POWER SYS. ANALYSIS+DESIGN
6th Edition
ISBN: 9780357700907
Author: Glover
Publisher: INTER CENG
expand_more
expand_more
format_list_bulleted
Concept explainers
Question
error_outline
This textbook solution is under construction.
Students have asked these similar questions
The dangers and failure in it and How can we be protect from these dangers and defects of Three-phase distribution transformers?
Q2) In the network in the figure below Y-Y connected transformers, each with
grounded neutrals, are at the ends of each transmission line that is not
terminating at bus 3. The transformers connecting the lines to bus 3 are Y-A, with
the neutral of the Y solidly grounded and the A sides connected to bus 3. All the
line reactances shown in the figure between busses include the reactances of the
transformers. Zero sequence values for these lines including transformers are 2.0
times those shown in the figure.
Both generators are Y-Connected. Zero-sequence reactances of the
generators connected to bus 1 and bus 3 are 0.04 and 0.08 per unit, respectively.
The neutral of the generator at bus 1 is connected to ground through a reactor
of 0.02 per unit; the generator at bus 3 has a solidly ground neutral.
Find the bus impedance matrices (¹), (²), z for the given network and
'bus' 'bus' bus
then compute the Subtransient current in per unit for a single line-to-ground fault
on bus 2 and the fault…
what is the definition of zero sequence impedance in a transformers? And what is the benefit of this check in transformers?
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- Discuss the role of FACTS (Flexible Alternating Current Transmission Systems) devices in power system control and optimization.arrow_forwardFor large power transformers rated more than 500 kVA, the winding resistances, which are small compared with the leakage reactances, can often be neglected. (a) True (b) Falsearrow_forward400Ω A k=0.9 600Ω B k=0.8 66Ω 600Ωarrow_forward
- Q2. Figure Q2 shows the single-line diagram. The scheduled loads at buses 2 and 3 are as marked on the diagram. Line impedances are marked in per unit on 100 MVA base and the line charging susceptances are neglected. a) Using Gauss-Seidel Method, determine the phasor values of the voltage at load bus 2 and 3 according to second iteration results. b) Find slack bus real and reactive power according to second iteration results. c) Determine line flows and line losses according to second iteration results. d) Construct a power flow according to second iteration results. Slack Bus = 1.04.20° 0.025+j0.045 0.015+j0.035 0.012+j0,03 3 |2 134.8 MW 251.9 MW 42.5 MVAR 108.6 MVARarrow_forwardb) A fault occurs at bus 3 of the network shown in Figure Q4. Pre-fault nodal voltages throughout the network are of 1 p.u. and the impedance of the electric arc is neglected. Sequence impedance parameters of the generator, transmission lines, transformer and load are given in Figure Q4. V₁ = 120° p.u. V₂ = 120° p.u. V₂ = 1/0° p.u. V₂= 120° p.u. jXj0.1 p.u. JX2) 0.1 p.u. jX0j0.15 p.u. jXn-j0.2 p.u. 1 JX(2)-j0.2 p.u. 2 jX)=j0.25 p.u. JX20-10.15 p.u. jXa(z)-j0.2 p.u. 4 jX2(0)=j0.2 p.u. jXT(1) j0.1 p.u. jXT(2)=j0.15 p.u. jXT(0)=j0.1 p.u. Figure Q4. Circuit for problem 4b). = jXj0.1 p.u. j0.1 p.u. - JX(2) JXL(0) 10.1 p.u. = (i) Assuming a balanced excitation, draw the positive, negative and zero sequence Thévenin equivalent circuits as seen from bus 3. (ii) Determine the positive sequence fault current for the case when a three- phase-to-ground fault occurs at bus 3 of the network. (iii) Determine the short-circuit fault current for the case when a one-phase- to-ground fault occurs at bus…arrow_forwardThe sample large power system network data's are given below, The total number of buses is 5 Three-phase short circuit fault subjected at the bus 5 The initial voltage of the faulted bus is 1.0 p.u The Zbus matrix element Z55 is 0.704 p.u Fault impedance Zf= 0.33 p.u Fault current (If )in p.u ..........arrow_forward
