The steady-state voltage drop between the load and the sending end of the line seen in (Figure 1) is excessive. Suppose that V-4950/0° V (rms). A capacitor is placed in parallel with the 192 kVA load and is adjusted until the steady-state voltage at the sending end of the line has the same magnitude as the voltage at the load end, that is, 4950 V (rms). The 192 kVA load is operating at a power factor of 0.8 lag. Part A Calculate the size of the capacitor in microfarads if the circuit is operating at 60 Hz. In selecting the capacitance, use the value that results in the lowest possible power loss in the line. Express your answer in microfarads to three significant figures. ▸ View Available Hint(s) Avec C= 22.8 Submit Previous Answers X Incorrect; Try Again; 5 attempts remaining Provide Feedback ? F

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter6: Power Flows
Section: Chapter Questions
Problem 6.61P
icon
Related questions
Question
The steady-state voltage drop between the load and the
sending end of the line seen in (Figure 1) is excessive
Suppose that V-4950/0° V (rms). A capacitor is
placed in parallel with the 192 kVA load and is adjusted
until the steady-state voltage at the sending end of the line
has the same magnitude as the voltage at the load end,
that is, 4950 V (rms). The 192 kVA load is operating at a
power factor of 0.8 lag.
Part A
Calculate the size of the capacitor in microfarads if the circuit is operating at 60 Hz. In selecting the capacitance, use the value that results in the lowest possible power loss in the line.
Express your answer in microfarads to three significant figures.
▸ View Available Hint(s)
Figure
1 of 1
202
1100
192 kVA
0.8
lag
ΜΕ ΑΣΦ. 11 vec
C= 22.8
Submit
Previous Answers
Incorrect; Try Again; 5 attempts remaining
Provide Feedback
?
F
Transcribed Image Text:The steady-state voltage drop between the load and the sending end of the line seen in (Figure 1) is excessive Suppose that V-4950/0° V (rms). A capacitor is placed in parallel with the 192 kVA load and is adjusted until the steady-state voltage at the sending end of the line has the same magnitude as the voltage at the load end, that is, 4950 V (rms). The 192 kVA load is operating at a power factor of 0.8 lag. Part A Calculate the size of the capacitor in microfarads if the circuit is operating at 60 Hz. In selecting the capacitance, use the value that results in the lowest possible power loss in the line. Express your answer in microfarads to three significant figures. ▸ View Available Hint(s) Figure 1 of 1 202 1100 192 kVA 0.8 lag ΜΕ ΑΣΦ. 11 vec C= 22.8 Submit Previous Answers Incorrect; Try Again; 5 attempts remaining Provide Feedback ? F
Expert Solution
steps

Step by step

Solved in 5 steps with 7 images

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning