Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN: 9781305632134
Author: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher: Cengage Learning
expand_more
expand_more
format_list_bulleted
Concept explainers
Question
error_outline
This textbook solution is under construction.
Students have asked these similar questions
The reactance of a generator is given as 0.1 pu based on the generator of 17 KV, 300 MVA. Determine the pu reactance on a base of 17 KV, 250 MVA. New pu reactance is.......
The reactance of a generator is given as 0.25 per-unit based on the generator’s of 18 kV, 500 MVA. Find its per-unit reactance on a base of 20 kV, 100 MVA.
a. 0.0505 b. 0.0605 c. 0.0405 d. 0.0606
two generators supplying a load.
Generator I has a no-load frequency
of 62.5 Hz and a slope Sp1 of I
MW/Hz. Generator 2 has a no-load
frequency of 62.0 Hz and a slope sp2
of I MW/Hz. The two generators are
supplying a real load totaling 2.5
MW at 0.8 PF lagging.
(a) At what frequency is this
system operating, and how
much power is supplied by
each of the two generators?
(b) Suppose an additional I-MW
load were attached to this
power system. What would
the new system frequency be,
and how much power would
Gl and G2 supply now?
Generator 1
VT V2
Generator 2
VTí
KVAR
KVAR
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- While the instantaneous electric power delivered by a single-phase generator under balanced steady-state conditions is a function of time havi ng two components of a constant and a double-frequency sinusoid, the total instantaneous electric power delivered by a three-phase generator under balanced steady-state conditions is a constant. (a) True (b) Falsearrow_forwardTwo generators are supplying a load. Both the generators have a no-load frequency of61.5 Hz and the slope sp of 1 MW/HZ. If they are supplying a real load of 2.0 MW at 0.8 pflagging, what would be the system frequency and power sharing between two generators?What measures can be taken to make the frequency 60 HZ. If an additional 1.0 MW load isconnected to the existing one what would the system frequency be.arrow_forwardA generating station has the following daily load cycle : Time (hours) 0-6 6-10 10-12 12–16 16-20 20-24 Load (MW) 20 25 30 25 35 Draw the load curve and find () maximum demand, (ií) units generated per day, (ii) average load, (iv) load factor, 20arrow_forward
- If the load draws a current of 2727 A, in phase, from a generator, which of the following statement is true? O A. The reactive power is flowing from generator to the load and the real power is flowing from the load to the generator. O B. Since the current is in phase with the generator voltage, both the real and reactive power is flowing from the generator to the load. O .Since the current is leading the generator, both the real and reactive power is flowing from the load to the generator. O D. The real power is flowing from generator to the load and the reactive power is flowing from the load to the generator. O E. None of the other choices are correctarrow_forwardA synchronous generator is rated 645 MVA, 24 kV, 0.9 pf lagging. It has a synchronous reactance 1.2 . The generator is feeding full load at 0.9 pf lagging at rated voltage. Calculate: (a) Excitation emf (E,) and power angle 8 (b) Reactive power drawn by the load Carry out calculations in pu form and convert the result to actual values.arrow_forwardQ₁/ Two identical S.G 600 Kv A, 48V; Connected in parallel to supply load when the field Current at the both generators are equal, and the prime mover at The generators have defferent speed droop Charactara stics. The one generator delivered 100 A and 0.9 lagging P.f. The other delivers 300d at 0.7 lag P.F. @ what is the real and reactive power of The load. how can we adjust the excitation to make both power fackops are equal.arrow_forward
- A generating station is to supply four regions of load whose peak loads are10 MW, 5 MW, 8 MW and 7 MW. The diversity factor at the station is 1-5 and the average annual load factor is 60%. Then the installed capacity is (25 to26)MW. O (24 to25)MW. O (23 to24)MW. Oarrow_forwardThere are only two generators in a power system, and these generators supply a total load of 10 MW. The no-load frequencies and droop constants for the generators are 51 Hz, 0.5Hz/MW, and 52 Hz, 1Hz/MW, respectively. What is the frequency of the combined system? What are the powers produced by individual generators? At this loading condi- tion, if the generator 1 is delivered to producc equal amount of power as the generator 2, what should be the no-load frequency of the generator 1?arrow_forwardA generating station has a connected load of (45MW) and a maximum demand is (15MW). with average demand of (6300KW), the value of demand * factor and load factor are 0.55, 1.5 0.33 ,0.42 O 3,0.14 Oarrow_forward
- Can ripple factors be grater then unity . Justify?arrow_forwardQa1. The three phases of a generator can be connected in either delia (D) or wye (Y) connection. List two advantages of three phase system over a single phase system. Also write mathematical relationship between the phase voltage and the ine voltage, and the phase current and the line current for both delia (D) and wye (Y) connections. Please answer in typing format please..arrow_forwardtwo synchronous generators are connected in parallel, feeding a load together. the frequency of the first generator in the no-load State is 52 Hz and the slope of the characteristic is 1 MW/Hz. the total power of the load fed by these two generators is 2.5 MW and the power coefficient is 0.6 inductive. by drawing the characteristic curve of the system;a) what is the frequency of the system when the load in question is fed, and how do the two generators share the load between themselvesb) if a load of 0.5 MW is added to the system, find the operating frequency of the new system and the powers given by each generatorc) if a second load of 0.5 MW is connected to the system, the idle operating frequency of the second generator is increased by 0.5 Hz, what happens to the operating frequency of the system and the power values given by the generatorsarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage LearningDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
Working Principle of DC Motor (animation of elementary model); Author: chrvoje engineering;https://www.youtube.com/watch?v=j_F4limaHYI;License: Standard Youtube License