POWER SYS. ANALYSIS+DESIGN
POWER SYS. ANALYSIS+DESIGN
6th Edition
ISBN: 9780357700907
Author: Glover
Publisher: INTER CENG
bartleby

Concept explainers

Students have asked these similar questions
The dangers and failure in it and How can we be protect from these dangers and defects of Three-phase distribution transformers?
Q2) In the network in the figure below Y-Y connected transformers, each with grounded neutrals, are at the ends of each transmission line that is not terminating at bus 3. The transformers connecting the lines to bus 3 are Y-A, with the neutral of the Y solidly grounded and the A sides connected to bus 3. All the line reactances shown in the figure between busses include the reactances of the transformers. Zero sequence values for these lines including transformers are 2.0 times those shown in the figure. Both generators are Y-Connected. Zero-sequence reactances of the generators connected to bus 1 and bus 3 are 0.04 and 0.08 per unit, respectively. The neutral of the generator at bus 1 is connected to ground through a reactor of 0.02 per unit; the generator at bus 3 has a solidly ground neutral. Find the bus impedance matrices (¹), (²), z for the given network and 'bus' 'bus' bus then compute the Subtransient current in per unit for a single line-to-ground fault on bus 2 and the fault…
what is the definition of zero sequence impedance in a transformers? And what is the benefit of this check in transformers?
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning