The results of open-circuit test and short-circuit test for a 60 kVA , 2400/500 V single phase transformer is given below: Voltage Current Power Open Circuit Test (LV side measurement) 450V 2.5A 500W Short Circuit Test (HV side measurement) 50V 25A 800W Determine: 1. the equivalent core loss resistance and magnetizing reactance referred to HV side; 2. the equivalent winding resistance and flux leakage reactance referred to HV side; 3. the voltage regulation at full-load and power factor of 0.85 lagging 4. the maximum efficiency
Three-Phase Transformers
Three-segment transformers are a type of transformer used to transform voltages of electrical systems into three ranges. Two type transformers are shell-type transformer and core type transformer. In brief, it could be described because of the exquisite kinds of configurations.
Transformer
Ever since electricity has been created, people have started using it in its entirety. We see many types of Transformers in the neighborhoods. Some are smaller in size and some are very large. They are used according to their requirements. Many of us have seen the electrical transformer but they do not know what work they are engaged in.
The results of open-circuit test and short-circuit test for a 60 kVA , 2400/500 V single phase transformer is given below:
Voltage | Current | Power | |
Open Circuit Test (LV side measurement) |
450V | 2.5A | 500W |
Short Circuit Test (HV side measurement) | 50V | 25A | 800W |
Determine:
1. the equivalent core loss resistance and magnetizing reactance referred to HV side;
2. the equivalent winding resistance and flux leakage reactance referred to HV side;
3. the voltage regulation at full-load and power factor of 0.85 lagging
4. the maximum efficiency