The refrigeration system of a food production firm is run using the Reversed Carnot Cycle. The temperature of the hot refrigerant supply in the system should be 52°C, while the temperature of the sink should be -14°C. Its capacity is projected to be at least 24 tons. It's important not to disregard losses. Find and Show unit analysis and conversion: a. COP and COP of Heat Pump b. Heat rejected from the system in kW c. Network in, Hp and Energy Efficiency Ratio

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter44: Geothermal Heat Pumps
Section: Chapter Questions
Problem 13RQ: If 14 gpm of water is flowing through an open-loop heat pump with a temperature difference of 7F,...
icon
Related questions
Question

The refrigeration system of a food production firm is run using the Reversed Carnot Cycle. The temperature of the hot refrigerant supply in the system should be 52°C, while the temperature of the sink should be -14°C. Its capacity is projected to be at least 24 tons. It's important not to disregard losses.

Find and Show unit analysis and conversion:

a. COP and COP of Heat Pump

b. Heat rejected from the system in kW

c. Network in, Hp and Energy Efficiency Ratio

Expert Solution
steps

Step by step

Solved in 5 steps

Blurred answer
Knowledge Booster
Available Energy
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning