When a load is connected to a power line with a frequency of 230V (rms) 50 Hz, it draws 4500 W at a power factor of 0.80. Find the required capacitance value to increase the power factor to 0.85.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.7P: Let a 100V sinusoidal source be connected to a series combination of a 3 resistor, an 8 inductor,...
icon
Related questions
Question

When a load is connected to a power line with a frequency of 230V (rms) 50 Hz, it draws 4500 W at a power factor of 0.80. Find the required capacitance value to increase the power factor to 0.85.

Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Single Phase Induction Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.