Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN: 9780133923605
Author: Robert L. Boylestad
Publisher: PEARSON
Bartleby Related Questions Icon

Related questions

Question
Q4) Consider the system shown in Figure Q3. This is a PID control of a second-order
plant G(s). Assume that disturbances d(s) enter the system as shown in the
diagram. It is assumed that the reference input F(s) is normally held constant, and
the response characteristics to disturbances are a very important consideration in
this system.
d(s)
F(s)-
C(s)
G(s)
y(s)
H(s)
Figure Q3
1
K(as + 1)(bs + 1)
G(s)
C(s) =
H(s) = 1
s² + 7s + 10'
In the absence of the reference input i.e. F(s) = 0, derive the closed-loop
transfer function between y(s) and d(s).
a)
b)
The performance specification requires that the unit step disturbance
response be such that the settling time be approximately half a second and the
system has reasonable damping. We may interpret the specification as 3 =
0.8 and wn = 8 for the dominant closed-loop poles. We may choose the third
pole at s = - 10 so that the effect of this real pole on the response is small.
Derive the required characteristic polynomial that satisfies the above
performance specification.
c) Using the result in a) and b), calculate the controller parameters ab, a + b
and K. Hence write down the controller transfer function C(s).
expand button
Transcribed Image Text:Q4) Consider the system shown in Figure Q3. This is a PID control of a second-order plant G(s). Assume that disturbances d(s) enter the system as shown in the diagram. It is assumed that the reference input F(s) is normally held constant, and the response characteristics to disturbances are a very important consideration in this system. d(s) F(s)- C(s) G(s) y(s) H(s) Figure Q3 1 K(as + 1)(bs + 1) G(s) C(s) = H(s) = 1 s² + 7s + 10' In the absence of the reference input i.e. F(s) = 0, derive the closed-loop transfer function between y(s) and d(s). a) b) The performance specification requires that the unit step disturbance response be such that the settling time be approximately half a second and the system has reasonable damping. We may interpret the specification as 3 = 0.8 and wn = 8 for the dominant closed-loop poles. We may choose the third pole at s = - 10 so that the effect of this real pole on the response is small. Derive the required characteristic polynomial that satisfies the above performance specification. c) Using the result in a) and b), calculate the controller parameters ab, a + b and K. Hence write down the controller transfer function C(s).
Expert Solution
Check Mark
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Text book image
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:PEARSON
Text book image
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
Text book image
Programmable Logic Controllers
Electrical Engineering
ISBN:9780073373843
Author:Frank D. Petruzella
Publisher:McGraw-Hill Education
Text book image
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:9780078028229
Author:Charles K Alexander, Matthew Sadiku
Publisher:McGraw-Hill Education
Text book image
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:9780134746968
Author:James W. Nilsson, Susan Riedel
Publisher:PEARSON
Text book image
Engineering Electromagnetics
Electrical Engineering
ISBN:9780078028151
Author:Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:Mcgraw-hill Education,