Please calculate the depth to the plastic centroid from the compression face, dpc, and the design capacity in pure compression, Nuo. a) b) c) Please determine whether this column is short or slender. Please calculate the design capacities at balanced failure, Nub and Mub d) Regardless of your answer to the previous part, consider the column to be slender. Please calculate the moment magnifier for this braced column, Sp. 2N20 к 300 400mm 50 I Lu=10.0m Idealised end restraints ė-100mm + N* ма 0 400 4N32 M* 600 * Section dpc. Expected BMD Over/....5) Eccentricity of dpc

Steel Design (Activate Learning with these NEW titles from Engineering!)
6th Edition
ISBN:9781337094740
Author:Segui, William T.
Publisher:Segui, William T.
Chapter5: Beams
Section: Chapter Questions
Problem 5.11.4P
icon
Related questions
Question

An inverted T RC column is proposed. Its cross-section and reinforcement is shown in the sketch below. The concrete characteristic strength is to be fc' = 32.MPa. The column can be considered to be braced with an unsupported length Lu = 10.0 m. The idealised end restraint conditions are shown in the sketch below. The nominal axial compression loads (including self-weight) that the column is to carry are:

Permanent action (G), NG = 2000 kN and Imposed action (Q), NQ = 1000 kN.

The line of action of the applied axial loads is at an eccentricity of e = 1 00 mm. The direction of the eccentricity is such that the induced moment will cause tension at the face with 4N32 reinforcement. The eccentricity and expected BMD for the column are shown in the sketch below (this BMD represents a single curvature along the length of the column). For consideration of the induced moment, I have calculated that the radius of gyration is r = 221 mm about the horizontal axis.

Please calculate the depth to the plastic centroid from the compression face, dpc, and the
design capacity in pure compression, Nuo.
a)
b)
c)
Please determine whether this column is short or slender.
Please calculate the design capacities at balanced failure, Nub and Mub
d) Regardless of your answer to the previous part, consider the column to be slender. Please
calculate the moment magnifier for this braced column, Sp.
2N20
к
300
400mm
50
I
Lu=10.0m
Idealised end restraints
ė-100mm
+
N*
ма
0
400
4N32
M*
600
* Section
dpc.
Expected BMD
Over/....5)
Eccentricity of dpc
Transcribed Image Text:Please calculate the depth to the plastic centroid from the compression face, dpc, and the design capacity in pure compression, Nuo. a) b) c) Please determine whether this column is short or slender. Please calculate the design capacities at balanced failure, Nub and Mub d) Regardless of your answer to the previous part, consider the column to be slender. Please calculate the moment magnifier for this braced column, Sp. 2N20 к 300 400mm 50 I Lu=10.0m Idealised end restraints ė-100mm + N* ма 0 400 4N32 M* 600 * Section dpc. Expected BMD Over/....5) Eccentricity of dpc
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Steel Design (Activate Learning with these NEW ti…
Steel Design (Activate Learning with these NEW ti…
Civil Engineering
ISBN:
9781337094740
Author:
Segui, William T.
Publisher:
Cengage Learning