Two transformers A and B have the following data Transformer A: 6600/440 V, (250 KVA ) requires ( 6%) of rated voltage to circulate (90%) of full load current at power factor (0.25) when the low voltage winding is short circuited and the no load loss is equal to (2500 W). Transformer B: 6600/420 V, (600 KVA) requires (9%) of rated voltage to circulate (80%) of full load current at power factor (0.16) when low voltage winding is short circuited and no load loss is equal to (4500 W). Calculate the followings:

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.34P: Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance...
icon
Related questions
Question
Q
Two transformers A and B have the following data
Transformer A: 6600/440 V, (250 KVA ) requires ( 6%) of rated voltage to
circulate (90%) of full load current at power factor (0.25) when the low voltage
winding is short circuited and the no load loss is equal to (2500 W).
Transformer B: 6600/420 V, (600 KVA) requires (9%) of rated voltage to
circulate (80%) of full load current at power factor (0.16) when low voltage
winding is short circuited and no load loss is equal to (4500 W).
Calculate the followings:
The maximum efficiency of each transformer at power factor (0.75) lagging.
Transcribed Image Text:Q Two transformers A and B have the following data Transformer A: 6600/440 V, (250 KVA ) requires ( 6%) of rated voltage to circulate (90%) of full load current at power factor (0.25) when the low voltage winding is short circuited and the no load loss is equal to (2500 W). Transformer B: 6600/420 V, (600 KVA) requires (9%) of rated voltage to circulate (80%) of full load current at power factor (0.16) when low voltage winding is short circuited and no load loss is equal to (4500 W). Calculate the followings: The maximum efficiency of each transformer at power factor (0.75) lagging.
Two transformers A and B have the following data
Transformer A: 6600/440 V, (250 KVA ) requires ( 6%) of rated voltage to
circulate (90%) of full load current at power factor (0.25) when the low voltage
winding is short circuited and the no load loss is equal to (2500 W).
Transformer B: 6600/420 V, (600 KVA) requires (9%) of rated voltage to
circulate (80%) of full load current at power factor (0.16) when low voltage
winding is short circuited and no load loss is equal to (4500 W).
Calculate the followings:
The terminal voltage when transformer A is supplying half load at power
factor (0.6) lagging and transformer B is supplying (85%) of full load at power
factor (0.85) leading.
Transcribed Image Text:Two transformers A and B have the following data Transformer A: 6600/440 V, (250 KVA ) requires ( 6%) of rated voltage to circulate (90%) of full load current at power factor (0.25) when the low voltage winding is short circuited and the no load loss is equal to (2500 W). Transformer B: 6600/420 V, (600 KVA) requires (9%) of rated voltage to circulate (80%) of full load current at power factor (0.16) when low voltage winding is short circuited and no load loss is equal to (4500 W). Calculate the followings: The terminal voltage when transformer A is supplying half load at power factor (0.6) lagging and transformer B is supplying (85%) of full load at power factor (0.85) leading.
Expert Solution
steps

Step by step

Solved in 5 steps with 4 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L