- 1. FIGURE 52 shows the one-line diagram of a simple three-bus power system with generation at bus I. The voltage at bus l is V1 = 1.0L0° per unit. The scheduled loads on buses 2 and 3 are marked on the diagram. Line impedances are marked in per unit on a 100 MVA base. For the purpose of hand calculations, line resistances and line charging susceptances are neglected a) Using Gauss-Seidel method and initial estimates of Va 0)-1.0+)0 and V o)- ( 1.0 +j0, determine V2 and V3. Perform two iterations (b) If after several iterations the bus voltages converge to V20.90-j0.10 pu 0.95-70.05 pu determine the line flows and line losses and the slack bus real and reactive power. 2 400 MW 320 Mvar Slack 0.0125 0.05 300 MW 270 Mvar FIGURE 52arrow_forwardThe one-line diagram of a simple power system is shown in Figure below. The neutral of each generator is grounded through a current-limiting reactor of 0.25/3 per unit on a 100-MVA base. The system data expressed in per unit on a common 100-MVA base is tabulated below. The generators are running on no-load at their rated voltage and rated frequency with their emfs in phase. G Stark Item Base MVA Voltage Rating X' x² 20 kV 20 kV 20/220 kV 20/220 kV 100 0.05 0.15 0.15 0.10 0.10 220 kV 0.125 0.125 0.30 0.15 0.25 025 0.7125 0.15 100 100 0.15 0.05 0.10 0.10 0.10 100 0.10 100 100 Lu La 220 kV 0.15 220 kV 0.35 100 A balanced three-phase fault at bus 3 through a fault impedance Zf= jo.I per unit. The magnitude of the fault current in amperes in phase b for this fault is: Select one: A. 345.3 B. 820.1 C. 312500 3888888 产产arrow_forward6. For a three bus power system assume bus 1 is the swing with a per unit voltage of 1.020 , bus 2 is a PQ bus with a per unit load of 2.0 + j0:5, and bus 3 is a PV bus with 1.0 per unit generation and a 1.0 voltage setpoint. The per unit line impedances are j0.1 between buses 1 and 2, j0.4 between buses 1 and 3, and j0.2 between buses 2 and 3. Using a flat start, use the Newton-Raphson approach to determine the first iteration phasor voltages at buses 2 and 3.arrow_forward
- b) A fault occurs at bus 4 of the network shown in Figure Q3. Pre-fault nodal voltages throughout the network are of 1 p.u. and the impedance of the electric arc is neglected. Sequence impedance parameters of the generator, transmission lines, and transformer are given in Figure Q3, where X and Y are the last two digits of your student number. jX(1) j0.1Y p.u. jX2)= j0.1Y p.u. jXko) = j0.1X p.u. V₁ = 120° p.u. V₂ = 120° p.u. (i) (ii) 0 jX(1) = j0.2 p.u. 1 jx(2) j0.2 p.u. 2 jX1(0) = j0.25 p.u. jXT(1) jXT(2) 종 3 j0.1X p.u. JX3(1) j0.1Y p.u. j0.1X p.u. JX3(2) j0.1Y p.u. jXT(0) j0.1X p.u. JX3(0)=j0.15 p.u. 0 = x = 1, jX2(1) j0.2Y p.u. V₁=1/0° p.u. jX(2(2) = j0.2Y p.u. jX2(0) = j0.3X p.u. = V3 = 120° p.u. Figure Q3. Circuit for problem 3b). For example, if your student number is c1700123, then: y = 7 = = jXa(r) = j0.13 p.u., jXa(z) = j0.13 p. u., and jXa(o) = j0.12 p. u. Assuming a balanced excitation, draw the positive, negative and zero sequence Thévenin equivalent circuits as seen from…arrow_forwardQ2\ The one-line diagram of a simple power system is shown in figure below. All impedances are expressed in per unit (pu) on a common MVA base. All resistances and shunt capacitances are neglected. The generators are operating on no load at their rated voltage. A three-phase fault occurs at bus 1 through a fault impedance of Zf = j0.08 per unit. Using Thevenin's theorem obtain the impedance to the point of fault and the fault current in per unit. Determine the bus voltages and line currents of generators during fault. X₁ = = 0.1 XT-0.1 3 1 to ojo XL=0.2 2 040 X₁ = 0.1arrow_forwardb) A fault occurs at bus 2 of the network shown in Figure Q3. Pre-fault nodal voltages throughout the network are of 1 p.u. and the impedance of the electric arc is neglected. Sequence impedance parameters of the generator, transmission lines, and transformer are given in Figure Q3, where X and Y are the last two digits of your student number. JX20 /0.1X p.u. jXa2) 0.1X p.u. JX20 j0.2Y p.u. V,= 120° p.u. V, 120° p.u. V, 120° p.u. jX4-70.2X p.u. jX2 j0.2X p.u. jX o 0.2Y p.u. jXncay J0.25 p.u. jXna J0.25 p.u. 3 jXno0.3 p.u. jXTu) /0.2Y p.u. jXra j0.2Y p.u. - j0.2Y p.u. Xp-10.1X p.u. jXa j0.1X p.u. jXp0)- j0.05 p.u. 0 Figure Q3. Circuit for problem 3b). For example, if your student number is c1700123, then: jXac1) = j0.22 p.u., jXac2) = j0.22 p.u., and jXaco) = j0.23 p. u. X-2 Y=8 (iv) Determine the short-circuit fault current for the case when a phase-to- phase fault occurs at bus 2.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
![Text book image](https://www.bartleby.com/isbn_cover_images/9781305632134/9781305632134_smallCoverImage.gif)
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning