POWER SYS. ANALYSIS+DESIGN
6th Edition
ISBN: 9780357700907
Author: Glover
Publisher: INTER CENG
expand_more
expand_more
format_list_bulleted
Concept explainers
Question
error_outline
This textbook solution is under construction.
Students have asked these similar questions
18 The incremental cost characteristics of two
generators delivering 200 MW are as follows:
dF
dP2
dF
= 2.0+0.01 P,
dP,
= 1.6+0.02P2
%3D
For economic operation the generation P, and P2
should be
(a) 100 MW and 100 MW
(b) 80 MW and 120 MW
(c) 200 MW and 100 MW
(d) 120 MW and 80 MW
When the load on a series generator is
increased, then the flux produced will
increase in direct proportion.
Select one:
True
False
Copper losses in a generator vary with load
Select one:
O True
O False
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- 32. The incremental cost characteristics of two generators delivering a load of 200 MW are as follows: dF = 2.0 + 0.01 P, dP, dP dF, -= 1.6 + 0.02 P, For economic operation the generators P, and P, should be (a) 120 MW and 80 MW (b) 81 MW and 120 MW (c) 120 MW and 120 MW (d) 80 MW and 80 MWarrow_forwardThe incremental cost characteristics of two generators delivering 200 MW are as follows: dF₁ = 2.0+ 0.01 P₁ and 2 = 1.6 +0.02 P₂ dP₁ dP₂ For economic operation, the generation P₁ and P₂ should bearrow_forwardThe maximum efficiency of 10Kw D.C generator is 98% and occurs at 80% of full load. Find the total copper losses at rated loadarrow_forward
- In transformers, the flux lost in the air is called nd as SKW. If tharrow_forwardWhen the load on a series generator is increased, then the fluxproducedwill increaseindirect proportion. Select one: True Falsearrow_forwardX₂=0.1 1 XL +03 Soto X₁ = 0.2 X = 0.1 X = 0.1 Above is the one-line diagram of a simple power system. Each generator is represented by an emf behind the subtransient reactance. All impedances are expressed in per unit on a common base. All resistances and shunt capacitance are neglected. The generators are operating on no load at their rated voltage with their emfs in phase. A symmetrical fault occurs at bus 1 through a fault impedance Z, =j0.08 per unit. a) Using Thevenin's Theorem, determine the impedance to the point of fault and the fault current in per unit. b) Find the bus voltages and line currents during the fault. 2 O otoarrow_forward
- Is it right P that given is it input or output power, more over delta/Y 377V/281V ,2.99A/3.15A what does it mean for these . Also free shaft conditions mean?arrow_forwardWhen a generator fails, its power output is lost, and the result is an imbalance between total load plus losses and total generation. Thus the frequency will: Select one: a. Remain the same b. None of these O c. Increase O d. Droparrow_forwardDetermine the power angle characteristic for the system shown in figure. The generator is operating at a terminal voltage of 1.05p.u. and the infinite bus is at 1.p.u. voltage. The generator is supplying 0.7p.u power to the infinite bus. Draw the power angle curve in graph sheet. 0.1 0.3 Generator 0.2 Infinite bus 0.3 모모arrow_forward
- • T or F, modify the wrong part if False, please underline twice your answer if True or False. During working operation of a wave-wound DC generator, since the generated EMF is directly proportional to the number of poles, you can increase the number of poles to increase the amount of generated EMF.arrow_forwardIn the system shown in Figure 1, the transformers are connected star-star with both star points grounded and the generator is connected in star with its star points grounded. The per unit impedances of each element on a 40 MVA base are given in Table 1 and the voltage levels are given in Table 2. 2 3 4 T1 L T2 8 101 · 101. İ Generator Z 0.01 +j [p.u.] 0.08 V₂ = V3 = V₁ = Figure 1: A section of the distribution system Transformer T1 Line Z 0.04 + j 0.03 + j 0.15000000000000002 0.06000000000000000 2 Table 1: Sequence impedances (p.u. on 40 MVA base) V BASE [KV] Voltages What are the voltages on bus (in p.u.)? V₁ = p.u. ਦਾ p.u. p.u. p.u. 0 Generator p.u. 0 3 Line Load Current A load current of 11.316 kA is flowing with a lagging power factor of 90 %. Convert this to a current vector in per-unit. IL = 10 Table 2: Voltage bases (kV) Transformer T2 0.04 + j 0.06000000000000000 Load 1 ILarrow_forwardWhen the load on a series generator is decreased, then the flux produced will be decreased in direct proportion. Select one: O True O Falsearrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage LearningElectricity for Refrigeration, Heating, and Air C...Mechanical EngineeringISBN:9781337399128Author:Russell E. SmithPublisher:Cengage Learning
![Text book image](https://www.bartleby.com/isbn_cover_images/9781305632134/9781305632134_smallCoverImage.gif)
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
![Text book image](https://www.bartleby.com/isbn_cover_images/9781337399128/9781337399128_smallCoverImage.gif)
Electricity for Refrigeration, Heating, and Air C...
Mechanical Engineering
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Cengage Learning