In a three-phase transmission line with a length of 150 km, a voltage of 250 kV and a frequency of 50 Hz, the diameter of the steel-cored aluminum conductors is 18 mm, the roughness coefficient of the conductors is 0.6, and the spacing between the conductors is 6 m. Since the average air temperature is 27˚ C and the air pressure is 762 mmHg along the line, find the corona voltage around the conductor and the total loss of the line according to the Peek formula.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter4: Transmission Line Parameters
Section: Chapter Questions
Problem 4.13P: A single-phase overhead transmission line consists of two solid aluminum conductors having a radius...
icon
Related questions
Question

In a three-phase transmission line with a length of 150 km, a voltage of 250 kV and a frequency of 50 Hz, the diameter of the steel-cored aluminum conductors is 18 mm, the roughness coefficient of the conductors is 0.6, and the spacing between the conductors is 6 m. Since the average air temperature is 27˚ C and the air pressure is 762 mmHg along the line, find the corona voltage around the conductor and the total loss of the line according to the Peek formula.

Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning