the during fault and post-fault period. Take H= 5.5Q Mj/MVA. (Roll=PQXY) j0.5, j0.1y O X = 0.2X P j0. 5,arrow_forwardHow do we handle a PV bus in the Gauss Seidel Method? What will happen to the bus voltage if the reactive power at a PV bus exceeds the upper bound? And why?arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning